36kV 40.5kV 44kV 45kV Pure air insulated Ring Main Unit (RMU) / switchboard panel

  • 36kV 40.5kV 44kV 45kV Pure air insulated Ring Main Unit (RMU) / switchboard panel

Key attributes

Brand ROCKWILL
Model NO. 36kV 40.5kV 44kV 45kV Pure air insulated Ring Main Unit (RMU) / switchboard panel
Rated voltage 36kV
Rated normal current 630/800A
Rated frequency 50/60Hz
Series SM66

Product descriptions from the supplier

Description

Description :

Pioneer in China's eco-friendly switchgear sector, we have specialized in R&D and manufacturing of SF₆-free switchgear for decades. With core technologies, we have established industry standards. Boasting a fully independent end-to-end production chain, we have built a product matrix of zero-emission and high-reliability eco-friendly switchgear, making us a trusted choice for power grid construction.

SM66 unit type SF6 ring net cabinet with SF6 load switch as main switch, for whole cabinet is suitable for electric distribution automation and compact also expandable metal close switchgear. It characters in its simple structure, flexible operation, reliable interlocking and convenient installation etc.which can provide the satisfactory technical projects both for different application occasions and users. With the adoption of sensor technology and the protection relay up to date, plus the advanced technology and flexible assembly project, SM66 unit type SF6 ring net cabinet can completely meet the requirement of continuously variable market.

Main function :

  • Good Insulation Performance;

  • Strong Arc Extinguishing Ability;

  • Excellent safety performance ;

  • Flexible and Reliable Operation;

  • Compact Structure and Modular Design;

  • High Degree of Intelligence.

Technology parameters:

The voltage classes of some of these eco-friendly switchgears include 6kV, 6.3kV, 6.6kV, 6.9kV, 7.2kV, 10kV, 10.5kV, 11kV, 11.5kV, 12kV, 13.2kV, 13.8kV, 14.5kV, 14.4kV, 15kV, 15.5kV, 15.6kV, 17.5kV, 20kV, 21.9kV, 22kV, 24kV, 30kV, 33kV, 33.5kV, 34.5kV, 35kV, 36kV, 38kV, 38.5kV, 40.5kV, 44kV, 45kV, 46kV, 66kV and 69kV. and customization is available.

No

Item

Unit

Parameter

1

Rated voltage

kV

36

40.5

2

Rated frequency

Hz

50/60

3

Rated current

A

630/800

4

1min Power frequency withstand voltage

wet

kV

70

95

dry

kV

80

110

5

Lightning impulse withstand voltage

kV

170

185

6

Rated short circuit breaking current (peak)

kA

195

215

7

Rated active load and close circuit breaking current

A

400/630

8

Rated transferring current

A

1200

1000

9

Rated short circuit making current (peak)

kA

63

63

10

Rated cable offload

A

50

11

Transformer offload

A

16

12

Rated withstand current (peak)

kA

63

13

Short time withstand current (2s)

kA

25

14

Mechanism life

times

2000

2000

Outline dimension drawing:

36kV 40.5kV air insulated Ring Main Unit RMU (1).png

Fixing of units:

36kV 40.5kV air insulated Ring Main Unit RMU (2).png

36kV 40.5kV air insulated Ring Main Unit RMU (3).png

What is the purpose of a ring main unit RMU?

A:Ring main unit (RMU) is used to distribute electrical power in a medium - voltage distribution network. It allows for sectionalizing the network, isolating faults, and enabling power transfer between different sections of the ring - shaped power network, ensuring reliable power supply.

What does the RMU stand for?

A:RMU stands for Ring Main Unit. It is a type of electrical switchgear used in medium-voltage electrical distribution systems, typically for distributing power in a ring circuit configuration.

 

 

 

FAQ
Q: Is the installation process of environmentally friendly cabinets more complex than traditional cabinets?
A:
No, the installation process is basically the same as that of traditional cabinets and even simpler in some aspects. They do not require special SF6 gas filling and recycling equipment; only basic steps such as cabinet fixing, cable connection, and insulation gas filling (for gas-insulated types) are needed. Manufacturers usually provide detailed installation manuals and on-site guidance. Professional electricians can complete the installation after simple training.
Q: What are the requirements for the installation environment of environmentally friendly cabinets?
A:
The installation environment should be free of severe vibration, corrosive gases (e.g., sulfur dioxide, hydrogen sulfide), and flammable/explosive substances. The ambient temperature should be between -40℃ and +70℃, and relative humidity should not exceed 95% (without condensation). The installation site should have sufficient space for maintenance and ventilation, and the foundation should be flat and firm to ensure the cabinet's stability.
Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m²m² Total staff: 700+ Highest Annual Export(usD): 150000000
Workplace: 108000m²m²
Total staff: 700+
Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: High Voltage Electrical Apparatus/Electric transformer
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

  • Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding Electrodes
    Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding ElectrodesWhen the grounding electrode of an Ultra-High-Voltage Direct Current (UHVDC) transmission system is located close to a renewable energy power station, the return current flowing through the earth can cause a rise in ground potential around the electrode area. This ground potential rise leads to a shift in the neutral-point potential of nearby power transformers, inducing DC bias (or DC offset) in their
    01/15/2026
  • HECI GCB for Generators – Fast SF6 Circuit Breaker
    1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
    01/06/2026
  • Distribution Equipment Transformer Testing, Inspection, and Maintenance
    1.Transformer Maintenance and Inspection Open the low-voltage (LV) circuit breaker of the transformer under maintenance, remove the control power fuse, and hang a “Do Not Close” warning sign on the switch handle. Open the high-voltage (HV) circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the HV switchgear, and hang a “Do Not Close” warning sign on the switch handle. For dry-type transformer maintenance: first clean the porcel
    12/25/2025
  • How to Test Insulation Resistance of Distribution Transformers
    In practical work, insulation resistance of distribution transformers is generally measured twice: the insulation resistance between thehigh-voltage (HV) windingand thelow-voltage (LV) winding plus the transformer tank, and the insulation resistance between theLV windingand theHV winding plus the transformer tank.If both measurements yield acceptable values, it indicates that the insulation among the HV winding, LV winding, and transformer tank is qualified. If either measurement fails, pairwise
    12/25/2025
  • Design Principles for Pole-Mounted Distribution Transformers
    Design Principles for Pole-Mounted Distribution Transformers(1) Location and Layout PrinciplesPole-mounted transformer platforms should be located near the load center or close to critical loads, following the principle of “small capacity, multiple locations” to facilitate equipment replacement and maintenance. For residential power supply, three-phase transformers may be installed nearby based on current demand and future growth projections.(2) Capacity Selection for Three-Phase Pole-Mounted Tr
    12/25/2025
  • Transformer Noise Control Solutions for Different Installations
    1.Noise Mitigation for Ground-Level Independent Transformer RoomsMitigation Strategy:First, conduct a power-off inspection and maintenance of the transformer, including replacing aged insulating oil, checking and tightening all fasteners, and cleaning dust from the unit.Second, reinforce the transformer foundation or install vibration isolation devices—such as rubber pads or spring isolators—selected based on the severity of vibration.Finally, strengthen sound insulation at weak points of the ro
    12/25/2025

Related Solutions

  • Intelligent Operation Solution for 12kV Vacuum Circuit Breakers: Integrating Real-time Monitoring & Lifetime Optimization
    Ⅰ. Equipment Operation & MaintenanceIntelligent Monitoring System Integration​Multi-parameter Real-time Monitoring: Embedded sensors (temperature, displacement, Hall effect current sensors) track contact temperature rise, mechanical characteristics (opening/closing speed, overtravel), coil current, and partial discharge signals. Data undergoes preprocessing via edge computing prior to cloud upload.​Lifetime Prediction Model: Dynamically evaluates remaining lifespan using electrical wear data
    06/10/2025
  • SF6 Circuit Breaker Solutions for Outdoor Installation (Anti-Pollution & Seismic Resistance)
    I.Core Challenges in Outdoor Installation​In high-voltage transmission and distribution systems, SF6 circuit breakers are exposed to complex outdoor environments for extended periods, facing the following critical issues:​Pollution & Insulation Degradation​Dust, salt fog, and industrial pollutants in outdoor environments easily adhere to equipment surfaces. In coastal or industrial areas, pollution levels may reach ​Class IV, resulting in insufficient creepage distance and triggering ​flasho
    05/12/2025
  • 12kV Indoor Vacuum Circuit Breaker Southeast Asia Solution: Anti-Corrosion Compact Design
    12kV Indoor Vacuum Circuit Breaker Southeast Asia Solution: Anti-Corrosion Compact DesignⅠ. Executive Summary​Southeast Asia faces rapidly growing electricity demand alongside environmental challenges including high temperatures, humidity, salt spray corrosion, and grid instability. This solution recommends ​Solid Insulated Pole-Mounted Vacuum Circuit Breakers (VCB)​​ featuring ​high reliability, ​compact design, and ​smart monitoring. Tailored for tropical climates and industrial scenarios, it
    06/10/2025
Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
+86
Click to upload file

IEE Business will not sell or share your personal information.

Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.