Vita servitii expectata 30–40 annos, accessus ab fronte, design compactum aequivalent SF6-GIS, sine manipulatione gas SF6 – amica climati, 100% insulatio aeris sicci. Commutator Nu1 est metallice inclusus, insulatus gas, cum design commutatoris extractibilis, et fuit testatus secundum standards pertinentes, approbatus ab laboratorio STL internationaliter recognitum.
Normae Compliance
Commutatoria: IEC 62271-1 Commutatoria et controllo alta tensio – Pars 1: Specificationes communes pro commutatoriis et controllo alternantis currentis
IEC 62271-200 Commutatoria et controllo alta tensio – Pars 200: Commutatoria metallice inclusa AC et controllo pro tensiis nominatis supra 1 kV et usque ad et includens 52 kV
Commutator: IEC 62271-100 Commutatoria et controllo alta tensio – Pars 100: Commutatores alternantis currentis
Disconnector / Territor: IEC 62271-102 Commutatoria et controllo alta tensio – Pars 102: Disconnectores et territores alternantis currentis
Transformator Currentis (CT): IEC 61869-2 Transformatores instrumentales – Pars 2: Transformatores currentis
Transformator Tensionis (VT): IEC 61869-3 Transformatores instrumentales – Pars 3: Transformatores tensionis
Insulatio: IEC 60071 Coordinatio insulationis
Codex IP: IEC 60529 Gradus protectionis praebiti a casibus (codex IP)
Codex IK: IEC 62262 Gradus protectionis praebiti a casibus contra impactus mechanicis externos (codex IK)
Systema Detectionis Tensionis (VDS): IEC 62271-213 Systemata detectionis tensionis pro commutatoriis et controllo alta tensio
Operatio: EN 50110 Operatio installationum electricarum
Installatio: IEC 61936-1 Installationes potentiales excedentes 1 kV AC
Conditiones Ambientales: IEC 60721-3-3 Classificatio conditionum ambientalium

Rationes Electricae
Tensio Nominata (Ur): 24 / 36 kV
Tensio Testi Frequentiae Potentiae / Impulsus (Ud/Up): 50/125 / 70/170 kV
Frequens Nominata (fr): 50/60 Hz
Currentus Nominatus Busbar (Ir): 2500 A
Currentus Nominatus Feeder: 1250 / 2000 A
Currentus Nominatus Cuspis Sustinendus (Ip): 78.8 / 81.9 kA
Currentus Nominatus Brevi Temporis (Ik): 31.5 kA / 3 s
Protectio Arcus Interni (AFLR): 31.5 kA / 1 s
Temperatura Operationis: -5 °C ad +40 °C
Dimensiones
Largitudo: 650 mm (1250 A), 900 mm (2000 A)
Altitudo: 2400 mm
Profunditas: 1500 mm
Medium Insulationis Aeris Sicci
Pressio Impleti ad 20°C (relativa): 200 kPa
Minima Pressio Operationis ad 20°C (relativa): 180 kPa
Ratio Fugae Gas: < 0.1 %/annum
Pressio Operationis Disci Relievi: ≥ 350 kPa (manometrum)
Serie Nominata Operationis: O – 0.3 s – CO – 15 s – CO

Secundum IEC 62271:
Classis Durabilitatis Commutatoris (secundum IEC 62271-100): M2, E2, C2
Classis Durabilitatis Disconnectoris (secundum IEC 62271-102): M0, E0
Tank inoxius sigillatus pro commutatoriis inclusis.
Medium insulationis aeris sicci eliminat necessitatem manipulationis gas SF6.
Magnitudo compacta aequivalens commutatoriis insulatis SF6.
Systema coni externi pro connectendo cables potentiis et busbars solid-insulatis
Non opus est operari gas pro installatione, commissioning, vel futuris modificationibus.
Systema ductuum relevari pressionis integratum.
Equipatus sensoribus pro monitoringu real-time status operationis commutatoriis.
Characteristica Usuaria:
Design compactus
Panel controlis accessibilis
Nullus SF6 – operatio secura et amica climati
Accessus ab fronte ad commutatoria
Accessibilitas:
Compartimentum cable, transformatores currentis (CTs), et transformatores tensionis (VTs) accessibilia ab fronte commutatoriis.
Facile grounding cables per commutator vacui assecurat operationem securam.
VTs metallici, shielding, et cables et busbars tactu securi augent securitatem.
Medium Insulationis:
Commutatoria impletur gas insulationis aeris sicci.
Characteristica aeris sicci:
Non-toxicus
Nulli F-gases involvuntur
Neutrale climatico
Non-flammabilis
Chemice neutrale
Design Panelis:
Assemblatus in fabrica et testatus typice.
Busbars unipolares, solid-insulati, shielded, plug-in.
Exemptus maintenance.
Commutator vacui.
Disconnector tricipitis pro disconnectione et grounding per commutator.
Grounding protectivus per commutator vacui.
Connectio cable per systema coni externi secundum DIN EN 50 181.
Transformatores instrumentales possunt substitui sine manipulatione gas.
Gradus protectionis:
IP65 pro omnibus partibus alta tensio circuiti principis.
IP3X pro casu commutatoriis.
Design Modularis:
Transformatores currentis et tensionis montantur externi pro facile maintenance.
Transformatores tensionis sunt metallici, plug-in, et disconnectabiles.
Substitutio panelis non requirit additionalis operatio gas vel movimentum panelium adjacentium.
Systemata protectionis et mensurae possunt integrari.
Compartimentum bassa tensio removibile; busbars et transformatores instrumentales sunt plug-in.
Optional: Relais multifunctionale digitale cum functionibus integrationis protectionis, control, communicationis, operationis, et monitoringis.
Independencia Ambientalis:
Nu1 constat commutatoriis inclusis in tank sigillatus intra casum externum. Hoc protegit componentes alta tensio ab influentiis ambientalibus sicut:
Conditiones ambientales asperae
Parametri externi includentes:
Sal, pulvis
Humiditas, corrosio
Insecta, rodentia
Altitudines installationis altae
Design Exemptus Maintenance:
Commutatoria Nuventura inclusa in tank sigillatus, insulatus aeris sicci, praebet operationem exemptam maintenance super vita servitii, assecurans:
Securitas personale
Supply potentiae fidelis et interrupta
Systema pressionis sigillatum designatum pro 30 annos
Exemptus maintenance sub conditionibus ambientalibus
Reductio costorum operationis
Automation et Digitalizatio:
Systemata automationis et relays assecurant operationem tempestivam et conditionalem equipmenti, permittentes:
Automation unidirectionalis et integrationem in systemata centralia Supervisory Control and Data Acquisition (SCADA).
Operationem equipmenti efficientem et cost-effective basatam in functionibus logicis, offerens solutiones flexibiles et integratas.
Integration Sensorum (Optionalis):
Systemata sensorum integrantur intra commutatoria, permittentes:
Monitoringus health real-time
Monitoringus continuus temperature gas, partial discharge, qualitas, et densitas
Economia in costibus maintenance programmati
Identificatio praeveniens potentialium defectuum ante evenirent