Free Expert Guides on Power Systems, Circuit Design & Electrical Troubleshooting

Access free engineering resources from IEE Business—covering power design, circuit layout, equipment selection, and troubleshooting. Expert-developed guides help engineers, procurement, and project teams make better decisions. Stay ahead on smart grids, renewables, efficiency, and AI tools. Improve reliability, reduce downtime, and enhance outcomes with real-world solutions. Explore our knowledge hub today.
Dynamic (contact) resistance measurements (DRM) test on circuit breakers
This test serves to ascertain the length and condition of the current - carrying section of the arcing contacts within SF6 circuit breakers. DRM (Dynamic Resistance Measurement) tests are carried out by passing DC current through the breaker's main contacts during the breaker's operation. Subsequently, the breaker analyser computes and plots the resistance as a function of time. When contact movement is concurrently recorded, the resistance at each contact position can be determined. Through DRM
03/17/2025
Consult
Tip
Consult
Tip
Test equipments for AIS high voltage disconnector switch insulators cracks and life
Acoustic Emission: This method can be effectively employed to detect hazardous cracks in support insulators on - site in an offline mode. It is well - suited for identifying damages caused by mechanical stress, such as fatigue - related cracks. However, it is ineffective for detecting defects like pores. Non - destructive Ultrasound: Relying on the ultrasound impulse method, this technique works offline by exciting the insulator and its defects through the injection of short acoustic impulses.
03/12/2025
Consult
Tip
Consult
Tip
Optimisation SF6 handling procedures during on-site testing and commissioning for GIS
Gas Compartment Design and OptimizationPre-filled SF6 Gas CompartmentsGas compartments are pre-filled with sulfur hexafluoride (SF6) at a pressure slightly above atmospheric pressure for transportation. This ensures that the equipment remains stable during transit and reduces the workload required for on-site installation.Optimization to Minimize SF6 UsageGas compartments are optimized to use the minimum amount of SF6 necessary for a given functionality. Since the lowest achievable SF6 recovery
03/11/2025
Consult
Tip
Consult
Tip
Trending method in switchgear control and auxiliary circuits visual check
The trending method involves verifying whether a signal lies within the normal range, exhibits consistent behavior in relation to other information, and does not show signs of drifting or abnormal fluctuations. Here are some examples:1. Operating environmental conditionsMonitoring temperature and humidity levels. Deviations from the normal range can impact the performance of electrical and mechanical components.2. Circuit breaker mechanical operation counterAutomation data is used to monitor the
03/10/2025
Consult
Tip
Consult
Tip
Low temperature ambient effect for outdoor vacuum circuit breaker (VCB) operation
The vacuum arc - interrupting performance relies on the arcing within the metal vapor, which is generated from the contact material. Significantly, this process remains unaffected by low temperatures.A vacuum interrupter is typically fabricated from metals and ceramics and undergoes brazing at approximately 800 degrees Celsius. The material characteristics of both metal and ceramic, as well as the brazed joints between them, are inherently resistant to low - temperature impacts.Sliding guides ar
03/06/2025
Consult
Tip
Consult
Tip
Timing tests method in switchgears
Timing tests serve the purpose of determining the durations for operations such as opening (tripping), closing, close - opening, and reclosing. These time measurements are crucial for ensuring the safe and reliable operation of circuit breakers, thus being a key outcome of proper circuit breaker design.The main contact times are verified after production, during commissioning, and while the circuit breaker is in - service as part of periodic maintenance. To conduct these tests, timing test devic
03/05/2025
Consult
Tip
Consult
Tip
Power factor test on circuit breakers
Assessing the Integrity of Internal and External InsulationTo ensure the reliability and safety of circuit breakers, it is essential to evaluate both their internal and external insulation. Testing equipment typically has an output voltage of 10 kV and is designed to be portable so that it can be used in all substation environments. While this testing is primarily used for oil circuit breakers (CBs), it can also be applied to SF6 switchgear.Purpose of Power Factor TestsPower factor tests are con
03/03/2025
Consult
Tip
Consult
Tip
Vacuum Circuit Breakers Testing Methods
When vacuum interrupters are manufactured or used in the field, there are three tests used to validate their functionality: 1. Contact Resistance Test; 2. High Potential Withstand Test; 3. Leak-rate Test.Contact Resistance Test During the contact resistance test, a micro-ohmmeter is applied to the closed contacts of the vacuum interrupter (VI), and the resistance is measured and recorded. The result is then compared against the design specifications and/or the average values for other vacuum in
03/01/2025
Consult
Tip
Consult
Tip
Bellows role in vacuum interrupters
Introduction to Vacuum Interrupters and BellowsWith technological advancements and the growing concern over global warming, vacuum circuit breakers have emerged as a significant consideration in the electrical engineering domain.Future power grids are placing increasingly stringent demands on the switching performance of circuit breakers, with a particular emphasis on higher switching speeds and extended operational lifetimes. In medium - voltage circuit breakers, vacuum interrupters (VIs) have
02/28/2025
Consult
Tip
Consult
Tip
Functional and operational tests for medium voltage circuit breaker operating mechanism components
Circuit Breaker Operation TestClose Operation Test – Local/RemoteThis test is conducted manually, locally, and remotely. In the manual operation test, the spring is charged manually, and the breaker is closed and opened manually as well. For local operation, control power and AC supply are provided to the spring charging motor, and the circuit breaker is closed using the TNC switch. The function of the closing coil and the operation of the spring charging motor are observed. If remote
02/26/2025
Consult
Tip
Consult