• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What is the function of the busbar in a switchgear, and how to select an appropriate busbar?

ABB
Field: Manufacturing
China

The role of busbars in switchgear:

Busbars are conductors in switchgear that collect, distribute, and transmit electrical energy. They connect the power source (such as the output terminal of a transformer) to various branches (such as the incoming terminals of circuit breakers), acting as a transfer station for electrical energy. This enables electrical energy to be distributed to different electrical equipment or circuits as required.

Methods for selecting appropriate busbars:

Current - carrying capacity

Select busbars according to the rated current of the switchgear to ensure that the busbars will not be damaged by overheating when operating at the rated current. Generally, refer to the busbar current - carrying capacity table and make corrections considering factors such as ambient temperature and installation method. For example, in a high - temperature environment, the current - carrying capacity of the busbar will decrease, and a larger - sized busbar needs to be selected.

Material

Common busbar materials include copper and aluminum. Copper busbars have good electrical conductivity, high mechanical strength, and corrosion resistance, but they are relatively costly. Aluminum busbars are less expensive, but their electrical conductivity and mechanical strength are relatively weaker. For occasions with high reliability requirements and limited space, copper busbars are mostly selected. In some cost - sensitive situations where space allows, aluminum busbars can be chosen.

Shape and size

Busbars come in shapes such as rectangular and circular. Rectangular busbars have good heat dissipation, small skin effect, and are easy to install and connect. Circular busbars have high mechanical strength. Select appropriate shapes and sizes according to the current magnitude and installation space. In high - current situations, multiple rectangular busbars may need to be used in parallel.

 

There are bare busbars and insulated busbars. Bare busbars are less costly but need to be used when there is sufficient safety distance. Insulated busbars have high safety and can reduce the risk of inter - phase short - circuits. They are suitable for switchgear with compact space and high safety requirements.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.