• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Why Does MVDC Grounding Cause System Faults?

Felix Spark
Field: Failure and maintenance
China

Analysis and Handling of DC System Grounding Faults in Substations

When a DC system grounding fault occurs, it can be classified as single-point grounding, multi-point grounding, loop grounding, or reduced insulation. Single-point grounding is further divided into positive-pole and negative-pole grounding. Positive-pole grounding may cause misoperation of protection and automatic devices, while negative-pole grounding may lead to failure to operate (e.g., relay protection or tripping devices). Once any ground fault exists, it forms a new ground path; it must be eliminated promptly. Otherwise, if a second or additional ground develops, it may lead to serious faults or accidents.

Under normal operation, the insulation resistance of both positive and negative poles of the DC system to ground is 999 kΩ. However, when outdoor equipment becomes damp, the DC system’s insulation resistance decreases. The alarm threshold for a 220V DC system is typically 25 kΩ, and 15 kΩ for a 110V system. State Grid Hubei Maintenance Company places high importance on grounding hidden dangers and has raised the alarm standard: a warning is triggered when insulation drops to 40 kΩ for 220V systems and 25 kΩ for 110V systems. This allows隐患 to be eliminated before insulation degradation develops into a full ground fault.

Grounding Cable Inside the DC Panel.jpg

Recently, due to prolonged severe weather and extended plum rain season with high humidity, six 500 kV substations in the province have experienced varying degrees of reduced DC insulation or direct grounding:

  • Enshi and Anfu: insulation dropped to 40 kΩ

  • Shuanghe: positive-pole grounding

  • Jiangxia: positive-pole grounding

  • Junshan: overall insulation reduction

  • Xian Nv Shan: insulation drop, negative-to-ground at 18 kΩ

  • Xinglong: positive-pole grounding

Case Analysis of Recent DC System Insulation Issues:

(1) 500 kV Enshi & Anfu Substations:
DC insulation monitoring devices showed insulation dropping to 40 kΩ. After observation, insulation partially recovered to an acceptable range. Based on past experience, the likely cause was moisture ingress in the thermal relay within outdoor disconnect switch mechanism enclosures.

(2) 500 kV Jiangxia Substation:
After a DC ground fault, secondary maintenance personnel checked the insulation monitor and found no abnormal signals. Field voltage measurements showed 0 V on the positive pole to ground. Using a DC grounding detector, the fault was traced to a moisture-affected contact in the density relay of the #2 bus tie control cabinet. After removing the faulty contact, the DC system insulation returned to normal.

Challenges in DC Grounding Troubleshooting:
Locating and handling DC grounding defects is challenging. Faults often recur with weather changes, and fault points are difficult to identify. Multi-point grounding can also occur. Most recent grounding issues were caused by reduced insulation in outdoor equipment contacts or cables. Contributing factors include aging components with degraded insulation and prolonged rain causing moisture ingress or equipment failure.

Enhancing DC Grounding Response Capability:
Effective handling requires coordinated efforts, standardized procedures, and integration of operation and maintenance (O&M) systems:

  • Safety Procedures:
    Before handling a DC ground fault, clear all personnel from relevant areas, especially those working on secondary circuits. At least two personnel must be present during fault location and repair. Prevent accidental DC short circuits or additional grounding. Implement safety measures to avoid protection misoperations.

  • Fault Location Strategy:
    Follow the principles: microprocessor-based detection first, then manual; external before internal; secondary before primary; signals before control. First, use the DC insulation monitoring device to locate the fault. If data is inaccurate, proceed with manual inspection.

  • Rapid Response Protocol:
    O&M staff must immediately collect alarm messages and abnormal signals from the insulation monitor. Secondary teams should quickly organize emergency repairs. If the monitor accurately identifies the faulty circuit, disconnect its power and observe if insulation recovers. If not, use a DC grounding detector to scan all DC circuits, identify suspect circuits, and test by power disconnection.

  • Precise Fault Isolation:
    Once the faulty circuit is identified, use schematics to pinpoint potential grounding points. Test by disconnecting suspected terminals. After confirmation, apply reliable insulation isolation. Coordinate closely with primary equipment teams to eliminate the fault promptly.

Preventive Measures to Reduce DC Grounding Incidents:

  • Improve operating environments. Install air conditioning in areas with inadequate temperature control. Seal terminal boxes, switch mechanism enclosures, and disconnect switch enclosures properly. Ensure cabinet doors are rainproof.

  • During regular inspections or transformer installations, thoroughly check whether gas relays, oil flow relays, oil level gauges, thermometers, and pressure relief devices have proper rain shields. Verify secure wiring box installation, presence of sealing gaskets, and that secondary cables are properly routed and undamaged.

  • Use scheduled outages to replace vulnerable outdoor secondary components that are frequently operated or continuously energized.

  • Eliminate design flaws or poor workmanship. Ensure secondary circuits are complete during commissioning—avoid parasitic circuits, loops, or crossovers. Pay attention to cleaning and dust removal during protection and automatic device inspections.

  • For technical upgrades or new construction, strictly follow design drawings. Conduct thorough pre-construction drawing reviews. Prevent DC I/II segment mixing, AC/DC mixing, and parasitic circuits that could cause DC system anomalies.

  • Strengthen operation, maintenance, and inspection of DC systems, DC distribution panels, and insulation monitoring devices across all substations. Ensure monitoring devices accurately reflect grounding locations, enabling rapid isolation by maintenance personnel.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.