Causes of Transformer Damage from Lightning Strikes and Whether It Can Still Be Used Afterward

Felix Spark
Felix Spark
Field: Failure and maintenance
China

1. What Causes Transformer Damage from Lightning Strikes?

  • Direct Lightning Strike: When lightning directly hits a transformer or its nearby transmission lines, it generates an enormous transient current that instantly flows through the transformer windings and core. This causes the insulation material to heat up rapidly—even melt—leading to winding short circuits or burnout. Damage from direct strikes is often catastrophic.

  • Lightning-Induced Voltage (Electromagnetic Induction): Even if lightning does not strike the transformer directly, its powerful electromagnetic field can induce voltages between the windings—especially in the absence of effective shielding. These induced voltages can be high enough to break down the transformer’s insulation, causing partial discharges. Over time, this cumulative stress degrades the insulation layer and eventually leads to failure.

  • Lightning Surge Ingress: Lightning-generated surges traveling along power lines can propagate rapidly to the transformer. If the transformer lacks adequate surge protection, these lightning waves can intrude directly into the transformer, causing overvoltage that damages the internal insulation system.

  • Ground Potential Rise (GPR) / Backflash: During a lightning strike, the lightning current flows through the grounding system, creating a voltage drop across the grounding resistance. If the transformer’s grounding resistance is too high, a significant ground potential rise may occur. This can result in "backflash," where the transformer tank or low-voltage side experiences a high relative potential, leading to equipment damage.

Power transformer.jpg

2. Can a Transformer Still Be Used After a Lightning Strike?

Whether a transformer can continue to be used after a lightning strike depends on the extent of the damage and the results of subsequent inspections. Typically, the following steps must be taken immediately after a strike:

  • Safety Isolation and Visual Inspection: First, ensure safety by isolating the affected transformer from the grid. Conduct a visual inspection for obvious physical damage, burn marks, or oil leakage.

  • Dissolved Gas Analysis (DGA): Analyzing dissolved gases in the transformer oil is a key method for diagnosing internal faults. A lightning strike may cause insulation materials to decompose, releasing specific gases such as hydrogen and acetylene. Oil sample analysis helps assess the severity of internal damage.

  • Electrical Testing: Perform tests including insulation resistance measurement, dielectric loss factor (tan δ) testing, and DC winding resistance measurement to evaluate whether the transformer’s electrical performance has been compromised.

  • Professional Assessment and Repair: Based on the above test results, qualified technicians should assess the extent of damage and determine repair feasibility. Minor insulation damage may be remedied through drying, localized winding repair, or insulation replacement. However, severe damage—such as burned-out windings—may require complete rewinding or replacement of the entire transformer.

In summary, transformers can be damaged by lightning through multiple mechanisms, and their usability after a strike depends entirely on the severity of the damage. The key to preventing lightning-related failures lies in establishing a robust lightning protection system, including installing surge arresters, implementing effective grounding, and using lightning-resistant transformers.

Give a tip and encourage the author!
Recommended
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Neutral Grounding Gap Protection Measures?In a certain power grid, when a single-phase ground fault occurs on a power supply line, both the transformer neutral grounding gap protection and the power supply line protection operate simultaneously, causing an outage of an otherwise healthy transformer. The main reason is that during a system single-phase ground fault, the zero-sequence overvoltage causes the transformer neutral grounding gap to break down. The resulting
Noah
12/05/2025
Innovative & Common Winding Structures for 10kV High-Voltage High-Frequency Transformers
Innovative & Common Winding Structures for 10kV High-Voltage High-Frequency Transformers
1.Innovative Winding Structures for 10 kV-Class High-Voltage High-Frequency Transformers1.1 Zoned and Partially Potted Ventilated Structure Two U-shaped ferrite cores are mated to form a magnetic core unit, or further assembled into series/series-parallel core modules. Primary and secondary bobbins are mounted on the left and right straight legs of the core, respectively, with the core mating plane serving as the boundary layer. Windings of the same type are grouped on the same side. Litz wire i
Noah
12/05/2025
How to Increase Transformer Capacity? What Needs to Be Replaced for Transformer Capacity Upgrade?
How to Increase Transformer Capacity? What Needs to Be Replaced for Transformer Capacity Upgrade?
How to Increase Transformer Capacity? What Needs to Be Replaced for Transformer Capacity Upgrade?Transformer capacity upgrade refers to improving the capacity of a transformer without replacing the entire unit, through certain methods. In applications requiring high current or high power output, transformer capacity upgrades are often necessary to meet demand. This article introduces methods for transformer capacity upgrade and the components that need to be replaced.A transformer is a critical
Echo
12/04/2025
Causes of Transformer Differential Current and Hazards of Transformer Bias Current
Causes of Transformer Differential Current and Hazards of Transformer Bias Current
Causes of Transformer Differential Current and Hazards of Transformer Bias CurrentTransformer differential current is caused by factors such as incomplete symmetry of the magnetic circuit or insulation damage. Differential current occurs when the primary and secondary sides of the transformer are grounded or when the load is unbalanced.Firstly, transformer differential current leads to energy waste. Differential current causes additional power loss in the transformer, increasing the load on the
Edwiin
12/04/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.