• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Synchronous Impedance Method

Edwiin
Edwiin
Field: Power switch
China

The Synchronous Impedance Method, also known as the EMF Method, replaces the impact of armature reaction with an equivalent imaginary reactance. To calculate voltage regulation using this method, the following data are required: armature resistance per phase, the Open-Circuit Characteristic (OCC) curve depicting the relationship between open-circuit voltage and field current, and the Short-Circuit Characteristic (SCC) curve showing the relationship between short-circuit current and field current.

For a synchronous generator following are the equation given below:

To calculate the synchronous impedance Zs, measurements are taken, and the value of Ea (armature-induced EMF) is derived. Using Ea and V (terminal voltage), voltage regulation is then computed.

Measurement of Synchronous Impedance

Synchronous impedance is determined through three primary tests:

  • DC Resistance Test

  • Open Circuit Test

  • Short Circuit Test

DC Resistance Test

In this test, the alternator is assumed to be star-connected with its DC field winding open-circuited, as depicted in the circuit diagram below:

DC Resistance Test

The DC resistance between each pair of terminals is measured using either the ammeter-voltmeter method or Wheatstone’s bridge. The average of three measured resistance values Rt is calculated, and the per-phase DC resistance RDC is derived by dividing Rt by 2. Considering the skin effect, which increases the effective AC resistance, the per-phase AC resistance RAC is obtained by multiplying RDC by a factor of 1.20–1.75 (typical value: 1.25), depending on the machine size.

Open Circuit Test

To determine synchronous impedance via the open-circuit test, the alternator operates at rated synchronous speed with load terminals open (loads disconnected) and field current initially set to zero. The corresponding circuit diagram is shown below:

Open Circuit Test (Continued)

After setting the field current to zero, it is gradually increased in steps while measuring the terminal voltage Et at each increment. The excitation current is typically raised until the terminal voltage reaches 125% of the rated value. A graph is plotted between the open-circuit phase voltage Ep = Et/sqrt 3 and the field current If, yielding the Open Circuit Characteristic (O.C.C) curve. This curve mirrors the shape of a standard magnetization curve, with its linear region extended to form an air gap line.

The O.C.C and air gap line are illustrated in the figure below:

Short Circuit Test

In the short circuit test, the armature terminals are shorted via three ammeters, as illustrated in the figure below:

Short Circuit Test (Continued)

Before starting the alternator, the field current is reduced to zero, and each ammeter is set to a range exceeding the rated full-load current. The alternator is operated at synchronous speed, with the field current increased in gradual steps—similar to the open-circuit test—while measuring the armature current at each increment. The field current is adjusted until the armature current reaches 150% of the rated value.

For each step, the field current If and the average of three ammeter readings (armature current Ia) are recorded. A graph plotting Ia against If yields the Short Circuit Characteristic (S.C.C), which typically forms a straight line, as shown in the figure below.

Calculation of Synchronous Impedance

To calculate the synchronous impedance Zs, first overlay the Open-Circuit Characteristic (OCC) and Short-Circuit Characteristic (SCC) on the same graph. Next, determine the short-circuit current ISC corresponding to the rated alternator voltage per phase Erated. The synchronous impedance is then derived as the ratio of the open-circuit voltage EOC (at the field current that yields Erated to the corresponding short-circuit current ISC, expressed as s = EOC / ISC.

The graph is shown below:

From the above figure, consider the field current If = OA, which produces the rated alternator voltage per phase. Corresponding to this field current, the open-circuit voltage is represented by AB.

Assumptions of the Synchronous Impedance Method

The synchronous impedance method assumes that synchronous impedance  (determined from the ratio of open-circuit voltage to short-circuit current via OCC and SCC curves) remains constant when these characteristics are linear. It further assumes that flux under test conditions matches that under load, though this introduces error as short-circuited armature current lags voltage by ~90°, causing predominantly demagnetizing armature reaction. Armature reaction effects are modeled as a voltage drop proportional to armature current, combined with reactance voltage drop, with magnetic reluctance assumed constant (valid for cylindrical rotors due to uniform air gaps). At low excitations,  is constant (linear/unsaturated impedance), but saturation reduces  beyond the OCC's linear region (saturated impedance). This method yields higher voltage regulation than actual loading, earning it the term pessimistic method.

Give a tip and encourage the author!
Recommended
How to Choose a Thermal Relay for Motor Protection?
How to Choose a Thermal Relay for Motor Protection?
Thermal Relays for Motor Overload Protection: Principles, Selection, and ApplicationIn motor control systems, fuses are primarily used for short-circuit protection. However, they cannot protect against overheating caused by prolonged overloading, frequent forward-reverse operation, or undervoltage operation. Currently, thermal relays are widely used for motor overload protection. A thermal relay is a protective device that operates based on the thermal effect of electric current, and is essentia
James
10/22/2025
How to Choose & Maintain Electric Motors: 6 Key Steps
How to Choose & Maintain Electric Motors: 6 Key Steps
"Selecting a High-Quality Motor" – Remember the Six Key Steps Inspect (Look): Check the motor’s appearanceThe motor’s surface should have a smooth, even paint finish. The nameplate must be properly installed with complete and clear markings, including: model number, serial number, rated power, rated current, rated voltage, allowable temperature rise, connection method, speed, noise level, frequency, protection rating, weight, standard code, duty type, insulation class, manufacturing date, and ma
Felix Spark
10/21/2025
 What Is the Working Principle of a Power Plant Boiler?
What Is the Working Principle of a Power Plant Boiler?
The working principle of a power plant boiler is to utilize the thermal energy released from fuel combustion to heat feedwater, producing a sufficient quantity of superheated steam that meets specified parameters and quality requirements. The amount of steam produced is known as the boiler's evaporation capacity, typically measured in tons per hour (t/h). Steam parameters primarily refer to pressure and temperature, expressed in megapascals (MPa) and degrees Celsius (°C), respectively. Steam qua
Edwiin
10/10/2025
What is the principle of live-line washing for substations?
What is the principle of live-line washing for substations?
Why Do Electrical Equipment Need a "Bath"?Due to atmospheric pollution, contaminants accumulate on insulating porcelain insulators and posts. During rain, this can lead to pollution flashover, which in severe cases may cause insulation breakdown, resulting in short circuits or grounding faults. Therefore, the insulating parts of substation equipment must be periodically washed with water to prevent flashover and avoid insulation degradation that could lead to equipment failure.Which Equipment Is
Encyclopedia
10/10/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.