• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How Altitude Affects HV Equipment Insulation & Temperature Rise?

James
Field: Electrical Operations
China

As altitude increases, air density, temperature, and atmospheric pressure decrease accordingly, leading to reduced dielectric strength of air gaps and external insulation performance of porcelain components. This results in degraded external insulation performance for high-voltage electrical equipment. Since most high-voltage equipment is designed for installation at altitudes below 1,000 meters, using such equipment at elevations exceeding 1,000 meters may compromise reliable insulation performance. Therefore, the external insulation strength of high-voltage switchgear used in high-altitude areas must be enhanced.

For high-altitude regions above 1,000 meters (up to 4,000 meters), it is generally required that for every additional 100 meters of elevation, the external insulation test voltage be increased by 1% during equipment selection and testing.

Temperature Rise.jpg

For high-voltage equipment operating at altitudes between 2,000 and 3,000 meters with voltages up to 110kV, the external insulation strength is typically enhanced by selecting equipment with one higher insulation level—this increases the impulse and power-frequency withstand voltages by approximately 30%.

For correction methods and calculations regarding external insulation at high altitudes, refer to IEC 62271-1, GB 11022, and Q/GDW 13001-2014 Technical Specification for External Insulation Configuration in High-Altitude Areas.

In addition to the impact of altitude on external insulation, according to IEC standards, if the temperature rise test of high-voltage equipment is conducted at an altitude below 2,000 meters, the temperature rise performance must be re-evaluated when the equipment is deployed at altitudes between 2,000 and 4,000 meters. This is because thinner air reduces the effectiveness of natural convection cooling.

Under normal test conditions, the measured temperature rise must not exceed the values specified in Table 3 of IEC 62271-1. When equipment is installed at altitudes above 2,000 meters, the allowable maximum temperature limit should be reduced by 1% for every additional 100 meters of elevation. However, in practice, it is generally unnecessary to impose special temperature rise limits based solely on increasing altitude. This is because higher altitudes are associated with lower substation ambient temperatures. Even if the temperature rise is higher, the final operating temperature of the equipment remains within acceptable limits (it is the final temperature, not the temperature rise, that affects equipment performance). Different altitudes correspond to different maximum ambient air temperatures, as shown in the table below.

Table 1: Maximum Ambient Air Temperature Corresponding to Different Altitudes

Altitude / m Maximum Ambient Air Temperature / °C
0~2000 40
2000~3000 35
3000~4000 30

In addition to affecting the external insulation of the primary (high-voltage) parts of high-voltage electrical equipment, high altitude also impacts control devices. Control cabinets may contain secondary components such as motors, circuit breakers, contactors, and relays, most of which rely on air insulation. Therefore, their insulation performance also degrades at high altitudes. This factor must be considered during equipment selection.

Give a tip and encourage the author!

Recommended

Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding Electrodes
Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding ElectrodesWhen the grounding electrode of an Ultra-High-Voltage Direct Current (UHVDC) transmission system is located close to a renewable energy power station, the return current flowing through the earth can cause a rise in ground potential around the electrode area. This ground potential rise leads to a shift in the neutral-point potential of nearby power transformers, inducing DC bias (or DC offset) in their
01/15/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Distribution Equipment Transformer Testing, Inspection, and Maintenance
1.Transformer Maintenance and Inspection Open the low-voltage (LV) circuit breaker of the transformer under maintenance, remove the control power fuse, and hang a “Do Not Close” warning sign on the switch handle. Open the high-voltage (HV) circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the HV switchgear, and hang a “Do Not Close” warning sign on the switch handle. For dry-type transformer maintenance: first clean the porcel
12/25/2025
How to Test Insulation Resistance of Distribution Transformers
In practical work, insulation resistance of distribution transformers is generally measured twice: the insulation resistance between thehigh-voltage (HV) windingand thelow-voltage (LV) winding plus the transformer tank, and the insulation resistance between theLV windingand theHV winding plus the transformer tank.If both measurements yield acceptable values, it indicates that the insulation among the HV winding, LV winding, and transformer tank is qualified. If either measurement fails, pairwise
12/25/2025
Send inquiry
+86
Click to upload file

IEE Business will not sell or share your personal information.

Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.