High voltage Incoming and outgoing feeders configuration in switch yards

Edwiin
12/09/2024

The incoming and outgoing feeders of switchgear cabinets are typically equipped with circuit breakers, isolating switches, and earthing switches to ensure the safe operation of the power system. In high-voltage switch stations, each feeder is also fitted with current transformers (CTs) and potential transformers (PTs) to connect protection and measurement devices. CTs are positioned on the busbar side of the PTs to allow protection devices to detect short circuits in the PTs. For feeders without their own PTs, the PTs are installed on the busbar to ensure busbar voltage monitoring is unaffected by individual feeder faults.

Additionally, depending on the specific requirements of the switchgear cabinet, feeders may be equipped with surge protection devices to prevent damage from lightning strikes or transient overvoltages. Coupling devices for frequency carrier signals may also be installed on the feeders to transmit communication signals or control commands, enabling remote monitoring and automated operations.

The diagram shows the typical configuration of various devices in a feeder arrangement, including current transformers, potential transformers, circuit breakers, isolating switches, earthing switches, surge protection devices, and coupling devices for carrier signals. This layout ensures the reliability and safety of the feeder while providing necessary support for protection and measurement.

(a) Overhead line feeder with double busbar.

(b) transformer feeder with double busbar.

  1. Busbar disconnecting switch

2) Circuit breaker

3) Feeder disconnecting switch

4) Earthing switch

5) Current transformer

6) Voltage transformer

7) Capacitive voltage transformer with coupling for frequency carrier signal

8) Blocking reactor against frequency carrier signals

Edwiin

Online condition monitoring device (OLM2) on high voltage Circuit Breakers
Online condition monitoring device (OLM2) on high voltage Circuit Breakers
This device is capable of monitoring and detecting various parameters according to the specifications outlined:SF6 Gas Monitoring:Utilizes a specialized sensor for measuring SF6 gas density.Capabilities include measuring gas temperature, monitoring SF6 leak rates, and calculating the optimal date for refilling.Mechanical Operation Analysis:Measures operational times for closing and opening cycles.Evaluates primary contacts separation speed, damping, and contact overtravel.Identifies signs of mec
Edwiin
02/13/2025
Anti pumping function in circuit breakers operating mechanism
Anti pumping function in circuit breakers operating mechanism
The anti - pumping function stands as a crucial characteristic of control circuits. In the absence of this anti - pumping function, assume that a user connects a maintained contact within the closing circuit. When the circuit breaker is closed onto a fault current, the protective relays will promptly trigger a tripping action. However, the maintained contact in the closing circuit will attempt to close the breaker (once again) onto the fault. This repetitive and dangerous process is referred to
Edwiin
02/12/2025
Ageing phenomena of current pass blades in high voltage disconnector switch
Ageing phenomena of current pass blades in high voltage disconnector switch
This failure mode has three primary origins:Electrical Causes: The switching of currents, such as loop currents, can lead to localized wear. At higher currents, an electric arc may burn at a specific spot, increasing the local resistance. As more switching operations occur, the contact surface wears down further, causing an increase in resistance.Mechanical Causes: Vibrations, often due to wind, are the main contributors to mechanical aging. These vibrations cause abrasion over time, leading to
Edwiin
02/11/2025
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Transient Recovery Voltage (TRV) stress similar to that encountered during a short-line fault can also occur due to the busbar connections on the supply side of a circuit breaker. This specific TRV stress is known as Initial Transient Recovery Voltage (ITRV). Given the relatively short distances involved, the time to reach the first peak of ITRV is typically less than 1 microsecond. The surge impedance of the busbars within a substation is generally lower compared to that of overhead lines.The f
Edwiin