Brand | ROCKWILL |
Model NO. | CKSS-12 Electrical ring main unit switchgear |
Rated voltage | 12kV |
Rated frequency | 50/60Hz |
Series | CKSS |
As industrial enterprises and institutions build new buildings, from the perspective of power supply and distribution, distribution transformers are generally small and medium-sized, with a capacity of no more than 1250kva, long-term reliable power supply and infrequent operation of high-voltage switches. For this kind of users, the functions of ring network cabinet are not the most complete, but they can best meet the requirements of ring network. Due to large-scale urban construction, many large-scale high-rise buildings have sprung up, and substations are often located downstairs. According to the fire protection requirements, substations and distribution equipment must be "oil-free", and with regard to the rational use of building area, transformers and distribution equipment. Due to the need for further miniaturization of equipment, annular bodies, vacuum circuit breakers, dry-type transformers and dry-type transformers are suitable for high-rise buildings under construction. The ring network cabinet has the advantages of simple structure, stable and safe operation, low maintenance cost and low operation cost. Compared with the switchgear with circuit breaker, it has outstanding advantages. The ring main cabinet needs higher function and smaller size load switch.
Product features
Cabinet structure: the inflatable compartment is made of 3 ~ 5mm thick stainless steel plate, which is welded by welding robot after being processed by NC machine tool, with less welding deformation and good air tightness. The other compartments are made of high-quality cold-rolled steel plate, which is welded after NC bending, with the characteristics of high precision and good strength; Each functional unit is an independent module, which is very convenient for assembly. Each sealed compartment of the cabinet is equipped with an independent pressure relief channel to ensure personal safety and equipment operation to the greatest extent. b. Protection grade: IP67 for inflation isolation; Low voltage cabinet is IP4X.
Normal service conditions
Ambient air temperature: maximum 40 ℃, (average value within 24 hours shall not exceed 35 ℃), minimum - 25 ℃
Altitude: no more than 3000m (coordinate with the manufacturer when it exceeds 3000m)
Air humidity: the average value of daily relative humidity shall not be greater than 95%, and the average value of monthly relative humidity shall not be greater than 90%
The amplitude of electromagnetic interference induced in the secondary system shall not exceed 1.6kV
Technical parameter
Rated voltage |
kV |
12 |
Power frequency withstand voltage phase to phase/earth |
kV |
42 |
Power frequency withstand voltage Between open contacts |
kV |
48 |
Impulse withstand voltage phase to phase/earth |
kV |
75 |
Impulse withstand voltage Between open contacts |
kV |
85 |
Rated frequency |
Hz |
50 |
Rated current |
A |
630 |
Rated short-time withstand current (4s) |
kA |
20/25 |
Rated peak withstand current |
kA |
50/63 |
Rated active load breaking current |
A |
630 |
Rated closed loop breaking current |
A |
630 |
Mechanical lifetime |
Ops |
10000 |