Why Is Transformer Core Single-Point Grounding Required and Multiple Grounding Prohibited?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

During transformer operation, the core and the metallic structures and components that secure the core and windings are exposed to a strong electric field, inducing a high potential relative to ground. If the core is left ungrounded, a potential difference can develop between the core and grounded parts such as clamps and the tank, leading to intermittent discharges. Additionally, the magnetic field surrounding the windings induces varying electromotive forces (EMF) in different metallic components due to their varying distances from the windings. Even small potential differences can result in continuous partial discharges across minor insulation gaps—discharges that are not only unacceptable but also difficult to detect and locate.

The effective solution is to reliably ground the core and all associated metallic structures, ensuring they are at the same electrical potential as the tank. However, this grounding must be implemented at a single point only. Core laminations are insulated from each other to suppress large eddy currents, which would otherwise cause excessive heating. Therefore, multiple grounding points are strictly prohibited, as they can create closed loops that allow circulating currents, leading to severe core overheating.

Why Multiple Grounding Points Are Prohibited:

If the core is grounded at more than one point, a closed conductive loop may form between the grounding points. When the main magnetic flux passes through this loop, it induces circulating currents, resulting in localized overheating and potentially serious damage. This may manifest as localized core burning or short circuits between laminations, increasing core losses and degrading transformer performance. In severe cases, such faults can lead to complete transformer failure, requiring extensive repair or core replacement.

Transformer ..jpg

Risks of Multiple Grounding:

In the presence of a strong electric field, ungrounded or improperly grounded core and metal parts can develop induced voltages, causing discharges to ground. Single-point grounding prevents the formation of circulating (or "ring") currents that would otherwise flow if multiple grounding points existed. These circulating currents cause localized overheating, degrade insulation, and damage metallic components, posing a significant risk to transformer reliability and safe operation.

Therefore, single-point grounding of the transformer core is essential for safe, stable, and efficient operation.

Give a tip and encourage the author!
Recommended
What Are Combined Transformer Standards? Key Specs & Tests
What Are Combined Transformer Standards? Key Specs & Tests
Combined Instrument Transformers: Technical Requirements and Testing Standards Explained with DataA combined instrument transformer integrates a voltage transformer (VT) and a current transformer (CT) into a single unit. Its design and performance are governed by comprehensive standards covering technical specifications, testing procedures, and operational reliability.1. Technical RequirementsRated Voltage:The primary rated voltages include 3kV, 6kV, 10kV, and 35kV, among others. The secondary v
Edwiin
10/23/2025
What Are the Types of Reactors? Key Roles in Power Systems
What Are the Types of Reactors? Key Roles in Power Systems
Reactor (Inductor): Definition and TypesA reactor, also known as an inductor, generates a magnetic field within the surrounding space when current flows through a conductor. Therefore, any current-carrying conductor inherently possesses inductance. However, the inductance of a straight conductor is small and produces a weak magnetic field. Practical reactors are constructed by winding the conductor into a solenoid shape, known as an air-core reactor. To further increase inductance, a ferromagnet
James
10/23/2025
35kV Distribution Line Single-Phase Ground Fault Handling
35kV Distribution Line Single-Phase Ground Fault Handling
Distribution Lines: A Key Component of Power SystemsDistribution lines are a major component of power systems. On the same voltage-level busbar, multiple distribution lines (for input or output) are connected, each with numerous branches arranged radially and linked to distribution transformers. After being stepped down to low voltage by these transformers, electricity is supplied to a wide range of end users. In such distribution networks, faults such as phase-to-phase short circuits, overcurre
Encyclopedia
10/23/2025
Why Upgrade to Maintenance-Free Transformer Breathers?
Why Upgrade to Maintenance-Free Transformer Breathers?
Maintenance-Free Moisture Absorption Technology for Oil-Immersed TransformersIn traditional oil-filled transformers, the temperature control system causes thermal expansion and contraction of insulating oil, requiring the sealing gel chamber to absorb significant moisture from the air above the oil surface. The frequency of manual silica gel replacement during patrols directly impacts equipment safety—delayed replacement can easily lead to oil degradation. Maintenance-free moisture absorbers rev
Felix Spark
10/23/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.