Çawnên Cemalî yên Jenerator û Sisteman Pêşkêşkirina
Çawnên jenerator di navbera çawnên derveyî û derveyî de were girîng kirin:
Çawnên motûrên sereke (wêgot, turbine) ji natûre mekanîkî ne û li ser dizaynên pîçeyekê hatine nîsandin, lê divê bi parastinan jeneratoran binihêrin da ku ji bo kirinên tripping.
Tîpanên Çawnên Derveyî
1. Çawnên Stator
2. Çawnên Rotor
3. Loss of Field/Excitation
4. Out-of-Step Operation
5. Motor Operation
6. Çawnên Mekanîkî
Mechanism of Rotor Overheating
Currents unbalanced stator (e.g., negative phase sequence) eddy currents di rotor de di duji system frequency (100/120 Hz) de, vê li ser derxistina localized re hatiye. Vê weakens rotor retaining wedges û rings.
Tîpanên Çawnên Derveyî
Abnormalities Power System
Generator Protection Devices
Schemes Key Protection
1. Stator Fault Protection
2. Rotor Fault Protection
3. Unbalanced Loading Protection
4. Overheating Protection
5. Mechanical Protection
6. Backup and Supplementary Protection
Protection Principles
Rotor Winding Fault Protection Mechanisms
Wound rotor winding short-circuit faults are safeguarded by overcurrent relays, which trip the generator upon detecting abnormal current surges. Earth faults pose another risk to rotor windings, though their protection requires specialized approaches.
In large thermal generators, rotor û field windings are typically ungrounded, meaning a single ground fault does not produce a fault current. However, such a fault elevates the potential of the entire field û exciter system. Extra voltages induced by opening the field û main generator breaker—especially during fault conditions—can stress the field winding insulation, potentially causing a second ground fault. A second fault may lead to localized iron heating, rotor distortion, û dangerous mechanical unbalance.
Rotor earth-fault protection often employs a relay that monitors insulation by applying an auxiliary AC voltage to the rotor. Alternatively, a voltage relay is used in series with a high-resistance network (commonly a combination of linear û non-linear resistors) across the rotor circuit. The center point of this network connects to ground via a sensitive relay coil (ANSI/IEEE/IEC code 64). Modern protection schemes increasingly favor combinations of linear û non-linear resistors for improved fault detection û insulation monitoring.
Loss of Field and Overexcitation Protection Mechanisms
Loss of field protection employs a relay to detect changes in reactive power flow. A typical scheme uses an Offset Mho (impedance) relay— a single-phase device supplied by generator current transformers (CTs) û voltage transformers (VTs)—to measure load impedance. The relay triggers when the impedance falls within its operating characteristic. A timing relay initiates generator tripping if leading reactive power persists for 1 second (standard timing).
Overexcitation Protection
To prevent core saturation during startup û shutdown, overexcitation protection (ANSI/IEEE/IEC code 59) is implemented, based on the relationship:B = V/f
where:
Core flux must stay below the saturation point, meaning voltage can only increase proportionally with frequency (speed). Rapid excitation increases risk overexcitation, detected by Volts per Hertz relays. These relays feature linear characteristics û trip when V/f exceeds set thresholds.
Stator and Rotor Overheating Protection
Reliable protection systems are critical to minimize damage û repair time, as generators are among the most expensive power system components.
This protection utilizes a relay that compares currents in two phases via current transformers (CTs), as illustrated in Figure 2. The protective settings are determined by the maximum time the rotor can endure overheating, defined by the equation K = I²t (derived from Joule's law), where I is the negative sequence current û t is the duration.
Manufacturer-specified typical time-current curves for this condition vary based on the prime mover type, as shown in the referenced diagram.
Reverse Power, Out-of-Step, û Frequency/Voltage Protection Systems
Reverse Power Protection (ANSI/IEEE/IEC Code 32)
This protection employs a power directional relay to monitor generator load, supplied by CTs û VTs (see Figure 3). The relay activates upon detecting negative power flow—indicating the generator is drawing power from the grid (motor operation)—û triggers tripping to prevent turbine damage.
Out-of-Step Protection
Designed to detect power system disturbances (not generator faults), this protection identifies pole slipping when the generator loses synchronism. It trips the generator breakers while keeping the turbine running, allowing re-synchronization after the disturbance clears.
Frequency and Voltage Protection
Under/Over Frequency Protection (ANSI/IEEE/IEC Code 81)
Under/Over Voltage Relays (Codes 27/59)
Monitor û control voltage deviations to protect equipment from stress û damage.
Phase Supplementary Start Protection
Prevents starting the generator into a fault û loaded condition. Low-set overcurrent relays engage only when frequency is below 52 Hz (for 60 Hz systems) û 42 Hz (for 50 Hz systems), ensuring protection during startup transients.
External Short-Circuit Protection
Overcurrent relays (50, 50N, 51, 51N) detect û clear faults on the external network, safeguarding the generator from excessive fault currents.
These protection schemes collectively address operational anomalies—from power flow reversals to system-wide disturbances—ensuring generator integrity û grid stability.