Application of Grounding Transformers in Generator Neutral Grounding Resistor Cabinets

Echo
Field: Transformer Analysis
China

When the capacitive current of a generator is slightly large, a resistor must be added at the generator neutral point to avoid power-frequency overvoltage that could damage the motor insulation during a ground fault. The damping effect of this resistor reduces the overvoltage and limits the ground fault current. During a single-phase ground fault of the generator, the neutral-to-ground voltage equals the phase voltage, typically several kilovolts or even above 10 kV. Therefore, this resistor must have a very high resistance value, which is economically expensive.

In general, a large high-value resistor is not directly connected between the generator neutral point and ground. Instead, a combination of a small resistor and a grounding transformer is used. The primary winding of the grounding transformer is connected between the neutral point and ground, while a small resistor is connected to the secondary winding. According to the formula, the impedance reflected to the primary side equals the secondary-side resistance multiplied by the square of the transformer turns ratio. Thus, with a grounding transformer, a small resistor can function as a high-value resistor.

Grounding earthing Transformer.jpg

During a generator ground fault, the neutral-to-ground voltage (equal to the voltage applied across the primary winding of the grounding transformer) induces a corresponding voltage on the secondary winding, which can be used as a basis for ground fault protection—i.e., the grounding transformer can extract zero-sequence voltage.

The rated primary voltage of the transformer is 1.05 times the generator phase voltage, and the rated secondary voltage is 100 volts. It is easy to connect a resistor to the secondary winding, and a 100 V resistor is readily available. Although the reflected ground fault current on the primary side becomes large due to the transformer ratio, a generator ground fault should trigger immediate tripping and shutdown, so the current duration is very short, resulting in minimal thermal effects, which poses no problem.

Give a tip and encourage the author!
Recommended
What are the classification types of power transformers and their applications in energy storage systems?
Power transformers are core primary equipment in power systems that realize electrical energy transmission and voltage conversion. Through the principle of electromagnetic induction, they convert AC power of one voltage level to another or multiple voltage levels. In the transmission and distribution process, they play a critical role in "step-up transmission and step-down distribution," while in energy storage systems, they perform voltage step-up and step-down functions, ensuring efficient pow
12/23/2025
Intelligent Grounding Transformers for Island Grid Support
1. Project BackgroundDistributed photovoltaic (PV) and energy storage projects are developing rapidly across Vietnam and Southeast Asia, yet face significant challenges:1.1 Grid Instability:Vietnam's power grid experiences frequent fluctuations (particularly in northern industrial zones). In 2023, coal power shortages triggered large-scale blackouts, resulting in daily losses exceeding USD 5 million. Traditional PV systems lack effective neutral grounding management capabilities, making equipmen
12/18/2025
Functions and Selection of Grounding Transformers in Photovoltaic Power Stations
1.Neutral Point Establishment and System StabilityIn photovoltaic power stations, grounding transformers effectively establish a system neutral point. According to relevant power regulations, this neutral point ensures the system maintains certain stability during asymmetric faults, functioning like a "stabilizer" for the entire power system.2.Overvoltage Limitation CapabilityFor photovoltaic power stations, grounding transformers can effectively limit overvoltages. Generally, they can control o
12/17/2025
Transformer Protection Settings: Zero-Sequence & Overvoltage Guide
1. Zero-Sequence Overcurrent ProtectionThe operating current for zero-sequence overcurrent protection of grounding transformers is typically determined based on the transformer's rated current and the maximum allowable zero-sequence current during system ground faults. The general setting range is approximately 0.1 to 0.3 times the rated current, with operating time usually set between 0.5 to 1 second to quickly clear ground faults.2.Overvoltage ProtectionOvervoltage protection is a critical com
12/17/2025
Related Products
Send inquiry
+86
Click to upload file

IEE Business will not sell or share your personal information.

Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.