Measurement of Three Phase Power

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is The Measurement Of Three Phase Power

Various methods are used for measurement of three phase power in three phase circuits on the basis of number of wattmeters used. We have three methods to discuss:

  1. Three wattmeters method

  2. Two wattmeters method

  3. Single wattmeter method.

Let us discuss one by one each method in detail.

Measurement of Three Phase Power by Three Wattmeters Method

The circuit diagram is shown below-
three wattmeter method power measurement

Here, it is applied to three phase four wire systems, current coil of all the three wattmeters marked as 1, 2 and 3 are connected to respective phases marked as 1, 2 and 3. Pressure coils of all the three wattmeters are connected to a common point at neutral line. Clearly each wattmeter will give reading as product of phase current and line voltage which is phase power. The resultant sum of all the readings of wattmeter will give the total power of the circuit. Mathematically we can write

Measurement of Three Phase Power by Two Wattmeters Method

In this method we have two types of connections

  1. Star connection of loads

  2. Delta connection of loads.

When the load is star connected load, the diagram is shown in below-
two wattmeter method of three phase power measurement
For star connected load clearly the reading of wattmeter one is product of phase current and voltage difference (V2-V3). Similarly the reading of wattmeter two is the product of phase current and the voltage difference (V2-V3). Thus the total power of the circuit is sum of the reading of both the wattmeters. Mathematically we can write

but we have, hence putting the value of.

We get total power as.
When delta connected load, the diagram is shown in below
two wattmeter method delta connected load
The reading of wattmeter one can be written as

and reading of wattmeter two is


but, hence expression for total power will reduce to.

Measurement of Three Phase Power by One Wattmeter Method

Limitation of this method is that it cannot be applied on unbalanced load. So under this condition we have.
Diagram is shown below:
one wattmeter method
Two switches are given which are marked as 1-3 and 1-2, by closing the switch 1-3 we get reading of wattmeter as

Similarly the reading of wattmeter when switch 1-2 is closed is

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s
Edwiin
10/24/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.