What tests are involved for IEC medium-voltage switchgear?
Mechanical Endurance TestingThe mechanical endurance of circuit breakers is tested according to IEC 62271-100, requiring 10,000 operations (M2 class). During testing at an overseas laboratory, the first prototype failed at 6,527 operations due to a trip spring fracture. The lab accepted this isolated failure, attributing it to spring installation issues. A second prototype was tested but similarly failed after over 6,000 operations due to another trip spring breakage. Consequently, the test lab