• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


ਵਿੱਕ ਫਰੀਕਵੈਂਸੀ ਕੰਟਰੋਲ (LFC) ਅਤੇ ਟਰਬਾਈਨ ਗਵਰਨਰ ਕੰਟਰੋਲ (TGC) ਦੀ ਪਾਵਰ ਸਿਸਟਮ ਵਿੱਚ ਵਰਤੋਂ

Edwiin
Edwiin
ਫੀਲਡ: ਪावਰ ਸਵਿੱਚ
China

thermal generating units di takrifi khurd

Bijli banane de upar renewable te non-renewable energy resources da vartaa janda hai. Thermal generating units power production da ek traditional tareeka hain. Iss units vich, coal, nuclear energy, natural gas, biofuel, te biogas da istemal karke boiler vich combustion kiyaa janda hai.

Generating unit da boiler ek bahut hi complex system hai. Iska sabse simple visualization yeh hai ke iska andar pipes se ghira hua ek chamber hota hai, jisme pani continuous tarah se circulates karta hai. Boiler vich fuel ka combustion se nikla thermal energy iss pani ko transfer kiya jata hai. Is process ke dauraan, pani high pressure (150 ksc se 380 ksc tak, design par depend karta hai) aur high temperature (530°C se 732°C tak, design specifications par depend karta hai) wala dry saturated steam mein transform ho jata hai.

Iss saturated steam ko turbine mein feed kiya jata hai, jahaan ise expand kiya jata hai aur ise temperature drop hoti hai. Is expansion process ke dauraan, steam apna thermal energy turbine shaft ke rotational energy mein transfer karta hai. Steam ki turbine mein entry control valve se regulate ki jati hai, jo turbine ke governing system se govern ki jati hai. Is prakar, turbine ki active power output governor se control ki jati hai. Turbine synchronous generator se coupled hota hai.

Synchronous generator turbine ki mechanical energy ko electrical energy mein convert karta hai. Synchronous generators nominal frequency par generally 11 kV se 26 kV ke beech voltage par electricity produce karte hain. Iss voltage ko phir 220 kV/400 kV/765 kV tak generating transformer se step up kiya jata hai transmission ke liye power grid mein. Power system studies mein, iss entire integrated system ko generating unit ke roop mein refer kiya jata hai.

Turbine Governor Control (TGC)

Jaise pehle mention kiya gaya, governor control valve ke position ko control karke turbine mein active power flow ko regulate karta hai. Ek hydraulic governor ko integral controller ke roop mein model kiya ja sakta hai jo turbine ki actual rotational speed se feedback leta hai. Figure 1 governor ke operation ko speed-control mode mein dikhata hai.

Turbine ki actual speed ko reference speed (nominal grid frequency se corresponding) ke against compare kiya jata hai. Resulting speed error signal (∆ωᵣ) phir governor mein feed kiya jata hai. Iss error signal ke based par, governor control valve position adjust karta hai: agar positive error signal detect kiya jata hai (actual frequency nominal frequency se zyada hai), to governor slightly valve band karta hai; vice versa, negative error signal receive hone par valve open karta hai.

“R” governor droop setting represent karta hai, jo typically 3% se 8% tak range karta hai. Mathematically, it is defined as:
R = (per unit change in frequency) / (per unit change in power)

Droop settings multiple generating units ke stable parallel operation ke liye critical hain, kyunki ye determine karte hain ke control area vich load kaise share kiya jaye. Units jo chota droop value rakhte hain, automatically bada share of the load assume karte hain.

Control Area

Power system mein generating units aur loads vast geographical regions par distributed hote hain. Stability maintain karne ke liye, entire grid smaller control areas (primarily based on geography) mein divided hota hai. This division enables:

  • Efficient load flow calculations

  • Precise control of frequency and power balance

Ek control area vich multiple generating units aur loads coexist karte hain. Subdividing the power system into control areas serves several key objectives:

1. Load Frequency Control

This framework enables the application of load-frequency control methods to maintain grid frequency—a concept explored in greater detail later.

2. Determination of Scheduled Interchanges

If a control area’s generation falls short of its load demand, power flows into the area from neighboring control areas via tie lines (and vice versa).

3. Effective Load Sharing

Load demand varies throughout the day (e.g., lower at night, peaking in the morning and evening). Control areas simplify the process of:

  • Allocating load across units based on projected demand and unit capacity

  • Calculating scheduled power interchanges with other control areas

Power Balance

Electrical energy is consumed in real-time (it cannot be stored on a large scale). Thus, power balance is a fundamental requirement:
Power Generated (P₉) = Load Demand (Pd) + Transmission Losses (Pₗ)

Transmission losses typically account for ~2% of generated power and are often neglected when focusing on frequency control. For simplicity, we approximate:
Power Generated (P₉) ≈ Load Demand (Pd)

Frequency Variation

Grid frequency fluctuates due to mismatches between load demand and generation. While minor deviations are stabilized by system inertia, significant gaps (e.g., unit trips, large load changes) can cause frequency to vary by ±5%. Key scenarios include:

  • Unplanned outages of generating units or transmission lines

  • Sudden connection/disconnection of large loads

In most cases (e.g., unit/line trips, large load connection), demand exceeds generation, causing frequency to drop. Conversely, if a transmission line serving a large load trips, generation may exceed demand, causing frequency to rise. Though the system responds oppositely to these scenarios, understanding frequency dips suffices to grasp both behaviors.

Why Frequency Dips Occur

Two inherent system behaviors drive frequency dips:

1. Load Dampening

Induction motors (e.g., household fans, industrial drives) dominate grid loads. Their power consumption is frequency-dependent: a 1% frequency reduction typically reduces active power consumption by ~2% in large systems. When new loads connect, frequency drops, and existing induction loads automatically consume less power—partially mitigating the demand-generation gap.

2. Kinetic Energy Release from Turbine-Generator (TG) Sets

Conventional TG sets have massive rotors (often >25 tonnes) spinning at 3000 RPM (for 50Hz grids). When demand exceeds generation, these rotors temporarily supply stored kinetic energy (for 3–5 seconds, depending on inertia). As rotors slow down, grid frequency drops.

Frequency Control

Load-frequency control (LFC) restores grid frequency to its nominal value after demand-generation mismatches. Two tiers of control exist:

1. Primary Frequency Control

At the unit level, the turbine’s governing system adjusts speed (and thus frequency). As shown earlier, each unit modulates steam input based on frequency deviations. The full primary control loop for a generating station is depicted in the figure below.

2. Secondary Frequency Control

This involves coordinated control across multiple units in different control areas, ensuring long-term frequency stability and optimal load sharing.

Primary Frequency Control Limitations

Primary frequency control alone results in a steady-state frequency deviation, influenced by the governor droop characteristic and load frequency sensitivity. This occurs because individual units adjust speed without considering where new loads are connected or how much load is added. Without such contextual assessment, power balance cannot be fully restored, and frequency deviation persists. Following primary control actions, the steady-state frequency error may be either positive or negative.

Secondary Frequency Control

Restoring system frequency to its nominal value requires secondary control, which accounts for new load locations and adjusts reference setpoints for selected units. When load increases in a control area, generation within that area must rise to:

  • Maintain demand-generation balance at the control area level

  • Keep scheduled interchanges with adjacent areas within pre-defined limits

To achieve this:

  • Automatic Generation Control (AGC) assigns specific units in each control area for secondary control.

  • A frequency bias loop is added to their control systems, providing real-time corrective signals based on load flow calculations.

Once revised load setpoints are issued, units begin adjusting generation. Due to the mechanical nature of power production, it takes 25–30 minutes for units to reach their scheduled outputs. When all generating stations achieve target generation, power balance is reinstated, and frequency returns to nominal.

The overall response of the system with the primary and secondary frequency control can be understood by the graph below.

System Response to Load Increase (A-B-C-D)
A-B: Transient Kinetic Energy Release

Before point A, the system operates in power balance. At point A, load suddenly increases from P₀ to P₀ + ∆P. A 3–5 second delay occurs before the governor responds. During this interval, the rotor's stored kinetic energy supplies the excess load, causing rotor speed to drop and frequency to dip to a minimum value f₁.

B-C: Primary Frequency Control Action

At ~5 seconds, the governor initiates speed control, increasing steam input to restore rotor speed. This phase lasts 20–25 seconds (dependent on the frequency dip magnitude). As discussed, primary control alone leaves a steady-state frequency error ∆f due to governor droop.

C-D: Secondary Frequency Control (AGC Activation)

Once frequency stabilizes, secondary control (via AGC) adjusts generation for selected units in each control area. This process considers:

  • New load reference setpoints

  • Frequency bias signals from real-time load flow calculations

Generation adjustments are limited by the units’ design ramp rates, taking several minutes to complete. Upon finishing, scheduled interchanges return to pre-calculated values, and the system achieves a new power balance with nominal frequency.

ਟਿਪ ਦਿਓ ਅਤੇ ਲੇਖਕ ਨੂੰ ਉਤਸ਼ਾਹਿਤ ਕਰੋ!
ਮਨਖੜਦ ਵਾਲਾ
ਫੋਟੋਵੋਲਟੈਕ ਬਿਜਲੀ ਉਤਪਾਦਨ ਸਿਸਟਮਾਂ ਦੀ ਰਚਨਾ ਅਤੇ ਕਾਰਵਾਈ ਦਾ ਸਿਧਾਂਤ
ਫੋਟੋਵੋਲਟੈਕ ਬਿਜਲੀ ਉਤਪਾਦਨ ਸਿਸਟਮਾਂ ਦੀ ਰਚਨਾ ਅਤੇ ਕਾਰਵਾਈ ਦਾ ਸਿਧਾਂਤ
ਫੋਟੋਵੋਲਟਾਈਕ (PV) ਪ੍ਰਸ਼ਕਤ ਜਨਿਤ ਸਿਸਟਮਾਂ ਦੀ ਰਚਨਾ ਅਤੇ ਕਾਰਜੀ ਸਿਧਾਂਤਫੋਟੋਵੋਲਟਾਈਕ (PV) ਪ੍ਰਸ਼ਕਤ ਜਨਿਤ ਸਿਸਟਮ ਮੁੱਖ ਰੂਪ ਵਿੱਚ PV ਮੌਡਯੂਲ, ਕਨਟਰੋਲਰ, ਇਨਵਰਟਰ, ਬੈਟਰੀਆਂ, ਅਤੇ ਹੋਰ ਸਹਾਇਕ ਸਾਮਗਰੀ (ਗ੍ਰਿਡ-ਕੰਨੈਕਟਡ ਸਿਸਟਮਾਂ ਲਈ ਬੈਟਰੀਆਂ ਦੀ ਲੋੜ ਨਹੀਂ ਹੁੰਦੀ) ਨਾਲ ਬਣਦਾ ਹੈ। ਇਸ ਦੀ ਪ੍ਰਕਾਰ ਉਸ ਦੇ ਆਧਾਰ ਤੇ ਵੰਡਿਆ ਜਾਂਦਾ ਹੈ ਕਿ ਇਹ ਸਾਰਵਭੌਮਿਕ ਪ੍ਰਸ਼ਕਤ ਗ੍ਰਿਡ ਉੱਤੇ ਨਿਰਭਰ ਕਰਦਾ ਹੈ ਜਾਂ ਨਹੀਂ। ਗ੍ਰਿਡ-ਸੀਗ਼ਿਲ ਸਿਸਟਮ ਗ੍ਰਿਡ ਦੀ ਵਿਚਕਾਰ ਸਹਾਇਕ ਰੂਪ ਵਿੱਚ ਕਾਮ ਕਰਦੇ ਹਨ। ਇਹ ਊਰਜਾ ਸਟੋਰੇਜ ਬੈਟਰੀਆਂ ਨਾਲ ਸਹਾਇਤ ਹੁੰਦੇ ਹਨ ਜਿਸ ਦੁਆਰਾ ਸਿਸਟਮ ਦੀ ਸਥਿਰ ਪ੍ਰਸ਼ਕਤ ਸਹਾਇਤ ਕੀਤੀ ਜਾਂਦੀ ਹੈ, ਰਾਤ ਦ
Encyclopedia
10/09/2025
ਕਿਵੇਂ ਇੱਕ PV ਪਲਾਂਟ ਦੀ ਮੈਨਟੈਨੈਂਸ ਕੀਤੀ ਜਾਂਦੀ ਹੈ? ਸਟੇਟ ਗ੍ਰਿਡ 8 ਆਮ O&M ਸਵਾਲਾਂ ਦੀਆਂ ਉੱਤਰਾਂ (2)
ਕਿਵੇਂ ਇੱਕ PV ਪਲਾਂਟ ਦੀ ਮੈਨਟੈਨੈਂਸ ਕੀਤੀ ਜਾਂਦੀ ਹੈ? ਸਟੇਟ ਗ੍ਰਿਡ 8 ਆਮ O&M ਸਵਾਲਾਂ ਦੀਆਂ ਉੱਤਰਾਂ (2)
1. ਗੜੀਆਂ ਦੇ ਸ਼ੁਕਨੇ ਦਿਨ ਵਿੱਚ, ਕੰਡੀਆਂ ਅਤੇ ਲੜਕੀਆਂ ਦੇ ਹਿੱਸੇ ਨੂੰ ਤੁਰੰਤ ਬਦਲਣ ਦੀ ਲੋੜ ਹੈ?ਤੁਰੰਤ ਬਦਲਣਾ ਮਹੱਤਵਪੂਰਨ ਨਹੀਂ ਮਨਾਇਆ ਜਾਂਦਾ। ਜੇਕਰ ਬਦਲਣਾ ਜ਼ਰੂਰੀ ਹੈ, ਤਾਂ ਸਵੇਰੇ ਜਾਂ ਸ਼ਾਮ ਦੇ ਸਮੇਂ ਵਿੱਚ ਕਰਨਾ ਉਚਿਤ ਹੈ। ਤੁਸੀਂ ਪਾਵਰ ਸਟੇਸ਼ਨ ਦੇ ਓਪਰੇਸ਼ਨ ਅਤੇ ਮੈਨਟੈਨੈਂਸ (O&M) ਕਾਰਜ ਦੇ ਵਿਅਕਤੀਆਂ ਨਾਲ ਤੁਰੰਤ ਸੰਪਰਕ ਕਰੋ, ਅਤੇ ਪ੍ਰੋਫੈਸ਼ਨਲ ਸਟਾਫ਼ ਨੂੰ ਸ਼ਾਹੀ ਲਈ ਭੇਜੋ।2. ਫੋਟੋਵੋਲਟਾਈਕ (PV) ਮੌਡਿਊਲਾਂ ਨੂੰ ਬਾਰੀਲਾ ਵਸਤੂਆਂ ਦੀ ਚੋਟ ਤੋਂ ਬਚਾਉਣ ਲਈ, PV ਐਰੇਏ ਦੇ ਆਲਾਵੇ ਤਾਰਾਂ ਦੇ ਸੁਰੱਖਿਆ ਸਕ੍ਰੀਨ ਲਾਉਣੀਆਂ ਹੋ ਸਕਦੀਆਂ ਹਨ?ਤਾਰਾਂ ਦੀਆਂ ਸੁਰੱਖਿਆ ਸਕ੍ਰੀਨਾਂ ਨੂੰ ਲਾਉਣਾ ਮਹੱਤਵਪੂਰਨ ਨਹੀ
Encyclopedia
09/06/2025
ਕਿਵੇਂ ਇੱਕ PV ਪਲਾਂਟ ਨੂੰ ਮੈਣੈਂਸ ਕੀਤਾ ਜਾਂਦਾ ਹੈ? ਸਟੇਟ ਗ੍ਰਿਡ 8 ਆਮ O&M ਸਵਾਲਾਂ ਦੇ ਉਤੱਰ ਦਿੰਦਾ ਹੈ (1)
ਕਿਵੇਂ ਇੱਕ PV ਪਲਾਂਟ ਨੂੰ ਮੈਣੈਂਸ ਕੀਤਾ ਜਾਂਦਾ ਹੈ? ਸਟੇਟ ਗ੍ਰਿਡ 8 ਆਮ O&M ਸਵਾਲਾਂ ਦੇ ਉਤੱਰ ਦਿੰਦਾ ਹੈ (1)
1. ਵਿਸਥਾਰਿਤ ਫੋਟੋਵੋਲਟਾਈਕ (PV) ਬਿਜਲੀ ਉਤਪਾਦਨ ਸਿਸਟਮਾਂ ਦੇ ਆਮ ਖੰਡਹਾਲ ਕਿਹੜੇ ਹਨ? ਸਿਸਟਮ ਦੇ ਵਿਭਿੱਨ ਘਟਕਾਂ ਵਿੱਚ ਕਿਹੜੀਆਂ ਟਿਕਾਉਣ ਯੋਗ ਸਮੱਸਿਆਵਾਂ ਪੈ ਸਕਦੀਆਂ ਹਨ?ਆਮ ਖੰਡਹਾਲ ਵਿੱਚ ਇਨਵਰਟਰ ਚਲਣ ਜਾਂ ਸ਼ੁਰੂ ਹੋਣ ਦੇ ਲਈ ਵੋਲਟੇਜ ਸ਼ੁਰੂਆਤੀ ਸੈੱਟ ਮੁੱਲ ਤੱਕ ਪਹੁੰਚਣ ਦੀ ਵਿਫਲਤਾ ਅਤੇ PV ਮੋਡਿਊਲਾਂ ਜਾਂ ਇਨਵਰਟਰ ਦੀ ਵਜ਼ਹ ਤੋਂ ਕਮ ਬਿਜਲੀ ਉਤਪਾਦਨ ਸ਼ਾਮਲ ਹੈ। ਸਿਸਟਮ ਦੇ ਘਟਕਾਂ ਵਿੱਚ ਪੈ ਸਕਦੀਆਂ ਟਿਕਾਉਣ ਯੋਗ ਸਮੱਸਿਆਵਾਂ ਜੋਕਦੀਆਂ ਹਨ ਜੋਕਦੀ ਜੰਕਸ਼ਨ ਬਕਸਾਂ ਦੀ ਭੱਸਾਹਟ ਅਤੇ PV ਮੋਡਿਊਲਾਂ ਦੀ ਸਥਾਨਿਕ ਭੱਸਾਹਟ ਹੈ।2. ਵਿਸਥਾਰਿਤ ਫੋਟੋਵੋਲਟਾਈਕ (PV) ਬਿਜਲੀ ਉਤਪਾਦਨ ਸਿਸਟਮਾਂ ਦੇ ਆਮ ਖੰਡਹਾਲ ਨੂੰ ਕਿਵੇਂ
Leon
09/06/2025
ਸ਼ੋਰਟ ਸਰਕਿਟ ਵੇਰਸਸ ਓਵਰਲੋਡ: ਅੰਤਰਾਂ ਦੀ ਸਮਝ ਅਤੇ ਆਪਣੀ ਪਾਵਰ ਸਿਸਟਮ ਦੀ ਰਕਸ਼ਾ ਕਿਵੇਂ ਕਰਨੀ ਹੈ
ਸ਼ੋਰਟ ਸਰਕਿਟ ਵੇਰਸਸ ਓਵਰਲੋਡ: ਅੰਤਰਾਂ ਦੀ ਸਮਝ ਅਤੇ ਆਪਣੀ ਪਾਵਰ ਸਿਸਟਮ ਦੀ ਰਕਸ਼ਾ ਕਿਵੇਂ ਕਰਨੀ ਹੈ
ਸ਼ੋਰਟ ਸਰਕਿਟ ਅਤੇ ਓਵਰਲੋਡ ਦੇ ਮੁੱਖ ਅੰਤਰ ਵਿੱਚੋਂ ਇੱਕ ਇਹ ਹੈ ਕਿ ਸ਼ੋਰਟ ਸਰਕਿਟ ਲਾਇਨ-ਟੁ-ਲਾਇਨ (ਲਾਇਨ ਦੇ ਬੀਚ) ਜਾਂ ਲਾਇਨ-ਟੁ-ਗਰੌਂਡ (ਲਾਇਨ ਅਤੇ ਧਰਤੀ ਦੇ ਬੀਚ) ਵਿੱਚ ਫਾਲਟ ਦੇ ਕਾਰਨ ਹੋਣਗਾ, ਜਦੋਂ ਕਿ ਓਵਰਲੋਡ ਉਸ ਸਥਿਤੀ ਨੂੰ ਦਰਸਾਉਂਦਾ ਹੈ ਜਿੱਥੇ ਸਾਧਨ ਆਪਣੀ ਪ੍ਰਤੀ ਸਹਿਯੋਗਤਾ ਤੋਂ ਵਧੀ ਵਿੱਤੀ ਲਵਾਉਂਦੇ ਹਨ।ਦੋਵਾਂ ਦੇ ਬਾਕੀ ਮੁੱਖ ਅੰਤਰ ਹੇਠ ਲਿਖੇ ਤੁਲਨਾ ਚਾਰਟ ਵਿੱਚ ਦੱਸੇ ਗਏ ਹਨ।ਓਵਰਲੋਡ ਸ਼ਬਦ ਆਮ ਤੌਰ 'ਤੇ ਸਰਕਿਟ ਜਾਂ ਜੋੜੀ ਗਏ ਸਾਧਨ ਦੀ ਸਥਿਤੀ ਨੂੰ ਦਰਸਾਉਂਦਾ ਹੈ। ਜਦੋਂ ਜੋੜੀ ਗਈ ਲੋਡ ਆਪਣੀ ਡਿਜਾਇਨ ਸਹਿਯੋਗਤਾ ਨੂੰ ਪਾਰ ਕਰ ਦਿੰਦੀ ਹੈ ਤਾਂ ਸਰਕਿਟ ਓਵਰਲੋਡ ਹੋ ਜਾਂਦਾ ਮਨਾਇਆ ਜਾਂਦਾ ਹੈ। ਓਵਰਲੋਡ ਸਾਧਨ
Edwiin
08/28/2025
ਪੁੱਛਗਿੱਛ ਭੇਜੋ
ਡਾਊਨਲੋਡ
IEE Business ਅੱਪਲੀਕੇਸ਼ਨ ਪ੍ਰਾਪਤ ਕਰੋ
IEE-Business ਐੱਪ ਦਾ ਉਪਯੋਗ ਕਰਕੇ ਸਾਮਾਨ ਲੱਭੋ ਸ਼ੁਲਤਾਂ ਪ੍ਰਾਪਤ ਕਰੋ ਵਿਸ਼ੇਸ਼ਜਣਾਂ ਨਾਲ ਜੋੜ ਬੰਧਨ ਕਰੋ ਅਤੇ ਕਿਸ਼ਤਾਵਾਂ ਦੀ ਯੋਗਦਾਨ ਵਿੱਚ ਹਿੱਸਾ ਲਓ ਆਪਣੇ ਬਿਜ਼ਨੈਸ ਅਤੇ ਬਿਜਲੀ ਪ੍ਰੋਜੈਕਟਾਂ ਦੀ ਵਿਕਾਸ ਲਈ ਮੁੱਖ ਸਹਾਇਤਾ ਪ੍ਰਦਾਨ ਕਰਦਾ ਹੈ