| Brand | Rw Energy |
| Series | KYN28A |
| Rated voltage | 3.6kV 7.2kV 11kV 24kV |
| Rated current | 630-3150A |
| Rated frequency | 50/60Hz |
KYN28A-11/24KV(GZS1) air-insulated metal-clad withdrawable switchgear (hereinafter as “switchgear”) is a necessary indoor power distribution equipment 3-phase AC 50Hz. It is mainly used to receive and distribute 3-24kV network electrical and control protection and monitoring to line circuit. Relay chamber panel can install in various types of microprocessor based relay protection device , and can realize the intelligent control system, with remote control, telemetry, remote communication and remote transfer function, through the CAN communication interface with fieldbus control network to prevent the mal-operation of circuit breaker, to prevent pushing and pulling handcart with load, to prevent grounding switch closed with charged, to prevent the grounding switch in the grounding position transmission and to prevent into live space, which is referred to as the "five-anti" function. The cabinet is equipped with VS1 (ZN63), ZN12V vacuum circuit breaker, also can be equipped with imported VD4 vacuum circuit breaker and VC series vacuum contactor. The switchgear meet the requirements of standard IEC62271-200,IEC62271-100 etc.
KYN28A-12 metal clad switchgear electrical cubicle is applicable for 3.6kV ~ 12kV with three-phase AC 50Hz single bus or single bus sectional system. It is mainly used for substation and distribution system of power plants, substation, industrial and mining enterprises, building hotels, municipal construction and petrochemical sector as power receiving, power distribution and the circuitcontrolling, protection and monitoring.
There may be condensation, when the temperature plunged with filth, the products apply to the following two conditions more severe than normal
Note:
Technical data
| No | Name | Unit | Parameter | ||||
| 1 | Insuation level |
Rated voltage | kV | 3.6 | 7.2 | 11 | |
| 1minpower frequency withstand volatge | kV | 24 | 32 | 42 | |||
| 2 | Lightning impulse withstand voltage (full wave) | kV | 40 | 60 | 75 | ||
| 3 | Rated frequency | Hz | 50/60 | ||||
| 4 | Rated current | A | 630.1250.1600.2000.2500.3150 | ||||
| 5 | 4s short time withstand current | kA | 20、25、31、31.5、40、50 | ||||
| 6 | Rated peak withstand current | kA | 50、63、80、100、125 | ||||
| 7 | Protection level | Enclosure IP4X, partition of each compartment is IP2X | |||||
Vaccum Circuit Breaker
| No | Name | Unit | VS1、ZN12V | VD4 | ||||
| 1 |
Insuation level |
Rated voltage | kV | 11 | ||||
| 1min power frequency withstand volatge | kV | 42 | ||||||
| 2 | Lightning impulse withstand voltage (full wave) | kV | 75 | |||||
| 3 | Rated frequency | Hz | 50/60 | |||||
| 4 | Rated current | A | 630.1250.1600.2000,2500.3150 | |||||
| 5 | Rated short circuit break current | kA | 20、25、31、31.5、40、50 | |||||
| 6 | 4s short time withstand current | kA | 20、25、31、31.5、40、50 | |||||
| 7 | Rated peak withstand current | kA | 40,50、63,80,100,125 | |||||
| 8 | Rated operate sequence | 0-0.3S-c0180S-CO | ||||||
| 9 | Rated short circuit break current>40kA, operation sequence | 0-180sco-180s-co | ||||||
| 10 | Closing sequence | ≤70 | ≈60 | |||||
| 11 | Open sequence | ≤50 | ≤45 | |||||
| 12 | Arcing time | ≤15 | ≤15 | |||||
| 13 | Break time | ≤65 | ≤60 | |||||
The enclosure is made of aluminium-zinc plated steel sheet by CNC machine, high precise dimension, short production cycle,excellent mechanical strength and nice appearance. The busbar compartment, VCB handc art compartment, cable compartment and relay compartment are separated by metal sheet. Flexible operation for handcart movement, clear position instruction, the earthing switch allow to making short circuit current and creditable mechanical interlock.