• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How Altitude Affects HV Equipment Insulation & Temperature Rise?

James
James
Field: Electrical Operations
China

As altitude increases, air density, temperature, and atmospheric pressure decrease accordingly, leading to reduced dielectric strength of air gaps and external insulation performance of porcelain components. This results in degraded external insulation performance for high-voltage electrical equipment. Since most high-voltage equipment is designed for installation at altitudes below 1,000 meters, using such equipment at elevations exceeding 1,000 meters may compromise reliable insulation performance. Therefore, the external insulation strength of high-voltage switchgear used in high-altitude areas must be enhanced.

For high-altitude regions above 1,000 meters (up to 4,000 meters), it is generally required that for every additional 100 meters of elevation, the external insulation test voltage be increased by 1% during equipment selection and testing.

Temperature Rise.jpg

For high-voltage equipment operating at altitudes between 2,000 and 3,000 meters with voltages up to 110kV, the external insulation strength is typically enhanced by selecting equipment with one higher insulation level—this increases the impulse and power-frequency withstand voltages by approximately 30%.

For correction methods and calculations regarding external insulation at high altitudes, refer to IEC 62271-1, GB 11022, and Q/GDW 13001-2014 Technical Specification for External Insulation Configuration in High-Altitude Areas.

In addition to the impact of altitude on external insulation, according to IEC standards, if the temperature rise test of high-voltage equipment is conducted at an altitude below 2,000 meters, the temperature rise performance must be re-evaluated when the equipment is deployed at altitudes between 2,000 and 4,000 meters. This is because thinner air reduces the effectiveness of natural convection cooling.

Under normal test conditions, the measured temperature rise must not exceed the values specified in Table 3 of IEC 62271-1. When equipment is installed at altitudes above 2,000 meters, the allowable maximum temperature limit should be reduced by 1% for every additional 100 meters of elevation. However, in practice, it is generally unnecessary to impose special temperature rise limits based solely on increasing altitude. This is because higher altitudes are associated with lower substation ambient temperatures. Even if the temperature rise is higher, the final operating temperature of the equipment remains within acceptable limits (it is the final temperature, not the temperature rise, that affects equipment performance). Different altitudes correspond to different maximum ambient air temperatures, as shown in the table below.

Table 1: Maximum Ambient Air Temperature Corresponding to Different Altitudes

Altitude / m Maximum Ambient Air Temperature / °C
0~2000 40
2000~3000 35
3000~4000 30

In addition to affecting the external insulation of the primary (high-voltage) parts of high-voltage electrical equipment, high altitude also impacts control devices. Control cabinets may contain secondary components such as motors, circuit breakers, contactors, and relays, most of which rely on air insulation. Therefore, their insulation performance also degrades at high altitudes. This factor must be considered during equipment selection.

Give a tip and encourage the author!
Recommended
How Often Should Transformers Be Overhauled?
How Often Should Transformers Be Overhauled?
1. Transformer Major Overhaul Cycle The main transformer shall undergo a core-lifting inspection before being put into service, and thereafter a core-lifting overhaul shall be performed every 5 to 10 years. Core-lifting overhaul shall also be carried out if a fault occurs during operation or if issues are identified during preventive tests. Distribution transformers operating continuously under normal load conditions may be overhauled once every 10 years. For on-load tap-changing transformers, t
Felix Spark
12/09/2025
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-voltage distribution lines refer to the circuits that, through a distribution transformer, step down the high voltage of 10 kV to the 380/220 V level—i.e., the low-voltage lines running from the substation to the end-use equipment.Low-voltage distribution lines should be considered during the design phase of substation wiring configurations. In factories, for workshops with relatively high power demand, dedicated workshop substations are often installed, where transformers supply power direc
James
12/09/2025
Adjustment and Precautions for H61 Oil Power 26kV Electric Transformer Tap Changers
Adjustment and Precautions for H61 Oil Power 26kV Electric Transformer Tap Changers
Preparatory Work Before Adjusting the Tap Changer of H61 Oil Power 26kV Electric Transformer Apply for and issue a work permit; carefully fill out the operation ticket; conduct a simulation board operation test to ensure the operation is error-free; confirm the personnel who will carry out and supervise the operation; if load reduction is required, notify affected users in advance. Before construction, power must be disconnected to take the transformer out of service, and voltage testing must be
James
12/08/2025
H59/H61 Transformer Failure Analysis and Protection Measures
H59/H61 Transformer Failure Analysis and Protection Measures
1.Causes of Damage to Agricultural H59/H61 Oil-Immersed Distribution Transformers1.1 Insulation DamageRural power supply commonly uses a 380/220V mixed system. Due to the high proportion of single-phase loads, H59/H61 oil-immersed distribution transformers often operate under significant three-phase load imbalance. In many cases, the degree of three-phase load imbalance far exceeds the limits permitted by operational regulations, causing premature aging, deterioration, and eventual failure of th
Felix Spark
12/08/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.