• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Top 5 Faults Found in H61 Distribution Transformers

Felix Spark
Felix Spark
Field: Failure and maintenance
China

Five Common Defects of H61 Distribution Transformers

1.Lead Wire Defects
Inspection Method: The three-phase DC resistance imbalance rate significantly exceeds 4%, or one phase is essentially open-circuited.
Remedial Measures: The core should be lifted for inspection to locate the defective area. For poor contacts, re-polish and tighten the connection. Poorly welded joints should be re-welded. If the welding surface area is insufficient, it should be enlarged. If the lead wire cross-section is inadequate, it should be replaced (with a larger size) to meet requirements.

2.Tap Changer Defects
Inspection Method: Measure DC resistance at different tap positions. If there is complete open circuit, the switch is likely burned out. If DC resistance imbalance occurs at a specific tap, individual contacts may be burned. A strong burnt smell indicates overheating or arcing.
Remedial Measures: Lift the core for inspection. If the switch contacts only show mild overheating, poor contact, or slight arcing marks, they can be removed, repaired, and reused. If severely burned or if there is evidence of ground discharge between contacts, the switch must be replaced. Ground discharge often causes deformation of the high-voltage winding’s tap section; in severe cases, the winding must be repaired or rewound (replaced).

3.Winding Defects
Inspection Method: Winding faults typically manifest as oil spraying from the conservator tank, bulging of the tank body, and a burnt oil odor. Insulation resistance and DC resistance measurements can be performed—insulation resistance near “zero” and unstable, increased DC resistance indicate winding issues.
Remedial Measures: Lift the core to assess the fault condition. Minor damage may be repairable for continued use. Severe faults require winding replacement. For conservator tank sealing issues, technical modifications should be implemented.

4.Reduced Insulation
Inspection Method: Regular insulation resistance tests and oil tests should be conducted on the transformer. Significant changes in measured values or results below the requirements specified in the "Regulations" indicate moisture ingress or degraded oil insulation performance.
Remedial Measures: If the transformer’s insulation resistance decreases, thorough drying is required. If oil insulation degrades, the oil should be replaced or filtered. Faulty seals and defective breathers (dehydrating breathers) must be repaired.

5.Core Defects
Inspection Method: Measure the insulation resistance of the core-through bolts. If it is less than 10 MΩ, repairs are needed.
Remedial Measures: After lifting the core, remove the damaged core-through bolt and replace its insulation.

Give a tip and encourage the author!
Recommended
How Voltage Harmonics Affect H59 Distribution Transformer Heating?
How Voltage Harmonics Affect H59 Distribution Transformer Heating?
The Impact of Voltage Harmonics on Temperature Rise in H59 Distribution TransformersH59 distribution transformers are among the most critical equipment in power systems, primarily functioning to convert high-voltage electricity from the power grid into low-voltage electricity required by end users. However, power systems contain numerous nonlinear loads and sources, which introduce voltage harmonics that adversely affect the operation of H59 distribution transformers. This article will discuss i
Echo
12/08/2025
What Is an H61 Distribution Transformer? Uses & Setup
What Is an H61 Distribution Transformer? Uses & Setup
H61 distribution transformers refer to transformers used in power distribution systems. In a distribution system, high-voltage electricity must be converted into low-voltage electricity via transformers to supply electrical equipment in residential, commercial, and industrial facilities. The H61 distribution transformer is a type of infrastructure equipment primarily used in the following scenarios: Supplying power from high-voltage grids to low-voltage grids: During power delivery, high-voltage
James
12/08/2025
How to Diagnose Faults in H59 Distribution Transformers by Listening to Their Sounds
How to Diagnose Faults in H59 Distribution Transformers by Listening to Their Sounds
In recent years, the accident rate of H59 distribution transformers has shown an upward trend. This article analyzes the causes of failures in H59 distribution transformers and proposes a series of preventive measures to ensure their normal operation and provide effective assurance for power supply.H59 distribution transformers play a vital role in power systems. With the continuous expansion of power system scale and the increasing single-unit capacity of transformers, any transformer failure n
Noah
12/08/2025
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?A surge arrester should be installed on the high-voltage side of the H61 distribution transformer. According to SDJ7–79 "Technical Code for Design of Overvoltage Protection of Electric Power Equipment," the high-voltage side of an H61 distribution transformer should generally be protected by a surge arrester. The grounding conductor of the arrester, the neutral point on the low-voltage side of the transformer, and the
Felix Spark
12/08/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.