22kV 24kV 25.8kV 27kV Self-powered single-phase Automatic Recloser / Reclosure Direct Supply

  • 22kV 24kV 25.8kV 27kV Self-powered single-phase Automatic Recloser / Reclosure Direct Supply
  • 22kV 24kV 25.8kV 27kV Self-powered single-phase Automatic Recloser / Reclosure Direct Supply

Key attributes

Brand ABB
Model NO. 22kV 24kV 25.8kV 27kV Self-powered single-phase Automatic Recloser / Reclosure Direct Supply
Rated voltage 27kV
Rated normal current 200A
Rated frequency 50/60Hz
Series Eagle

Product descriptions from the supplier

Description

Product Introduction

Product Range:Up to 27kV, 200A, 8kA

This is a single phase self-powered vacuum interrupting recloser. It can be mounted directly to the pole as a new installation or a replacement to oil filled single-phase reclosers. It can be installed separately on single phase laterals or in a group of three for a three-phase lateral circuit.
Eagle recloser drastically improves the reliability indices for utilities simply by eliminating the sustained interruptions experienced by the customers due to fuse-blowing schemes and momentary interruptions due to fuse-saving schemes. By reducing the number of truck rolls, the utility can save on operational costs and at the same time avoid revenue losses due to outages.
Eagle provides highest interrupting rating among its class with higher BIL (basic insulation level) and continuous current rating providing application from major three-phase feeder laterals to the end-of-line single phase laterals.

Technical parameters

The voltage classes of some of these Automatic Reclosers include 6kV, 6.3kV, 6.6kV, 6.9kV, 7.2kV, 10kV, 10.5kV, 11kV, 11.5kV, 12kV, 13.2kV, 13.8kV, 14.5kV, 14.4kV, 15kV, 15.5kV, 15.6kV, 17.5kV, 20kV, 21.9kV, 22kV, 24kV, 30kV, 33kV, 33.5kV, 34.5kV, 35kV, 36kV, 38kV, 38.5kV, 40.5kV, 44kV, 45kV, 46kV, 66kV and 69kV. Rated Short-Circuit Breaking Current includes 8kA, 12.5kA, 16kA, 20kA, 25kA, 31.5kA and customization is available.

The following technical parameters fully present the product's electrical parameter configurations, mechanical performance parameters, and dimensional details to facilitate precise system integration and application planning.

Technical specifications for hardware

Nominal operating voltage

15/27 kV

Rated max. Voltage

27 kV

Rated power frequency

60 HZ

Rated continuous current

200 A

Rated symmetrical interrupting current

8 kA RMS

Rated short-time withstand current

8 kA

Rated short-time withstand duration

1 sec

Rated peak-withstand current

20.8 kA

Rated lightning impulse withstand voltage (BIL)

125 kV

Rated power frequency dry/wet withstand (60 s)

60 kV

Creep distance H1 to H2 terminal

668 mm

Recloser unit weight

20 kg (44 lb)

Auxiliary power

12 V DC (for programming)

Operating temperature

-25 °C to +60 °C

Rated number of operations

10,000 operations

Ingress protection

IP65

Standards compliance

IEEE C37.60/IEC 62271-111

Technical specifications for electronics and software

Modes of operation

Autorecloser

Sectionalizer  

Breaker/switch

Rated operating duty

Min O 0.2 s CO 2 s CO 2 s CO lockout

Max O 5 s CO 5 s CO 20 s CO lockout

Minimum pickup fault current

10 A

Minimum current for WI-FI communication

5 A (1)

Minimum power-up time

25 ms

Protection functions

50/51P

Other functions

Second harmonic inrush restraint

Cold load pickup

Non-reclose/hot line tag

Switch on to fault

TCC curve accuracy

> 50 A: ±1%

> 20 A: ±2.5%

> 10 A: ±5%

< 10 A: ±1.6 A

Operating curves

ANSI/IEC, recloser, fuse, hydraulic and custom curves

Records

Events and fault records (1000)

Internal device events (100)

Disturbance records (250)

Load profile (60 days)

Security log (1000)

Communication

Wi-Fi with WPA2 128 Bit-Encryption

Auto Disable Feature

Hide SSID Feature

( 1) Tripping/reclosing capability is not dependent on availability of a specific minimum preload current.

Key features

Key features highlight the product&rsquo;s innovative design, high-performance capabilities, and operational advantages, ensuring optimal suitability for diverse industrial and power system requirements.

  • Can function as a recloser, breaker, or a sectionalizer

  • Main operating handle for mechanical opening, closing and resetting without relying on battery backup

  • Mounting design that allows manual swing down open for a visual disconnect

  • Conventional open/close indicator cup semaphore and a LED beacon for lockout indication

  • Adaptable non-reclose and hot line tag modes

  • Wide selection of fuse, recloser and user programmable protection curves

  • Platform / device independent web-based user interface

  • Full event, security, loading and fault recording capability with GPS time stamps

  • 128-bit encryption with WPA2 level security for Wi-Fi connection

  • Cold load pickup and 2nd harmonic inrush blocking for each curve

Key benefits

Key benefits underscore the product&rsquo;s reliability, efficiency, and cost-effectiveness, delivering tangible value for power distribution and industrial applications.

  • Can be applied on circuits up to 27kV, 200A &ndash; avoiding need to stock multiple part numbers

  • High fault current rating (8 kA) allows installation across the feeder

  • Self-powered design eliminating the need for an external power source

  • &ldquo;No arcing&rdquo; operations to keep personnel safety intact

  • Battery-free operations provide a truly maintenance-free life cycle

  • Ability to restore power after an extended outage without the need for batteries

  • One-to-one replacement for hydraulic reclosers by using identical mounting and protection curves

  • Hassle-free web-based interface and secure Wi-Fi communication

Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 20000m² Total staff: Highest Annual Export(usD): 580000000
Workplace: 20000m²
Total staff:
Highest Annual Export(usD): 580000000
Services
Business Type: Sales
Main Categories: High Voltage Electrical Apparatus/Low Voltage Electrical Apparatus
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

  • Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding Electrodes
    Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding ElectrodesWhen the grounding electrode of an Ultra-High-Voltage Direct Current (UHVDC) transmission system is located close to a renewable energy power station, the return current flowing through the earth can cause a rise in ground potential around the electrode area. This ground potential rise leads to a shift in the neutral-point potential of nearby power transformers, inducing DC bias (or DC offset) in their
    01/15/2026
  • HECI GCB for Generators – Fast SF6 Circuit Breaker
    1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
    01/06/2026
  • Distribution Equipment Transformer Testing, Inspection, and Maintenance
    1.Transformer Maintenance and Inspection Open the low-voltage (LV) circuit breaker of the transformer under maintenance, remove the control power fuse, and hang a “Do Not Close” warning sign on the switch handle. Open the high-voltage (HV) circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the HV switchgear, and hang a “Do Not Close” warning sign on the switch handle. For dry-type transformer maintenance: first clean the porcel
    12/25/2025
  • How to Test Insulation Resistance of Distribution Transformers
    In practical work, insulation resistance of distribution transformers is generally measured twice: the insulation resistance between thehigh-voltage (HV) windingand thelow-voltage (LV) winding plus the transformer tank, and the insulation resistance between theLV windingand theHV winding plus the transformer tank.If both measurements yield acceptable values, it indicates that the insulation among the HV winding, LV winding, and transformer tank is qualified. If either measurement fails, pairwise
    12/25/2025
  • Design Principles for Pole-Mounted Distribution Transformers
    Design Principles for Pole-Mounted Distribution Transformers(1) Location and Layout PrinciplesPole-mounted transformer platforms should be located near the load center or close to critical loads, following the principle of “small capacity, multiple locations” to facilitate equipment replacement and maintenance. For residential power supply, three-phase transformers may be installed nearby based on current demand and future growth projections.(2) Capacity Selection for Three-Phase Pole-Mounted Tr
    12/25/2025
  • Transformer Noise Control Solutions for Different Installations
    1.Noise Mitigation for Ground-Level Independent Transformer RoomsMitigation Strategy:First, conduct a power-off inspection and maintenance of the transformer, including replacing aged insulating oil, checking and tightening all fasteners, and cleaning dust from the unit.Second, reinforce the transformer foundation or install vibration isolation devices—such as rubber pads or spring isolators—selected based on the severity of vibration.Finally, strengthen sound insulation at weak points of the ro
    12/25/2025

Related Solutions

  • Electrical House (eHouse) Solutions
    Reduce site complexity, improve lead timeABB eHouses are prefabricated transportable substations, designed to house medium voltage and low voltage switchgear, critical power equipment and automation cabinets.An eHouse solution is a cost effective, risk reduced alternative to conventional concrete block and brick construction. Each eHouse module is custom engineered to meet application requirements with respect to equipment layout, site footprint limitations and logistics considerations.Installat
    04/16/2025
  • Improve speed to deployment Modular prefabricated and pre-engineered solutions
    Reduce site works and risk of schedule delays and cost overrunsOverview:With a complicated data center project that has short delivery timelines, prefabricated modular solutions and pre-engineered modular solutions may be the answer.Modular solutions are ideal for enterprise, colocation, edge and cloud data centers, where project replicability and expandability are critical, alongside fast deployment time.Reduce risk by leveraging prefabricated and integrated solutions:Fast track projects with p
    04/16/2025
Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now