Surge Impedance Loading

Encyclopedia
Field: Encyclopedia
0
China

SIL Definition


Surge Impedance Loading (SIL) is defined as the power a transmission line delivers to a load that matches the line’s surge impedance.

 


Surge Impedance


Surge Impedance is the balance point where capacitive and inductive reactances of a transmission line cancel each other out.

 


Long transmission lines (> 250 km) inherently possess distributed inductance and capacitance. When activated, the capacitance feeds reactive power into the line, and the inductance absorbs it.

 


Now if we take the balance of the two reactive powers we arrive at the following equation

 


Capacitive VAR = Inductive VAR

 


Where,

V = Phase voltage

I = Line Current

Xc = Capacitive reactance per phase

XL = Inductive reactance per phase

Upon simplifying

 


eec5aa71e277fb8a6a441d95579c8b7c.jpeg

 


Where,

f = Frequency of the system

L = Inductance per unit length of the line

l = Length of the line

Hence we get,

 


ee12cd10bba3bf52fcd36e98dfb23186.jpeg

 


This quantity having the dimensions of resistance is the Surge Impedance. It can be considered as a purely resistive load which when connected at the receiving end of the line, the reactive power generated by capacitive reactance will be completely absorbed by inductive reactance of the line.


It is nothing but the Characteristic Impedance (Zc) of a lossless line.

 


Transmission Line Properties


  • Key properties such as distributed inductance and capacitance are fundamental to understanding transmission line behavior.



  • Key properties such as distributed inductance and capacitance are fundamental to understanding transmission line behavior.



  • Calculations involving the characteristic impedance and load impedance help in understanding how SIL influences power transmission efficiency.

 


Practical Application


SIL is crucial for designing transmission lines to ensure voltage stability and efficient power delivery.

 



Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g
12/15/2025
Send inquiry
+86
Click to upload file

IEE Business will not sell or share your personal information.

Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.