Test for Thickness of Insulation of Power Cable

03/22/2024

What Is Test For Thickness Of Insulation Of Power Cable

This test covers the technique to confirm the thickness of insulation and sheath of electric power cables. Adequate thickness of insulation and sheath is provided to power cable meet up the voltage stresses and mechanical stresses imposed on the cable during its service life. The measurement of such thickness is necessary to verify whether it is as per specified limit or not. These dimensions ensure safe and reliable performance of the cable.

Apparatus required to test for thickness of insulation of Power Cable

This is purely a measurement process, hence the apparatus for the test are to be chosen very carefully. There should be, a micrometer gauge capable of measuring at least 0.01 mm variation, a vernier caliper which can clearly read at least 0.01 mm count, a measuring microscope with linear magnification of not less than 7 times and the possibility of reading at least to 0.01 mm, and a graduated magnifying glass can read clearly at least 0.01 mm.

First different pieces of specimen are to be prepared for different measuring instruments and methods. The specimen may be of 2 types 1st one is pieces of core cable and 2nd one is slice pieces.
sheath thickness test
insulation thickness test

Procedure for testing of Thickness of Insulation of Power Cable

Approximately not less than 300 mm long pieces of core or cable cut from final product is used in the case of round conductor and outer sheath. The specimen must cut from the final product and remove all the covering materials above insulation or sheath without damaging the insulation and sheath. Slice pieces cut from the cable are used for optical measurement. In this case the materials outside and inside of the insulation or sheath which to be measured, can be removed if required. The slice is cut in sufficiently thin pieces along the plane perpendicular to the axis of the cable. The measurements are preferably taken at room temperature. The diameter of core of the cable and the diameter of insulated core and cable with insulation as well as the sheath is measured with the help of micrometer gauge or a vernier caliper. The measurement must be taken perpendicular to the axis of the core or cable.

The measurements should be taken at different 3 points of equal interval along the length of the specimen. These intervals may be about 75 mm in the case of 300 mm long piece of specimen. Each measurement is taken for the diameter of inside and outside of the insulation or sheath. At each point two measurements shall be made for better accuracy. Hence total 6 measurements of the diameter of below as well as above of insulation/sheath are taken. Taking an average of 6 measured outer diameters; we get the average measured outer diameter of the insulation / sheath. Similarly, by taking an average of 6 measured inner diameters, we get the average measured inner diameter of the insulation / sheath. Difference of average outer and inner diameter divided by two is nothing but the average radial thickness of the insulation/sheath.

sheath thickness test
Where the visual examination of the specimen reveals eccentricity, the optical method shall be used by taking slice section the specimen.
In the case of sliced section the specimen is placed under a measuring microscope along the optical axis. For circular specimen 6 such measurements are taken along the periphery at a regular interval. For noncircular conductor, such measurement is done radially at each point where the thickness of insulation appears minimum. The numbers of slices are taken from a specimen at regular interval along its length in such a manner that the total of such measurement would be not less than 18. For example, in case of circular conductor, at least 3 slices are taken from a specimen and 6 measurements in each slice to be carried out. In case of noncircular conductor, the number of slices taken from a specimen depends upon the number of points of minimum thickness of insulation. As in this case measurement is only made at the minimum thickness points.

Calculation for Thickness of Insulation/Sheath of Cable

For Core/Cable Piece

Where, Dout is the average of six measurements taken for outer diameter of the insulation/sheath
Where, Din is the average of six measurements taken for inner diameter of the insulation/sheath.
For Slice Piece – The average of 18 optical measurements is taken as the minimum thickness of insulation/sheath.

Report
Heading – Test for Thickness of Insulation/Sheath
Cable Type –
Batch No./Lot No. –
Cable No./Drum No. –

Results:
Reference Specification ………………………………

Conclusion – Specimen meets/does not meet the requirements of specification.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Analysis of Abnormal Causes of High-Voltage Cable Grounding Circulation and Typical Cases
Analysis of Abnormal Causes of High-Voltage Cable Grounding Circulation and Typical Cases
I. Introduction to Cable Grounding Loop CurrentCables rated 110 kV and above use a single-core structure. The alternating magnetic field generated by the operating current induces a voltage on the metallic sheath. If the sheath forms a closed circuit through the earth, a grounding loop current will flow on the metallic sheath. Excessive grounding loop current (loop current exceeding 50 A, more than 20% of the load current, or a ratio of maximum-to-minimum phase current greater than 3) not only a
09/03/2025
Considerations and Recommendations for Flame-Retardant Selection of High-Voltage Cables
Considerations and Recommendations for Flame-Retardant Selection of High-Voltage Cables
1.Flame-Retardant Cable Classification StandardsThe flame-retardant standard system is divided into two main categories. The first category follows the "Classification of Burning Behavior for Electric and Optical Fiber Cables" GB 31247. Cables complying with this standard system are widely used in densely populated areas such as high-speed railways and subways. This standard imposes strict requirements on parameters such as smoke density, heat release, and total smoke production, and cables typi
09/03/2025
Repair of high-voltage cable metallic sheaths
Repair of high-voltage cable metallic sheaths
I. Functions of Metallic Sheaths and Necessity of RepairThe metallic sheath of high-voltage cables is a metal shielding structure laid outside the insulation layer, including types such as lead sheaths, aluminum sheaths, and steel wire armor. Its core functions include mechanical protection (resisting external impact and compression), electrochemical corrosion protection (isolating moisture and soil pollutants), electromagnetic shielding (reducing electromagnetic interference to the environment)
09/03/2025
What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!