• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Optimisation SF6 handling procedures during on-site testing and commissioning for GIS

Edwiin
Edwiin
Field: Power switch
China

Gas Compartment Design and Optimization

Pre-filled SF6 Gas Compartments

Gas compartments are pre-filled with sulfur hexafluoride (SF6) at a pressure slightly above atmospheric pressure for transportation. This ensures that the equipment remains stable during transit and reduces the workload required for on-site installation.

Optimization to Minimize SF6 Usage

Gas compartments are optimized to use the minimum amount of SF6 necessary for a given functionality. Since the lowest achievable SF6 recovery pressure is defined, the mass of SF6 released into the atmosphere is directly proportional to the size of the gas compartment. Through this optimization, the usage of SF6 can be minimized, thereby reducing environmental impact.

Use of Cable Plugs for Connecting High-Voltage Cables

Cable plugs are used to connect high-voltage cables, eliminating the need for complete SF6 recovery or opening the gas compartment when connecting the cables to the GIS. The cable compartment includes a socket, and the cables are simply plugged in. This method simplifies the connection process while maintaining the system's seal and safety.

Utilizing Power Voltage Transformers (VT) for High-Voltage Testing

During high-voltage testing, power voltage transformers (VT) can energize from the low-voltage side, thus avoiding the need to handle SF6 to connect the high-voltage source for testing. After the high-voltage test, the power VT can continue to function as a standard instrument transformer. This approach not only enhances testing efficiency but also reduces the need for SF6 handling.

Use of Bushing Connections for High-Voltage Testing

Bushing connections can be used to connect the high-voltage source for testing without the need to handle SF6. However, this method may introduce some limitations related to on-site partial discharge tests. Despite these limitations, it still provides a convenient and environmentally friendly way to perform high-voltage tests.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.