66-500kV High-Voltage Power Cables with Cross-Linked Polyethylene (XLPE) Insulation

  • 66-500kV High-Voltage Power Cables with Cross-Linked Polyethylene (XLPE) Insulation

Key attributes

Brand Wone Store
Model NO. 66-500kV High-Voltage Power Cables with Cross-Linked Polyethylene (XLPE) Insulation
Rated voltage 48/66kV
Rated frequency 50/60Hz
Series YJLW

Product descriptions from the supplier

Description

Product Description

66 - 500kV High-Voltage Power Cables with Cross-Linked Polyethylene (XLPE) Insulation are crucial components in modern power transmission systems. Designed to operate within a voltage range from 66 kilovolts to 500 kilovolts, these cables are primarily used for long - distance and large - capacity power transmission, connecting major power generation sources like power plants to substations in urban centers, industrial areas, and other key electricity - consuming regions. The cross - linked polyethylene insulation provides excellent electrical and thermal properties, ensuring stable and reliable power delivery over extended periods.

 Features

  • Wide Voltage Adaptability:These cables can handle a broad voltage spectrum from 66kV to 500kV. This flexibility allows them to be applied in various power grid scenarios, from regional high - voltage distribution networks to long - haul super - high - voltage transmission lines. For example, in a large - scale industrial zone, 66kV cables can distribute power within the area, while 500kV cables can connect the zone to a distant power plant.

  • Superior Insulation Performance:XLPE insulation offers high dielectric strength, effectively preventing electrical breakdown. It has a low dielectric loss, reducing energy dissipation during power transmission. Additionally, XLPE has good thermal stability, capable of withstanding continuous operating temperatures up to around 90°C, and short - circuit temperatures as high as 250°C for a short duration. This ensures the cable's long - term reliability and safety under different electrical load conditions.

  • Long - Distance Transmission Capability:Engineered for long - distance power transmission, these cables minimize power losses. The high - quality conductors, usually made of high - purity copper or aluminum, combined with the excellent insulation properties, enable efficient power transfer over tens or even hundreds of kilometers. This is essential for connecting remote power generation facilities, such as wind farms in coastal areas or hydroelectric power plants in mountainous regions, to major population centers.

  • Robust Mechanical and Environmental Resistance:They are constructed to withstand various mechanical stresses, including tensile forces, bending, and external impacts. The outer sheaths are often made of durable materials like polyethylene or polyvinyl chloride, providing protection against moisture, chemical corrosion, and physical damage. This makes the cables suitable for different installation environments, whether buried underground, laid in tunnels, or installed overhead.

Product model

Model

name

Copper core

Aluminum core

YJLW02

YJLLW02

XLPE Insulated Wrinkled Aluminum Sheathed PVC Sheathed Power Cable

YJLW02-Z

YJLLW02-Z

XLPE Insulated Wrinkled Aluminum Sheath PVC Sheathed Longitudinal Water Blocking Power Cable

YJL02

YJLL02

Cross-linked polyethylene insulated smooth aluminum sheathed PVC sheathed power cable

YJL02-Z

YJLL02-Z

XLPE insulated smooth aluminum sheathed PVC sheathed longitudinal water-blocking power cable

YJLW03

YJLLW03

XLPE Insulated Wrinkled Aluminum Sheathed Polyethylene Sheathed Power Cable

YJLW03-Z

YJLLW03-Z

XLPE Insulated Wrinkled Aluminum Sheathed Polyethylene Sheathed Longitudinal Water Blocking Power Cable

YJL03

YJLL03

Cross-linked polyethylene insulated smooth aluminum sheathed polyethylene sheathed power cable

YJL03-Z

YJLL03-Z

Cross-linked polyethylene insulated smooth aluminum sheathed polyethylene sheathed longitudinal water-blocking power cable

Product specifications

Rated voltage U0/U kV

48/66

64/110

127/220

290/500

Section/mm2

240~1600

240~1600

400~2500

800~2500

Product performance indicators

  • Conductor DC resistance

Nominal cross-section/mm2

Maximum Conductor Resistance at 20°C/(Ω/km)

copper

aluminium

240

0.0754

0.125

300

0.0601

0.100

400

0.0470

0.0778

500

0.0366

0.0605

630

0.0283

0.0469

800

0.0221

0.0367

800

0.0221

-

1000

0.0176

-

1200

0.0151

-

1400

0.0129

-

1600

0.0113

-

1800

0.0101

-

2000

0.0090

-

2200

0.0083

-

2500

0.0072

-

  • Partial discharge test

Cable rated voltage U0/U
kV

48/66

64/110

127/220

290/500

Partial discharge test

Test voltage/kV

72

96

190

435

Sensitivity/pC

<10

<5

Discharge volume

No discharge detected

  • Voltage test

Cable rated voltage U0/U
kV

48/66

64/110

127/220

290/500

Power frequency voltage test

Test voltage/kV

120

160

318

580

Duration/min

30

30

30

60

Performance requirements:

No breakdown

Product use

This product is suitable for transmission and distribution lines with a rated voltage of 66~500kV for transmission and distribution energy, and the scope of use includes direct burial, tunnels, cable trenches, pipeline occasions, etc., and can be produced according to customer requirements (low smoke and halogen-free) flame retardant, termite prevention type, etc.

Implementation standards

This product performsIEC 60840-2020、IEC 62607-2022、GB/T 11017-2014、GB/T 18890-2015、GB/T 22078-2008。

Characteristics of use

  • The long-term maximum temperature allowed by the conductor during normal operation of the cable is 90 °C, and the maximum temperature allowed by the cable conductor is 250 °C in the event of a short circuit (the maximum duration does not exceed 5s);

  • The laying temperature of the cable should not be lower than 0°C;

  • The minimum bending radius is 20D (D is the outer diameter of the cable).

  • Product model specifications

Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 1000m² Total staff: Highest Annual Export(usD): 300000000
Workplace: 1000m²
Total staff:
Highest Annual Export(usD): 300000000
Services
Business Type: Sales
Main Categories: Wire cable/High Voltage Electrical Apparatus/Low Voltage Electrical Apparatus/Instrument meters/New energy/Tester/Integrated Electrical Equipment/Production equipment/Generator/Electrical fittings/Instrument Transformer/Equipment Parts
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

  • Main Transformer Accidents and Light Gas Operation Issues
    1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
    02/05/2026
  • Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
    Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
    01/30/2026
  • Neutral point grounding operation mode for 110kV~220kV power grid transformers
    The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
    01/29/2026
  • Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
    Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
    01/29/2026
  • Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
    Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
    01/29/2026
  • Understanding Transformer Neutral Grounding
    I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
    01/29/2026

Related Solutions

  • Dedicated Vacuum Contactor Solution for Port Shore Power Systems
    I. Background and Challenges​Shore power systems have become core technical equipment for ports to reduce carbon emissions and noise pollution. However, these systems face two major challenges in the harsh operational environment of ports:​Severe Environmental Corrosion: High humidity and salt spray in port areas cause serious corrosion to metal components and enclosures of electrical equipment, significantly impacting electrical lifespan and operational reliability.​High Switching Requirements:
    09/13/2025
  • ABB Vacuum Contactor KC2 Power Supply System Technical Transformation Plan
    Issue Overview​The 10kV air compressor starting system of a company utilizes the ABB vacuum contactor KC2 as the control component for the operating circuit. The dedicated wide-voltage power supply module paired with this contactor presents the following issues:​Frequent failures: The power supply module fails to properly transition the voltage from 300V to 12V, resulting in fuse blowouts.​Poor heat dissipation: Enclosed installation of the module leads to insufficient heat dissipation, acceler
    09/13/2025
  • Solution for Medium-Voltage Motor Control and Protection Using Vacuum Contactor-Fuse (VCF) in a Coal Conveying System
    1.Project BackgroundA coal conveying system comprises 15 belt conveyors driven by medium-voltage motors. The system operates under complex conditions, with motors often subjected to heavy loads and frequent starts. To address these challenges and achieve effective control and reliable protection during motor startup, the project comprehensively adopts Vacuum Contactor-Fuse (VCF) combination devices for the 6kV medium-voltage motor power distribution. This solution details the technical features,
    09/13/2025
Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.