What is an Over Current Relay?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China


What is an Over Current Relay?


Overcurrent Relay Definition


An overcurrent relay is a protective device that operates solely based on current without the need for a voltage coil.


Working Principle of Over Current Relay


The core component of an overcurrent relay is a current coil. Under normal conditions, the coil’s magnetic effect is too weak to overcome the restraining force and move the relay’s element. However, if the current increases sufficiently, its magnetic effect intensifies, surpassing the restraining force and prompting the moving element to alter the relay’s contact position. This fundamental working principle applies across different types of overcurrent relays.


Types of Over Current Relay


Depending upon time of operation, there are various types of Over Current relays, such as,

 


  • Instantaneous over current relay.

  • Definite time over current relay.

  • Inverse time over current relay.

 


Inverse time over current relay or simply inverse OC relay is again subdivided as inverse definite minimum time (IDMT), very inverse time, extremely inverse time over current relay or OC relay.


Instantaneous Over Current Relay


Construction and working principle of instantaneous over current relay is quite simple.In an instantaneous overcurrent relay, a magnetic core is wrapped with a current coil. An iron piece, supported by a hinge and a restraining spring, is positioned such that it remains detached from the core when current is below a preset threshold, keeping the normally open (NO) contacts open. Exceeding this threshold, the increased magnetic attraction pulls the iron to the core, closing the contacts.


We refer the pre-set value of current in the relay coil as pickup setting current. This relay is referred as instantaneous over current relay, as ideally, the relay operates as soon as the current in the coil gets higher than pick upsetting current. There is no intentional time delay applied. But there is always an inherent time delay which we cannot avoid practically. In practice, the operating time of an instantaneous relay is of the order of a few milliseconds.


b58d1e2d9d52b157b1e62dc1744a6168.jpeg

eef838fb4bb68cf33435835ad763ca68.jpeg


Definite Time Over Current Relay


This relay is created by applying intentional time delay after crossing pick up the value of the current. A definite time overcurrent relay can be adjusted to issue a trip output at an exact amount of time after it picks up. Thus, it has a time setting adjustment and pickup adjustment.


a97bfb0676289b6070e9f9b887f6ef49.jpeg


Inverse Time Over Current Relay


Inverse time overcurrent relays, typically found in induction type rotating devices, operate faster with increased input current, inversely varying their operation time with current. This characteristic is ideal for swift fault clearing in severe conditions. Additionally, this inverse timing can also be programmed into microprocessor-based relays, enhancing their versatility in overcurrent protection.


4807ad3835da85c436539992efded118.jpeg


Inverse Definite Minimum Time Over Current Relay or IDMT O/C Relay


In an overcurrent relay, achieving perfect inverse time characteristics is challenging. As system current rises, so does the secondary current from the current transformer (CT) until the CT saturates, halting further increases in relay current. This saturation marks the limit of inverse characteristic effectiveness, leading to a fixed minimum operation time despite further increases in fault level. This behavior defines the IDMT relay, noted for its inverse response initially, which stabilizes at high current levels.

 

Give a tip and encourage the author!
Recommended
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?A surge arrester should be installed on the high-voltage side of the H61 distribution transformer. According to SDJ7–79 "Technical Code for Design of Overvoltage Protection of Electric Power Equipment," the high-voltage side of an H61 distribution transformer should generally be protected by a surge arrester. The grounding conductor of the arrester, the neutral point on the low-voltage side of the transformer, and the
Felix Spark
12/08/2025
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Neutral Grounding Gap Protection Measures?In a certain power grid, when a single-phase ground fault occurs on a power supply line, both the transformer neutral grounding gap protection and the power supply line protection operate simultaneously, causing an outage of an otherwise healthy transformer. The main reason is that during a system single-phase ground fault, the zero-sequence overvoltage causes the transformer neutral grounding gap to break down. The resulting
Noah
12/05/2025
110kV Transformer Zero-Sequence Protection: Issues & Improvement Measures
110kV Transformer Zero-Sequence Protection: Issues & Improvement Measures
Problems with Zero-Sequence Protection of 110 kV TransformersIn an effectively grounded system, the neutral-to-ground displacement voltage of a transformer is limited to a certain level, and the neutral-point gap protection does not operate. The purpose of installing gap protection is to prevent damage to transformer insulation caused by elevated zero-sequence voltage in non-effectively grounded systems. The discharge gap only operates when a single-phase ground fault occurs, all directly ground
Echo
12/03/2025
Chinese Protection Relay Earns IEC 61850 Ed2.1 Level-A Certification
Chinese Protection Relay Earns IEC 61850 Ed2.1 Level-A Certification
Recently, the NSR-3611 low-voltage protection and control device and the NSD500M high-voltage measurement and control device—both developed by a Chinese protection and control equipment manufacturer—successfully passed the IEC 61850 Ed2.1 Server Level-A certification test conducted by DNV (Det Norske Veritas). The devices have been awarded the international Level-A certification by the Utilities Communication Architecture International Users Group (UCAIug). This milestone marks the manufacturer
Baker
12/02/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.