Di çavdaristanê elektrîkî de pîvanên ku hewce ye ku we bi an re earthing bikin bixebit:
Nokta nötr ya dawerên gera an
Bingeha metallî yên hemû cihazên barbardê barkirina
Frameworka hemû cihazên bardbard barkirina
Hemû structura metallî, ji bo vê yekê ku taybet ne di cihazên bardbard barkirina de
Hemû pîvanên ku hewce ye ku we bi an re earthing bikin bi grida earthing ê bi rodên mild steel ê bi dayîna korozîya piştgiriyê hatine girêdayî kirin. Rodên girêdayîser û min 600 mm derbarê dibeş û ser zemin hatine kirdin. Eger ê rodên bi şopandin horîzontal bikevane birikê cable trench, road, underground pipework, an rail track, rodan divê barêran jî bi 300 mm derbarê dibêj barêrê.
Her îmanê ku MS rods bikar in di navbera zemin de bi kar in, normala ms flats bikar in di ser zemin de. We connection between different earthing points and earning grid as the riser dîtin. Normala ms flats bikar in di parrucê risers ser zemin de. Rod portion of the risers below the ground level is identical to the rod conductors use for creating the main earth grid.
Hemû structura fero bi grida earthing ê bi du riser hatine girêdayî kirin. Di vê caseyê de, riser yek ji roda earthing grid în x direction û yek ji y direction hatine girtin.
Hemû pîvanên earthing ya cihazên din bi serê fashion ê hatine girêdayî kirin.
Hemû isolator mechanism boxes bi auxiliary earth mat individual hatine girêdayî kirin û her auxiliary earth mat bi main earth grid.
Her auxiliary earth mat just 300 mm derbarê zemin hatine kirdin.
Hemû raisers flats bi earthing pads of the equipment by nut bolts hatine girêdayî kirin û bolted connections by anticorrosive paints divê nekirin. This point of earthing can not be welded to facilitate equipment replacement as when required.
The leads come as riser from the earth mat should be welded with earth grid. The flats above ground should also be welded to the rod conductors below the ground. We must paint the welded points with red lead and bitumen.
Shield wire comes down along the a leg of gantry structure. Shield wire which comes down along the a leg of gantry structure is referred as down comer. Downcomer is clamped with the leg members of the structure at every 2 meters intervals. This downcomer is connected with a earthing lead coming directly from a pipe earth electrode. Diagonally opposite leg of the same structure should directly be connected to the main earthing grid via riser.
Each bus post insulator or BPI is connected to the main earthing grid via two risers. A 50 mm × 10 mm ms flat comes down along the BPI support structure from each of the two earthing points of BPI metallic base. These ms flats from base of the BPI are connected to the risers come from x and y conductor of main earthing grid.

One 50 mm × 10 mm ms flat comes down along the a leg of current transformer support structure from metallic base of the CT. This is connected to the main earthing grid via riser. Diagonally opposite vertical leg members of the structure is connected to the main earthing grid via another riser. If first riser comes from x conductor of the ground grid then second riser must come from the rod conductor of y direction.
The CT junction box should also be connected to the main earthing grid from two points by means of 50 mm × 10 mm ms flats.
Supporting structure of each pole of a circuit breaker along with the metallic base of the poles are connected to the main earthing grid via two risers one preferably from x and other from y direction. The structure of the poles are connected together with 50 mm × 8 mm ms flat. The mechanism box of each pole is also connected to the main earthing grid via 50 mm × 10 mm ms flat.
The base of each pole of the isolator should be connected together with the help of one 50 mm × 10 mm ms flat. This ms flat will be connected to the main earthing grid via two risers one preferably from x and other from y direction earth mat conductors. The mechanism box of the isolator should be connected to the auxiliary earth mat and the auxiliary earth mat then connected to the main earthing grid to two different points on the main earthing grid.
The base of the lightning arrestors must be connected to the main earthing grid via one riser and structure of the lightning arrestors must be connected to the main earthing grid via another riser. One extra earthing connection is provided in lightning arrestors which connects a treated earth pit via surge counter of the arrestors. This earth pit may be with test link.
The base of the CVT or capacitive voltage transformer is connected to the main earthing grid via a riser. The special earthing point on the base of the CVT is connected to the pipe earth electrode with 50 mm × 8 mm ms flat. The bottom portion of the support structure is also connected to the main earthing grid via riser. Two opposite earthing points of the CVT junction box should also be connected to the main earthing grid.
The supporting structure of a cable sealing system should be connected to the main earthing grid via two risers. The earthing strip of size 50 mm × 10 mm ms flat must come down from the top of the supporting structure.
There are two protected leads provided on two opposite sides of the bay marshalling kiosk. These two points must be connected to the main earthing grid via two risers. These links are provided on the lower portion of the marshalling kiosk or box.
The base of the earthing transformer must be connected to the main earthing grid via two risers. The neutral point of the earthing transformer must be connected to the pipe earth electrode with a test link. The neutral to ground connection should go through a neutral current transformer for earth fault protection purpose.