Prevention of incorrect opening/closing of circuit breakers:

  • Mechanical interlock: The operating handle must be inserted into a specific position and operated in sequence, directly restricting incorrect opening/closing.

  • Electrical interlock: The closing circuit of the circuit breaker is connected in series with the auxiliary contact of the disconnector. Closing is prohibited if the disconnector is not fully closed.

Prevention of load-breaking operation of disconnectors:

  • Mechanical interlock: The operating mechanisms of the circuit breaker and disconnector are locked by a mechanical linkage. The disconnector cannot be operated when the circuit breaker is closed.

  • Electrical interlock: The operating circuit of the disconnector is connected in series with the normally closed auxiliary contact of the circuit breaker. The circuit is disconnected when the circuit breaker is closed, prohibiting disconnector operation.

Prevention of grounding switch closing (or grounding wire installation) on live circuits:

  • Mechanical interlock: The operating mechanism of the grounding switch is mechanically interlocked with the cable chamber door. The door cannot be opened to install grounding wires when the cable chamber is live.

  • Electrical interlock: The closing circuit of the grounding switch is connected in series with the contact of the live-line indicator. Closing is prohibited when the circuit is live, as the circuit is disconnected.

Prevention of circuit breaker closing with grounding switch engaged (or grounding wire installed):

  • Mechanical interlock: The operating mechanisms of the grounding switch and circuit breaker are mechanically interlocked. The circuit breaker cannot be closed when the grounding switch is engaged.

  • Electrical interlock: The closing circuit of the circuit breaker is connected in series with the normally closed auxiliary contact of the grounding switch. Closing is prohibited when the grounding switch is engaged, as the circuit is disconnected.

Prevention of unauthorized access to live compartments:

  • Mechanical interlock: The switchgear door is interlocked with the operating mechanisms of the disconnector and grounding switch. The door cannot be opened when the compartment is live.

  • Electrical interlock: The electromagnetic lock circuit of the door is connected in series with the live-line indicator contact. The electromagnetic lock is energized to lock the door when the compartment is live.

Give a tip and encourage the author!

Recommended

Main Transformer Accidents and Light Gas Operation Issues
1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
02/05/2026
Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.