Tensile Test of Conductors

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is The Tensile Test Of Conductors

This test is performed only to confirm tensile strength of aluminum wires used for conductor in electric power cables. This test is significantly performed on conductor material to judge the strength of this material. A cable conductor is often subjected to pull from one end during laying, installing and manufacturing hence it should be strong enough to tolerate the pulling force as well. Hence it becomes necessary to ensure that the conductor material has sufficient tensile strength.

Apparatus required for Tensile Test

  • Tensile Testing Machine: An automatic machine, with two end grips properly designed to hold the conductor with sufficient strength so that the conductor cannot slid by any means during the test. The machine should have sufficient capacity to apply required tension during test.

  • Plane Faced Micrometer which can able to measure accurately even 0.01 mm variation. This is used to measure the diameter of the specimen conductor.

  • Suitable Scale with least scale division 1 mm to measure length of the specimen conductor.

  • Weighing Balance with sensitivity of 0.01g to measure mass of the specimen.

tensile test machineMethod of Tensile Test of Conductors

A specimen of conductor with length little bit longer than gauge length (gauge length is the length of the specimen on which test is carried out) is first taken. To be careful that the minimum length of the entire specimen shall be such that it should have extra length at two ends after its gauge length for holding the same by grips of tensile testing machine. No pre-conditioning of the specimen is required for Tensile test.

Procedure of Tensile Test of Conductors

Before the test is conducted the diameter of the specimen is measured by plane faced micrometer and recorded. In case of shaped solidal conductor, the mass and length of specimen are determined by weigh balance ans measuring scale respectively. Now the test specimen is fixed and fitted in-between the jaws of the machine by means of grips. The load is applied to the specimen and it is increased gradually and uniformly. The rate of separation of jaws of the machine shall not be more than 100 mm per minute. When the Tensile test specimen is fractured, that breaking load is noted down from the dial of the tensile testing machine, and then tension strength is calculated.

Tabulation of Observations of Tensile Test of Conductors

Diameter of Circular Wire in mm

Shaped Solidal Conductor

Cross Sectional Area in mm2

Breaking Load in N


Mass in g

Length in mm



Calculation

Report

Sample No

Aluminum Conductor Grade

Tensile Strength, N/mm2



Observed

Specified

Conclution: Specimen meets/does not meet the requirements of specification.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
Low-Voltage Distribution Cabinet Maintenance Steps and Safety Guide
Low-Voltage Distribution Cabinet Maintenance Steps and Safety Guide
Maintenance Procedure for Low-Voltage Power Distribution FacilitiesLow-voltage power distr ibution facilities refer to the infrastructure that delivers electrical power from a power supply room to end-user equipment, typically including distribution cabinets, cables, and wiring. To ensure the normal operation of these facilities and guarantee user safety and power supply quality, regular maintenance and servicing are essential. This article provides a detailed introduction to the maintenance pro
Edwiin
10/28/2025
Low-Voltage Electrical Work Safety Preparation and Operation Guide
Low-Voltage Electrical Work Safety Preparation and Operation Guide
Low-Voltage Electrician Safety Operating Procedures1. Safety Preparation Before performing any low-voltage electrical work, personnel must wear approved protective equipment, including insulating gloves, insulating boots, and insulating workwear. Carefully inspect all tools and equipment for proper operation. Report any damage or malfunction immediately for repair or replacement. Ensure adequate ventilation at the worksite. Avoid prolonged work in confined spaces to prevent fire hazards or poiso
Echo
10/28/2025
How to Handle Common Faults in RMU and Transformer Substations?
How to Handle Common Faults in RMU and Transformer Substations?
1. Ring Main Unit (RMU) and Transformer SubstationThe ring main unit (RMU) and transformer substation is a critical terminal in a distribution ring network system. The operational status of this terminal is directly affected by the performance of the distribution ring network system. Therefore, this section discusses the advantages, system composition, and key characteristics of the distribution ring network.1.1 Advantages of RMU and Transformer SubstationDue to technological limitations, radial
Felix Spark
10/28/2025
Six Key Differences Between Ring Main Units and Switchgear Explained
Six Key Differences Between Ring Main Units and Switchgear Explained
Differences Between Ring Main Units (RMUs) and SwitchgearIn power systems, both ring main units (RMUs) and switchgear are common distribution equipment, but they differ significantly in function and structure. RMUs are primarily used in ring-fed networks, responsible for power distribution and line protection, with the key feature being multi-source interconnection through a closed-loop ring network. Switchgear, as a more general-purpose distribution device, handles power reception, distribution
Echo
10/28/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.