• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Free Expert Guides on Power Systems, Circuit Design & Electrical Troubleshooting

Access free engineering resources from IEE Business—covering power design, circuit layout, equipment selection, and troubleshooting. Expert-developed guides help engineers, procurement, and project teams make better decisions. Stay ahead on smart grids, renewables, efficiency, and AI tools. Improve reliability, reduce downtime, and enhance outcomes with real-world solutions. Explore our knowledge hub today.
Faults and Handling Measures for 220 kV Outgoing Circuit Breakers and Disconnectors
1. Significance of Enhancing Fault Handling for 220 kV Outgoing Circuit Breakers and Disconnectors220 kV transmission lines are highly efficient and energy-saving high-voltage power transmission systems that significantly benefit daily life. A fault in a circuit breaker can severely compromise the safety and reliability of the entire power grid. As critical components of high-voltage transmission systems, circuit breakers and disconnectors play essential roles in power flow control and fault pro
11/13/2025
Consult
Tip
Consult
Tip
Infrared, UV & Ultrasonic Busbar Discharge Testing
1. Methods for Detecting Busbar Discharge1.1 Insulation Resistance TestThe insulation resistance test is a simple and commonly used method in electrical insulation testing. It is highly sensitive to through-type insulation defects, overall moisture absorption, and surface contamination—conditions that typically result in significantly reduced resistance values. However, it is less effective in detecting localized aging or partial discharge faults.Depending on the equipment’s insulation class and
10/31/2025
Consult
Tip
Consult
Tip
Handling Substation Blackout: Step-by-Step Guide
1. Purpose of Handling Total Substation BlackoutA total blackout at a 220 kV or higher substation may lead to widespread power outages, significant economic losses, and instability in the power grid, potentially causing system separation. This procedure aims to prevent voltage loss in main grid substations rated 220 kV and above.2. General Principles for Handling Total Substation Blackout Establish contact with dispatch as soon as possible. Restore station service power promptly. Quickly restore
10/31/2025
Consult
Tip
Consult
Tip
How to Handle Common Faults in RMU and Transformer Substations?
1. Ring Main Unit (RMU) and Transformer SubstationThe ring main unit (RMU) and transformer substation is a critical terminal in a distribution ring network system. The operational status of this terminal is directly affected by the performance of the distribution ring network system. Therefore, this section discusses the advantages, system composition, and key characteristics of the distribution ring network.1.1 Advantages of RMU and Transformer SubstationDue to technological limitations, radial
10/28/2025
Consult
Tip
Consult
Tip
What are the common issues in SF₆ gas circuit faults and circuit breaker failure-to-operate faults?
This article categorizes faults into two main types: SF₆ gas circuit faults and circuit breaker failure-to-operate faults. Each is described below:1.SF₆ Gas Circuit Faults1.1 Fault Type: Low gas pressure, but density relay does not trigger alarm or lockout signalCause: Faulty density gauge (i.e., contact not closing)Inspection & Handling: Calibrate actual pressure using a standard gauge. If confirmed, replace the density gauge.1.2 Density Relay Triggers Alarm or Lockout Signal (but pressure
10/24/2025
Consult
Tip
Consult
Tip
Why Does MVDC Grounding Cause System Faults?
Analysis and Handling of DC System Grounding Faults in SubstationsWhen a DC system grounding fault occurs, it can be classified as single-point grounding, multi-point grounding, loop grounding, or reduced insulation. Single-point grounding is further divided into positive-pole and negative-pole grounding. Positive-pole grounding may cause misoperation of protection and automatic devices, while negative-pole grounding may lead to failure to operate (e.g., relay protection or tripping devices). On
10/23/2025
Consult
Tip
Consult
Tip
The Four Key Aspects of Transformers: Construction, Lightning Protection, Common Faults, and Noise Issues
With the rapid development of China's economy, the power industry has also gradually expanded in scale, increasing the requirements for both the installed capacity and the single-unit capacity of power transformers. This article provides a brief introduction to four aspects: transformer construction, transformer lightning protection, transformer faults, and transformer noise.A transformer is a commonly used electrical device capable of converting AC electrical energy. It can transform one form o
10/20/2025
Consult
Tip
Consult
Tip
7 Common VCB Failures and How to Fix Them
Fault Analysis and Troubleshooting of High-Voltage Vacuum Circuit BreakersIntroduction: Advantages and EvolutionHigh-voltage vacuum circuit breakers (VCBs) offer significant advantages over traditional oil or SF₆-based breakers, including: Oil-free and environmentally friendly design High dielectric strength in vacuum Excellent arc-quenching capability Long electrical and mechanical life Compact size, light weight Suitable for frequent operation Fire-resistant and low maintenanceThese benefits h
10/16/2025
Consult
Tip
Consult
Tip
Electric Cable Faults
Cable Faults DefinitionCable faults are issues in electric cables that disrupt the flow of electricity, including short circuits, earth faults, and open circuits.Causes of Cable FaultsFaults can be caused by damaged insulation due to water, moisture, ageing, or improper handling.Fault Type There may be a short circuit between two conductors, There may be earth fault, i.e., fault between conductor and ground, There may be open circuit caused due to disconnection of the conductor.Detection Methods
07/24/2024
Consult
Tip
Consult
Tip
Dual Fuzzy-Sugeno Method to Enhance Power Quality Performance Using a Single-Phase Dual UPQC-Dual PV Without DC-Link Capacitor
This paper proposes a novel configuration of a dual UPQC supplied by a dual photovoltaic (PV), hereinafter referred to as 2UPQC-2PV,to improve the power quality performance of a single-phase 220 V/50 Hz distribution system. The 2UPQC-2PV configuration is proposed to anticipate the possible failure of both inverters in one of the UPQC circuits. The PV array replaces the DC-link capacitor to maintain its voltage connected to the DC-link of the UPQC constant while at the same time supplying active
03/06/2024
Consult
Tip
Consult
Tip
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.