5 Common Transmission Line Faults and Effective Prevention Methods

Edwiin
Edwiin
Field: Power switch
China

1. Overview

A transmission line fault is a sudden power interruption caused by various factors. To restore supply and prevent recurrence, operators must first locate the fault point, identify the type, determine the cause, and implement repairs.

The most common faults include:

  • Lightning strikes

  • Ice buildup (icing)

  • Wind deviation (wind sway)

  • Bird-related issues

  • Pollution flashover

  • External damage

Understanding these faults and their prevention is critical for grid reliability.

2. Lightning Strike Faults

Lightning is a powerful atmospheric discharge from charged thunderclouds. For transmission lines, it causes two main hazards:

  • Direct strikes: Hit conductors, ground wires, or towers, causing high currents and flashovers.

  • Induced surges: Occur when lightning strikes nearby, inducing high voltages on lines, leading to insulation breakdown.

Causes

Lightning can cause tripping, equipment damage, outages, and even widespread blackouts—especially in high-lightning areas.

Prevention Measures

  • Install shield wires with reduced protection angles

  • Lower tower grounding resistance

  • Use coupling ground wires or buried conductors

  • Install line surge arresters

  • Apply differential insulation or arc protection (e.g., arc horns, parallel gaps)

  • Enhance insulation levels

  • Use automatic reclosing to restore power after transient faults

  • Install pre-discharge rods or negative-angle needles

3. Ice Buildup (Icing) Faults

Icing occurs in cold, wet conditions (–5°C to 0°C) with fog or drizzle, forming glaze ice. Repeated freeze-thaw cycles create dense mixed ice, leading to heavy accumulation on conductors.

Ice typically forms on the windward side and may cause conductor twisting, resulting in circular or elliptical shapes.

Ice Buildup (Icing) Faults.jpg

Causes

Climate change has increased extreme weather, making icing a major threat. It can cause:

  • Mechanical overloading

  • Galloping (aerodynamic instability)

  • Ice flashover

  • Uneven de-icing jumps

  • Broken conductors or collapsed towers

Prevention Strategies: Avoid, Resist, Modify, Prevent, De-ice

  • Route lines away from icing-prone areas (e.g., lakes, high altitudes, wind corridors)

  • Reduce span lengths and tension section length

  • Strengthen towers and ground wire supports

  • Use anti-icing conductors (e.g., high-strength ACSR)

  • Install armor rods for mechanical protection

  • Use V-string or double suspension insulators to prevent ice bridging

4. Wind Deviation (Wind Sway) Faults

Wind deviation is the lateral movement of conductors or insulators under wind load, reducing air clearance and causing flashover—especially on jumper wires or suspension strings.

Wind Deviation (Wind Sway) Faults.jpg

Types

  • Jumper swing on angle towers

  • Insulator string tilt under wind pressure

  • Conductor-to-conductor or conductor-to-tower clearance reduction

Insulator string sway is the leading cause of wind-induced tripping.

Causes

  • Design limitations: Many lines are rated for 30 m/s winds, underestimating microclimate or localized high-wind zones (e.g., canyons, ridges).

  • Strong localized winds: Typhoons, downbursts, or gusts increase conductor displacement and electric field stress at sharp hardware points.

  • Rain effects: Wind-driven rain forms conductive water paths, lowering air gap insulation strength.

Prevention Measures

  • Increase tower head clearance and design safety margins

  • Reduce spans and conductor sag

  • Add weights (dampers) to insulator strings

  • Use V-string or double-string configurations

  • Install wind-resistant guy wires or external tension cables

5. Bird-Related Faults

Bird-related faults occur when birds nesting, defecating, or flying near lines cause flashovers or equipment damage.

Bird-Related Faults.jpg

Fault Types

  • Nest-related: Long nesting materials bridge conductors and towers.

  • Dropping-related: Droppings reduce insulator insulation, causing flashover.

  • Bird-body short circuits: Large birds bridge phases or conductor-to-ground.

  • Pecking damage or collision faults

  • Secondary faults from nesting debris

Causes

  • Nesting materials creating conductive paths

  • Conductive bird droppings on insulators

  • Birds perching or flying near energized parts

Prevention Measures

  • Route new lines ≥5 km from bird habitats and avoid flight corridors

  • Install physical deterrents:

    • Bird guards, nest blockers, spikes, shields

    • Large-diameter or bird-safe insulators

    • Insulator covers and waterproof barriers

  • Use active repellents:

    • Sonic, visual, or intelligent sound-and-light bird scarers

  • Provide alternatives:

    • Install artificial nests or bird perches away from equipment

Give a tip and encourage the author!
Recommended
MVDC: Future of Efficient, Sustainable Power Grids
MVDC: Future of Efficient, Sustainable Power Grids
The Global Energy Landscape Is Undergoing a Fundamental Transformation toward a "fully electrified society," characterized by widespread carbon-neutral energy and the electrification of industry, transportation, and residential loads.In today’s context of high copper prices, critical mineral conflicts, and congested AC power grids, Medium-Voltage Direct Current (MVDC) systems can overcome many limitations of traditional AC networks. MVDC significantly enhances transmission capacity and efficienc
Edwiin
10/21/2025
Grounding Causes of Cable Lines and the Principles of Incident Handling
Grounding Causes of Cable Lines and the Principles of Incident Handling
Our 220 kV substation is located far from the urban center in a remote area, surrounded primarily by industrial zones such as Lanshan, Hebin, and Tasha Industrial Parks. Major high-load consumers in these zones—including silicon carbide, ferroalloy, and calcium carbide plants—account for approximately 83.87% of our bureau’s total load. The substation operates at voltage levels of 220 kV, 110 kV, and 35 kV.The 35 kV low-voltage side mainly supplies feeders to ferroalloy and silicon carbide plants
Felix Spark
10/21/2025
Overhead Power Lines & Towers: Types, Design & Safety
Overhead Power Lines & Towers: Types, Design & Safety
Besides ultra-high voltage AC substations, what we encounter more frequently are power transmission and distribution lines. Tall towers carry conductors that leap across mountains and seas, stretching into the distance before reaching cities and villages. This is also an interesting topic—today, let's explore transmission lines and their supporting towers.Power Transmission and DistributionFirst, let’s understand how electricity is delivered. The electric power industry primarily consists of fou
Encyclopedia
10/21/2025
Automatic Reclosing Modes: Single, Three-Phase & Composite
Automatic Reclosing Modes: Single, Three-Phase & Composite
General Overview of Automatic Reclosing ModesTypically, automatic reclosing devices are categorized into four modes: single-phase reclosing, three-phase reclosing, composite reclosing, and disabled reclosing. The appropriate mode can be selected based on load requirements and system conditions.1. Single-Phase ReclosingMost 110kV and higher transmission lines employ three-phase single-shot reclosing. According to operational experience, over 70% of short-circuit faults in high-voltage overhead li