5 Common Transmission Line Faults and Effective Prevention Methods

Edwiin
Edwiin
Field: Power switch
China

1. Overview

A transmission line fault is a sudden power interruption caused by various factors. To restore supply and prevent recurrence, operators must first locate the fault point, identify the type, determine the cause, and implement repairs.

The most common faults include:

  • Lightning strikes

  • Ice buildup (icing)

  • Wind deviation (wind sway)

  • Bird-related issues

  • Pollution flashover

  • External damage

Understanding these faults and their prevention is critical for grid reliability.

2. Lightning Strike Faults

Lightning is a powerful atmospheric discharge from charged thunderclouds. For transmission lines, it causes two main hazards:

  • Direct strikes: Hit conductors, ground wires, or towers, causing high currents and flashovers.

  • Induced surges: Occur when lightning strikes nearby, inducing high voltages on lines, leading to insulation breakdown.

Causes

Lightning can cause tripping, equipment damage, outages, and even widespread blackouts—especially in high-lightning areas.

Prevention Measures

  • Install shield wires with reduced protection angles

  • Lower tower grounding resistance

  • Use coupling ground wires or buried conductors

  • Install line surge arresters

  • Apply differential insulation or arc protection (e.g., arc horns, parallel gaps)

  • Enhance insulation levels

  • Use automatic reclosing to restore power after transient faults

  • Install pre-discharge rods or negative-angle needles

3. Ice Buildup (Icing) Faults

Icing occurs in cold, wet conditions (–5°C to 0°C) with fog or drizzle, forming glaze ice. Repeated freeze-thaw cycles create dense mixed ice, leading to heavy accumulation on conductors.

Ice typically forms on the windward side and may cause conductor twisting, resulting in circular or elliptical shapes.

Ice Buildup (Icing) Faults.jpg

Causes

Climate change has increased extreme weather, making icing a major threat. It can cause:

  • Mechanical overloading

  • Galloping (aerodynamic instability)

  • Ice flashover

  • Uneven de-icing jumps

  • Broken conductors or collapsed towers

Prevention Strategies: Avoid, Resist, Modify, Prevent, De-ice

  • Route lines away from icing-prone areas (e.g., lakes, high altitudes, wind corridors)

  • Reduce span lengths and tension section length

  • Strengthen towers and ground wire supports

  • Use anti-icing conductors (e.g., high-strength ACSR)

  • Install armor rods for mechanical protection

  • Use V-string or double suspension insulators to prevent ice bridging

4. Wind Deviation (Wind Sway) Faults

Wind deviation is the lateral movement of conductors or insulators under wind load, reducing air clearance and causing flashover—especially on jumper wires or suspension strings.

Wind Deviation (Wind Sway) Faults.jpg

Types

  • Jumper swing on angle towers

  • Insulator string tilt under wind pressure

  • Conductor-to-conductor or conductor-to-tower clearance reduction

Insulator string sway is the leading cause of wind-induced tripping.

Causes

  • Design limitations: Many lines are rated for 30 m/s winds, underestimating microclimate or localized high-wind zones (e.g., canyons, ridges).

  • Strong localized winds: Typhoons, downbursts, or gusts increase conductor displacement and electric field stress at sharp hardware points.

  • Rain effects: Wind-driven rain forms conductive water paths, lowering air gap insulation strength.

Prevention Measures

  • Increase tower head clearance and design safety margins

  • Reduce spans and conductor sag

  • Add weights (dampers) to insulator strings

  • Use V-string or double-string configurations

  • Install wind-resistant guy wires or external tension cables

5. Bird-Related Faults

Bird-related faults occur when birds nesting, defecating, or flying near lines cause flashovers or equipment damage.

Bird-Related Faults.jpg

Fault Types

  • Nest-related: Long nesting materials bridge conductors and towers.

  • Dropping-related: Droppings reduce insulator insulation, causing flashover.

  • Bird-body short circuits: Large birds bridge phases or conductor-to-ground.

  • Pecking damage or collision faults

  • Secondary faults from nesting debris

Causes

  • Nesting materials creating conductive paths

  • Conductive bird droppings on insulators

  • Birds perching or flying near energized parts

Prevention Measures

  • Route new lines ≥5 km from bird habitats and avoid flight corridors

  • Install physical deterrents:

    • Bird guards, nest blockers, spikes, shields

    • Large-diameter or bird-safe insulators

    • Insulator covers and waterproof barriers

  • Use active repellents:

    • Sonic, visual, or intelligent sound-and-light bird scarers

  • Provide alternatives:

    • Install artificial nests or bird perches away from equipment

Give a tip and encourage the author!
Recommended
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-voltage distribution lines refer to the circuits that, through a distribution transformer, step down the high voltage of 10 kV to the 380/220 V level—i.e., the low-voltage lines running from the substation to the end-use equipment.Low-voltage distribution lines should be considered during the design phase of substation wiring configurations. In factories, for workshops with relatively high power demand, dedicated workshop substations are often installed, where transformers supply power direc
James
12/09/2025
Three-Phase SPD: Types, Wiring & Maintenance Guide
Three-Phase SPD: Types, Wiring & Maintenance Guide
1. What Is a Three-Phase Power Surge Protective Device (SPD)?A three-phase power surge protective device (SPD), also known as a three-phase lightning arrester, is specifically designed for three-phase AC power systems. Its primary function is to limit transient overvoltages caused by lightning strikes or switching operations in the power grid, thereby protecting downstream electrical equipment from damage. The SPD operates based on energy absorption and dissipation: when an overvoltage event occ
James
12/02/2025
Railway 10kV Power Through Lines: Design & Operation Requirements
Railway 10kV Power Through Lines: Design & Operation Requirements
The Daquan Line has a large power load, with numerous and scattered load points along the section. Each load point has a small capacity, with an average of one load point every 2-3 km, so two 10 kV power through lines should be adopted for power supply. High-speed railways use two lines for power supply: primary through line and comprehensive through line. The power sources of the two through lines are taken from the dedicated bus sections fed by the voltage regulators installed in each power di
Edwiin
11/26/2025
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Railway power systems primarily consist of automatic block signaling lines, through-feeder power lines, railway substations and distribution stations, and incoming power supply lines. They provide electricity to critical railway operations—including signaling, communications, rolling stock systems, station passenger handling, and maintenance facilities. As an integral part of the national power grid, railway power systems exhibit distinct characteristics of both electrical power engineering and
Echo
11/26/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.