Shunt Reactor Function, Calculation, and Compensation

Electrical4u
Field: Basic Electrical
0
China

What Is A Shunt Reactor

What is Shunt Reactor

A shunt reactor is a piece of electrical equipment used in high voltage power transmission systems to stabilize the voltage during load variations. A traditional shunt reactor has a fixed rating and is either connected to the transmission line all the time or switched in and out depending on the load.

A three phase shunt reactor is generally connected to 400KV or above electrical bus system for capacitive reactive power compensation of the power system and to control dynamic over voltage occurring in the system due to load rejection.

The shunt reactor should be capable of withstanding maximum continuous operating voltage (5% higher the rated voltage in case of 400 KV system) under normal power frequency variation without exceeding the top spot temperature of 150oC at any part of the shunt reactor.

The shunt reactor should be of gapped core type or magnetically shielded air core type. Both of these designs help to maintain the impedance of the reactor fixed. The impedance should be maintained at a constant value for avoiding harmonic current generated due to the system over voltage.
shunt reactor
The shunt reactor has mainly core losses during its normal operating condition. So, care should be taken for minimizing the core losses during design.

Measurement of Losses in Shunt Reactor

We should measure the losses of a shunt reactor at rated voltage and frequency. But for very high voltage shunt reactor, it may be difficult to arrange such a high test voltage during measurement of losses. This difficulty can be overcome, by measuring the losses of the shunt reactor at any voltage lower than the system voltage of the reactor. Then this measured loss is multiplied by the square of the ratio of rated current to the current of the reactor at applied reduced test voltage to obtain the loss at rated voltage.


As the power factor of the shunt reactor is very low, loss measurement of shunt reactor by conventional wattmeter is not very reliable, instead of bridge method of measurement may be adopted for better accuracy.
This test can not segregate the losses in various parts of the reactor. To avoid, correction of test result for a reference temperature, it is preferable to take the measurement when the average temperature of the winding becomes equal to the reference temperature.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
Ensuring Reliability: A Deep Dive into Transformer Maintenance
IntroductionElectric transformers are the backbone of modern power distribution systems, silently enabling the reliable delivery of electricity to homes, businesses, and industries. As these critical assets age and the demand for uninterrupted power grows, the importance of diligent transformer maintenance has never been greater. This essay explores the essential role of transformer maintenance, highlighting the value of proactive care, the impact of advanced diagnostic technologies, and the tra
Vziman
09/03/2025
How does a transformer work?
Transformer Operation PrincipleA transformer is an electrical device that operates on the principle of electromagnetic induction to transfer electrical energy from one circuit to another. It enables the adjustment of voltage levels within an alternating current (AC) system, either stepping up (increasing) or stepping down (decreasing) voltage while maintaining the same frequency.Working Principle:Basic ComponentsA transformer consists of two coils, known as windings—the "primary winding" connect
Rockwell
09/03/2025
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
Edwiin
08/30/2025
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025