• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Neutral sa Klima na 24kV Switchgear para sa Sustenableng Grids | Nu1

Edwiin
Larangan: Pansakto ng kuryente
China

Inaasahang habang buhay ng serbisyo na 30-40 taon, may front access, kompak na disenyo na katumbas ng SF6-GIS, walang handling ng gas ng SF6 – climate-friendly, 100% dry air insulation. Ang Nu1 switchgear ay metal-enclosed, gas-insulated, na may disenyo ng withdrawable circuit breaker, at ito ay type-tested batay sa mga relevant na pamantayan, na aprubado ng internationally recognized STL laboratory.

Pagsunod sa Mga Pamantayan

  • Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for alternating current switchgear and controlgear

  • IEC 62271-200 High-voltage switchgear and controlgear – Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV

  • Circuit Breaker: IEC 62271-100 High-voltage switchgear and controlgear – Part 100: Alternating current circuit breakers

  • Disconnector / Earthing Switch: IEC 62271-102 High-voltage switchgear and controlgear – Part 102: Alternating current disconnectors and earthing switches

  • Current Transformer (CT): IEC 61869-2 Instrument transformers – Part 2: Current transformers

  • Voltage Transformer (VT): IEC 61869-3 Instrument transformers – Part 3: Voltage transformers

  • Insulation: IEC 60071 Insulation coordination

  • IP Code: IEC 60529 Degrees of protection provided by enclosures (IP code)

  • IK Code: IEC 62262 Degrees of protection provided by enclosures against external mechanical impacts (IK code)

  • Voltage Detection System (VDS): IEC 62271-213 Voltage detecting systems for high-voltage switchgear and controlgear

  • Operation: EN 50110 Operation of electrical installations

  • Installation: IEC 61936-1 Power installations exceeding 1 kV AC

  • Environmental Conditions: IEC 60721-3-3 Classification of environmental conditions

NU1..jpg

Mga Electrical Ratings

  • Rated Voltage (Ur): 24 / 36 kV

  • Power Frequency / Impulse Test Voltage (Ud/Up): 50/125 / 70/170 kV

  • Rated Frequency (fr): 50/60 Hz

  • Rated Busbar Current (Ir): 2500 A

  • Rated Feeder Current: 1250 / 2000 A

  • Rated Peak Withstand Current (Ip): 78.8 / 81.9 kA

  • Rated Short-Time Current (Ik): 31.5 kA / 3 s

  • Internal Arc Protection (AFLR): 31.5 kA / 1 s

  • Operating Temperature: -5 °C to +40 °C

Sukat

  • Width: 650 mm (1250 A), 900 mm (2000 A)

  • Height: 2400 mm

  • Depth: 1500 mm

Dry Air Insulation Medium

Filling Pressure at 20°C (relative): 200 kPa

Minimum Operating Pressure at 20°C (relative): 180 kPa

Gas Leakage Rate: < 0.1 %/year

Pressure Relief Disc Operating Pressure: ≥ 350 kPa (gauge)

Rated Operating Sequence: O – 0.3 s – CO – 15 s – CO

NU1..jpg

Batay sa IEC 62271:

  • Circuit Breaker Durability Class (per IEC 62271-100): M2, E2, C2

  • Disconnector Durability Class (per IEC 62271-102): M0, E0

  • Sealed stainless-steel tank for enclosed switchgear.

  • Dry air insulation medium eliminates the need for SF6 gas handling.

  • Compact size equivalent to SF6-insulated switchgear.

  • External cone plug-in system for connecting power cables and solid-insulated busbars

  • No gas work required for installation, commissioning, or future modifications.

  • Integrated pressure relief duct system.

  • Equipped with sensors for real-time monitoring of switchgear operational status.

User-Friendly Features:

  • Compact design

  • Accessible control panel

  • No SF6 – safe and climate-friendly operation

  • Front access to switchgear

Accessibility:

  • Cable compartment, current transformers (CTs), and voltage transformers (VTs) accessible from the front of the switchgear.

  • Easy cable grounding via vacuum circuit breaker ensures safe operation.

  • Metal-coated VTs, shielding, and touch-safe cables and busbars enhance safety.

Insulation Medium:

Switchgear filled with dry air insulation gas.

Characteristics of dry air:

  • Non-toxic

  • No F-gases involved

  • Climate neutral

  • Non-flammable

  • Chemically neutral

Panel Design:

  • Factory-assembled and type-tested.

  • Single-pole, solid-insulated, shielded, plug-in busbars.

  • Maintenance-free.

  • Vacuum circuit breaker.

  • Three-position disconnector for disconnection and grounding via circuit breaker.

  • Protective grounding via vacuum circuit breaker.

  • Cable connection via external cone plug-in system according to DIN EN 50 181.

  • Instrument transformers can be replaced without gas handling.

Degree of protection:

  • IP65 for all high-voltage parts of the main circuit.

  • IP3X for the switchgear enclosure.

Modular Design:

  • Current and voltage transformers mounted externally for easy maintenance.

  • Voltage transformers are metal-coated, plug-in, and disconnectable.

  • Panel replacement requires no additional gas work or movement of adjacent panels.

  • Protection and measurement systems can be integrated.

  • Low-voltage compartment is removable; busbars and instrument transformers are plug-in

  • Optional: Digital multifunction protection relay with integrated protection, control, communication, operation, and monitoring functions.

Environmental Independence:
The Nu1 consists of switchgear enclosed in a sealed tank inside an outer enclosure. This protects high-voltage components from environmental influences such as:

Harsh environmental conditions

External parameters including:

  • Salt, dust

  • Humidity, corrosion

  • Insects, rodents

  • High installation altitudes

Maintenance-Free Design:

Nuventura switchgear is enclosed in a sealed, dry-air-insulated tank, providing maintenance-free operation over its service life, ensuring:

  • Safety of personnel

  • Reliable and uninterrupted power supply

  • Sealed pressure system designed for 30 years

  • Maintenance-free under environmental conditions

  • Reduced operational costs

Automation and Digitization:

Automation systems and relays ensure timely and conditional operation of the equipment, enabling:

  • Unidirectional automation and integration into central Supervisory Control and Data Acquisition (SCADA) systems.

  • Cost-effective and efficient equipment operation based on logic functions, offering flexible and integrated solutions.

Sensor Integration (Optional):

Sensor systems are integrated within the switchgear, enabling:

  • Real-time health monitoring

  • Continuous monitoring of gas temperature, partial discharge, quality, and density

  • Savings on scheduled maintenance costs

  • Early identification of potential failures before they occur

Magbigay ng tip at hikayatin ang may-akda!
Inirerekomenda
Inquiry
I-download
Kumuha ng IEE-Business Application
Gamit ang app na IEE-Business upang makahanap ng kagamitan makuha ang mga solusyon makipag-ugnayan sa mga eksperto at sumama sa industriyal na pakikipagtulungan kahit kailan at saanman buong pagsuporta sa pag-unlad ng iyong mga proyekto at negosyo sa enerhiya