How do I calculate the fault current at the secondary side of a transformer which is supplying a transmission line with a certain impedance?

Encyclopedia
Field: Encyclopedia
0
China

Calculating the fault current (short-circuit current) on the secondary side of a transformer supplying a transmission line is a complex process that involves multiple parameters of the power system. Below are the steps and relevant formulas to help you understand how to perform this calculation. We will assume the system is a three-phase AC system, and the fault occurs on the transformer's secondary side.

1. Determine System Parameters

Transformer Parameters:

  • Rated capacity of the transformer rated S rated (unit: MVA)

  • Transformer impedance ZT (usually given as a percentage, e.g., ZT =6%)

  • Primary-side voltage of the transformer V1(unit: kV)

  • Secondary-side voltage of the transformer V2 (unit: kV)

Transmission Line Parameters:

  • Impedance of the transmission line ZL (unit: ohms or ohms per kilometer)

  • Length of the transmission line L (unit: kilometers)

Equivalent Source Impedance:

The equivalent impedance of the source ZS (unit: ohms), typically provided by the upstream grid. If the source is very strong (e.g., from a large power plant or infinite bus), you can assume ZS ≈0.

2. Normalize All Impedances to the Same Base

To simplify calculations, it's common to normalize all impedances to the same base value (usually the primary or secondary side of the transformer). Here, we choose to normalize all impedances to the secondary side of the transformer.

  • Base Voltage: Select the secondary-side voltage V2 as the base voltage.

  • Base Capacity: Choose the rated capacity of the transformer rated Srated as the base capacity.

The base impedance is calculated as:

a303e058419e33105d4165227b2802e1.jpeg

where V2  is the secondary-side line voltage (kV), and S rated is the rated capacity of the transformer (MVA).

3. Calculate Transformer Impedance

The transformer impedance ZT is usually given as a percentage and needs to be converted to an actual impedance value. The conversion formula is:

cc18e313a996bc5764173344f4744262.jpeg

4. Calculate Transmission Line Impedance

If the transmission line impedance is given in ohms per kilometer, calculate the total impedance based on the line length L:

94a638355d5c20d8da8668249f38517e.jpeg

5. Calculate Equivalent Source Impedance

If the equivalent source impedance ZS is known, use it directly. If the source is very strong, you can assume ZS≈0.

6. Calculate Total Impedance

The total impedance Ztotal  is the sum of the transformer impedance, transmission line impedance, and equivalent source impedance:

d2206b2e94a08987069742aeda344bc6.jpeg

7. Calculate Fault Current

The fault current Ifault can be calculated using Ohm's Law:

00fd0dfb7dc686a10c67a75c828fc275.jpeg

where V2  is the secondary-side line voltage (kV), and Ztotal  is the total impedance (ohms).

Note: The calculated I fault is the line current (kA). If you need the phase current, divide by 

06a8ba97c2cff4c61eb745afebfe91d0.jpeg

8. Consider System Short-Circuit Capacity

In some cases, it may be necessary to consider the system's short-circuit capacity SC , which can be calculated as:

70cd8a200d7fef9c86e9bb7fe21c6ff2.jpeg

where SC is in MVA.

9. Consider Parallel Transmission Lines

If there are multiple parallel transmission lines, the impedance of each line ZL must be combined in parallel. For n parallel lines, the total transmission line impedance is:

e20db109c9869cca63e720f1a2110e08.jpeg

10. Consider Other Factors

Load Impact: In real systems, loads can affect the short-circuit current, but in most cases, load impedance is much larger than the source impedance and can be neglected.

Relay Protection Action Time: The duration of the short-circuit current depends on the action time of relay protection devices, which typically operate within milliseconds to seconds to clear the fault.

Summary

To calculate the fault current on the secondary side of a transformer supplying a transmission line, you need to consider the transformer impedance, transmission line impedance, and equivalent source impedance. By normalizing all impedances to the same base value and applying Ohm's Law, you can calculate the fault current. In practical applications, you should also consider the action time of relay protection devices and the impact of loads.

Give a tip and encourage the author!

Recommended

Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Understanding Transformer Neutral Grounding
I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
01/29/2026
Voltage Imbalance: Ground Fault, Open Line, or Resonance?
Single-phase grounding, line break (open-phase), and resonance can all cause three-phase voltage unbalance. Correctly distinguishing among them is essential for rapid troubleshooting.Single-Phase GroundingAlthough single-phase grounding causes three-phase voltage unbalance, the line-to-line voltage magnitude remains unchanged. It can be classified into two types: metallic grounding and non-metallic grounding. Inmetallic grounding, the faulted phase voltage drops to zero, while the other two phas
11/08/2025
Composition and Working Principle of Photovoltaic Power Generation Systems
Composition and Working Principle of Photovoltaic (PV) Power Generation SystemsA photovoltaic (PV) power generation system is primarily composed of PV modules, a controller, an inverter, batteries, and other accessories (batteries are not required for grid-connected systems). Based on whether it relies on the public power grid, PV systems are divided into off-grid and grid-connected types. Off-grid systems operate independently without relying on the utility grid. They are equipped with energy-s
10/09/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.