• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Testing of Electrical Power Cable | Type Test | Acceptance Test | Routine Test

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is Testing Of Electrical Power Cable

  1. The following tests are the type test of electrical power cable.

    Physical tests for insulation and sheath

    1. Tensile strength and elongation at break

    2. Aging in an air oven

    3. Aging in air bomb

    4. Aging in an oxygen bomb

    5. Hot set

    6. Oil resistance

    7. Tear resistance


    8. Insulation resistance

    9. High voltage (water immersion) test

    10. Flammability test (only for SE-3, SE-4)

    11. Water abortion test (for insulation)

    12. Persulphate test (for copper )

    13. Annealing test (for copper)

    14. Tensile test (for Aluminium)

    15. Wrapping test (for Aluminium)

    16. Conductor resistance test (for all)

    17. Test for thickness of insulation (for all)

    18. Measurement of overall diameter (where specified)(for all)


  2. Acceptance test: The following shall constitute acceptance test:

    1. Annealing test (for copper)

    2. Tensile test (for Aluminium )

    3. Wrapping test (for Aluminium )

    4. Conductor resistance test

    5. Test for the thickness of insulation and sheath and overall diameter

    6. Tensile strength and elongation at break of insulation and heath

    7. Hot set test for insulation and sheath

    8. High voltage test

    9. Insulation resistance test

  3. Routine test: The following shall constitute the routine test.

    1. Conductor resistance test

    2. High voltage test

    3. Insulation resistance test

High Voltage Test (Water Immersion Test) :
Approximate 3 meters long core is removed as a sample from the finished cable or cord. The sample then is so immersed in a water bath at room temperature that its ends protrude at least 200 mm above the water level. After 24 hours, an alternating voltage of the required level is applied between
conductor and water. This voltage is raised as per requirement within 10 sec and hold constant at this value for 5 min. If the sample fails in this test, one more sample can be subjected to this test.

Test on completed cables (Acceptance and routine test) :
This test shall be carried out between conductors or between conductor and screen/armor. The test shall be carried out on required voltage the test shall be carried out at room temperature and the time of application shall be 5 min no failure of Insulation shall occur.

Flammability Test :
Period of burning after removal of the flame shall not exceed 60 sec and the unaffected portion from the lower edge of the top clamp shall be at least 50 mm.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
Low-Voltage Distribution Cabinet Maintenance Steps and Safety Guide
Low-Voltage Distribution Cabinet Maintenance Steps and Safety Guide
Maintenance Procedure for Low-Voltage Power Distribution FacilitiesLow-voltage power distr ibution facilities refer to the infrastructure that delivers electrical power from a power supply room to end-user equipment, typically including distribution cabinets, cables, and wiring. To ensure the normal operation of these facilities and guarantee user safety and power supply quality, regular maintenance and servicing are essential. This article provides a detailed introduction to the maintenance pro
Edwiin
10/28/2025
Low-Voltage Electrical Work Safety Preparation and Operation Guide
Low-Voltage Electrical Work Safety Preparation and Operation Guide
Low-Voltage Electrician Safety Operating Procedures1. Safety Preparation Before performing any low-voltage electrical work, personnel must wear approved protective equipment, including insulating gloves, insulating boots, and insulating workwear. Carefully inspect all tools and equipment for proper operation. Report any damage or malfunction immediately for repair or replacement. Ensure adequate ventilation at the worksite. Avoid prolonged work in confined spaces to prevent fire hazards or poiso
Echo
10/28/2025
How to Handle Common Faults in RMU and Transformer Substations?
How to Handle Common Faults in RMU and Transformer Substations?
1. Ring Main Unit (RMU) and Transformer SubstationThe ring main unit (RMU) and transformer substation is a critical terminal in a distribution ring network system. The operational status of this terminal is directly affected by the performance of the distribution ring network system. Therefore, this section discusses the advantages, system composition, and key characteristics of the distribution ring network.1.1 Advantages of RMU and Transformer SubstationDue to technological limitations, radial
Felix Spark
10/28/2025
Six Key Differences Between Ring Main Units and Switchgear Explained
Six Key Differences Between Ring Main Units and Switchgear Explained
Differences Between Ring Main Units (RMUs) and SwitchgearIn power systems, both ring main units (RMUs) and switchgear are common distribution equipment, but they differ significantly in function and structure. RMUs are primarily used in ring-fed networks, responsible for power distribution and line protection, with the key feature being multi-source interconnection through a closed-loop ring network. Switchgear, as a more general-purpose distribution device, handles power reception, distribution
Echo
10/28/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.