Pole discrepancy definition in circuit breaker

Edwiin
01/17/2025

Pole Discrepancy in Circuit Breakers

Pole discrepancy typically refers to differences in operating times between the three phases or poles of a switching device during the same operation. These discrepancies can affect the synchronization of the circuit breaker's poles, which is crucial for reliable operation.

Challenges in Continuous Monitoring

Determining pole discrepancy on a continuous basis can be less accurate because it often relies on break time or make time recordings obtained through current transformers (CTs). Break and make times can vary depending on how the contact movement coincides with the current waveforms. Additionally, the timing of current zero crossings in the second and third poles depends on system earthing conditions.

Mechanisms and Safety Systems

Circuit breakers where each pole has a separate operating mechanism are usually equipped with a safety system that trips the breaker if not all poles respond when a close command signal is given. This scenario represents an extreme example of pole discrepancy, measured in milliseconds. The system triggers only on unsuccessful closings and does not activate during single-phase open-close sequences, such as those occurring during automatic reclosure operations.

Standards and Acceptable Deviations

The International Electrotechnical Commission (IEC) specifies that the discrepancy in both opening and closing times should be less than one-half cycle of the rated frequency. Many manufacturers set a maximum acceptable deviation in opening times to 5 milliseconds.

Visual Representation

In the figure below, pole discrepancy (Td) is illustrated in a circuit breaker timing test. This visual aid helps to understand the variations in the timing of the poles and their impact on overall breaker performance.

Figure Caption

Figure: Illustration of pole discrepancy (Td) in a circuit breaker timing test. The graph shows the timing differences between the three poles during the breaking and making operations, highlighting the importance of minimizing these discrepancies for optimal performance.

Edwiin

Online condition monitoring device (OLM2) on high voltage Circuit Breakers
Online condition monitoring device (OLM2) on high voltage Circuit Breakers
This device is capable of monitoring and detecting various parameters according to the specifications outlined:SF6 Gas Monitoring:Utilizes a specialized sensor for measuring SF6 gas density.Capabilities include measuring gas temperature, monitoring SF6 leak rates, and calculating the optimal date for refilling.Mechanical Operation Analysis:Measures operational times for closing and opening cycles.Evaluates primary contacts separation speed, damping, and contact overtravel.Identifies signs of mec
Edwiin
02/13/2025
Anti pumping function in circuit breakers operating mechanism
Anti pumping function in circuit breakers operating mechanism
The anti - pumping function stands as a crucial characteristic of control circuits. In the absence of this anti - pumping function, assume that a user connects a maintained contact within the closing circuit. When the circuit breaker is closed onto a fault current, the protective relays will promptly trigger a tripping action. However, the maintained contact in the closing circuit will attempt to close the breaker (once again) onto the fault. This repetitive and dangerous process is referred to
Edwiin
02/12/2025
Ageing phenomena of current pass blades in high voltage disconnector switch
Ageing phenomena of current pass blades in high voltage disconnector switch
This failure mode has three primary origins:Electrical Causes: The switching of currents, such as loop currents, can lead to localized wear. At higher currents, an electric arc may burn at a specific spot, increasing the local resistance. As more switching operations occur, the contact surface wears down further, causing an increase in resistance.Mechanical Causes: Vibrations, often due to wind, are the main contributors to mechanical aging. These vibrations cause abrasion over time, leading to
Edwiin
02/11/2025
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Transient Recovery Voltage (TRV) stress similar to that encountered during a short-line fault can also occur due to the busbar connections on the supply side of a circuit breaker. This specific TRV stress is known as Initial Transient Recovery Voltage (ITRV). Given the relatively short distances involved, the time to reach the first peak of ITRV is typically less than 1 microsecond. The surge impedance of the busbars within a substation is generally lower compared to that of overhead lines.The f