High-Voltage SF₆-Free Ring Main Unit: Adjustment of Mechanical Characteristics

James
Field: Electrical Operations
China

(1) The contact gap is primarily determined by insulation coordination parameters, interruption parameters, contact material of the high-voltage SF₆-free ring main unit, and the design of the magnetic blowout chamber. In practical application, a larger contact gap is not necessarily better; instead, the contact gap should be adjusted as close as possible to its lower limit to reduce operating energy consumption and extend service life.

(2) The determination of contact overtravel is related to factors such as contact material properties, making/breaking current, electrical life parameters, contact pressure, and dynamic and thermal stability parameters. In actual applications, the contact overtravel should not be set too large; it is generally 15% to 40% of the contact gap, typically around 2 mm.

(3) The determination of contact pressure is associated with the contact structure, material properties, contact condition, making/breaking current, electrical life parameters, dynamic and thermal stability parameters, and mechanical performance requirements.

To ensure that the contacts of the high-voltage SF₆-free ring main unit do not separate or undergo arcing/welding under the influence of electrodynamic repulsive forces between contacts, the contact pressure must be adjusted to exceed the electrodynamic repulsive force between the contacts, as well as any additional repulsive forces generated by other parts of the electrical circuit.

(4) Closing and opening speeds are fundamental factors affecting the interrupting/making capability and service life of high-voltage vacuum contactors, making their selection particularly critical. Provided that the technical performance requirements of the high-voltage vacuum contactor are satisfied, the closing and opening speeds should be adjusted as low as reasonably possible, which is undoubtedly beneficial for improving the contactor’s service life (especially mechanical life) and reducing power consumption.

Give a tip and encourage the author!

Recommended

Comparative Analysis of High-Voltage Load Switch Technologies
A load switch is a type of switching device positioned between circuit breakers and disconnectors. It features a simple arc extinguishing device capable of interrupting rated load current and certain overload currents, but cannot interrupt short-circuit currents. Load switches can be classified into high-voltage and low-voltage types according to their operating voltage.Solid gas-producing high-voltage load switch: This type utilizes the energy from the breaking arc itself to cause gas-producing
12/15/2025
Analysis of Faults and Solutions for 17.5kV Ring Main Units in Distribution Networks
With the improvement of social productivity and people's quality of life, the demand for electricity is continuously increasing. To ensure the effectiveness of power grid system configuration, it is necessary to reasonably construct distribution networks based on actual conditions. However, during the operation of distribution network systems, 17.5kV ring main units play a very important role, so the impact caused by failures is extremely significant. At this point, it is essential to adopt reas
12/11/2025
How to install a DTU on an N2 Insulation ring main unit?
DTU (Distribution Terminal Unit), a substation terminal in distribution automation systems, is secondary equipment installed in switching stations, distribution rooms, N2 Insulation ring main units (RMUs), and box-type substations. It bridges primary equipment and the distribution automation master station. Older N2 Insulation RMUs without DTUs cannot communicate with the master station, failing to meet automation requirements. While replacing entire RMUs with new DTU-integrated models would sol
12/11/2025
Design of a New 12kV Environmentally Friendly Gas-Insulated Ring Main Unit
1. Specific Design1.1 Design ConceptState Grid Corporation of China actively promotes grid energy conservation and low-carbon development to achieve national carbon peak (2030) and neutrality (2060) goals. Environmentally friendly gas-insulated ring main units represent this trend. A new 12kV integrated environmentally friendly gas-insulated ring main unit was designed combining vacuum interrupter technology with three-position disconnectors and vacuum circuit breakers. The design utilized Solid