Analysis and Countermeasures of a 145kV Disconnect Switch Maloperation Incident

Felix Spark
Felix Spark
Field: Failure and maintenance
China

1. Introduction

In Indonesia's power grid, 145kV high voltage disconnect switches (HVDs) are critical for maintaining transmission reliability across its archipelagic terrain. However, maloperation incidents pose significant risks to grid stability. This article investigates a 145kV HVD maloperation in an Indonesian substation, analyzing root causes and proposing countermeasures while referencing IP66 protection standards and IEC 60068-3-3 compliance to enhance operational safety.

2. Incident Overview in Indonesia

In March 2024, a 145kV disconnect switch in a Java Island substation unexpectedly opened during a routine load transfer, triggering a cascade of protective relay activations. The incident occurred in a coastal substation near Surabaya, where the switch's IP66-rated enclosure was theoretically designed to withstand tropical conditions. The unscheduled opening disrupted power supply to 120,000 households and caused a 30MW load shed, with repair costs exceeding $800,000. Post-incident analysis revealed a combination of environmental degradation and control system flaws as primary causes.

3. Root Cause Analysis
3.1 Control System Vulnerabilities
3.1.1 Parasitic Circuit Induction

The switch's DC control circuit shared a common ground with the substation's lightning protection system, a design flaw identified in 20% of Indonesian 145kV substations (2023 PLN report). During a nearby thunderstorm, transient overvoltages induced 12V DC spikes in the control wiring, mistakenly activating the switch's opening relay. Similar to a 2022 incident in Bali, where ground loops caused 145kV HVD misoperation, this case highlighted inadequate isolation between control and protection circuits.

3.1.2 Relay Aging

The switch's electromagnetic relay, rated for 100,000 operations, had exceeded 150,000 cycles without replacement. Insulation breakdown in the relay coil, detected via post-fault autopsy, allowed arcing that bridged normally open contacts. IEC 60068-3-3 thermal cycling tests later confirmed the relay's epoxy insulation degraded at >60°C, a common temperature in Indonesia's unairconditioned switchyards.

3.2 Environmental Degradation
3.2.1 IP66 Seal Failure

Despite IP66 certification, the switch's EPDM gasket showed 3mm cracks, allowing salt mist ingress. Coastal air in East Java contains 0.05mg/m³ of chloride ions, accelerating corrosion. SEM analysis of the gasket revealed ozone cracking, a result of prolonged exposure to UV radiation (annual UV index >12) and humidity >85%. This compromised the enclosure's dust/water protection, with internal components showing 0.2mm rust deposits on copper contacts.

3.2.2 Moisture-induced Insulation Degradation

High humidity (90% RH average) caused condensation on the switch's composite insulator, reducing surface resistivity from 10¹²Ω to 10⁸Ω. Partial discharge (PD) monitoring data showed PD activity increased from 5pC to 25pC over six months, a precursor to flashover. The insulator's hydrophobic coating, compliant with IEC 60068-3-3, lost effectiveness after three years in tropical conditions, failing to repel water films.

3.3 Maintenance Deficiencies
3.3.1 Inadequate Lubrication

The switch's mechanical linkage had insufficient silicone grease (NLGI Grade 2), leading to 15% increased friction in the operating mechanism. Temperature sensors recorded 40°C hotter than baseline in the pivot joints, causing stick-slip motion that generated mechanical shocks, mimicking normal opening commands. This aligns with PLN's 2024 report showing 43% of 145kV HVD maloperations relate to neglected lubrication.

3.3.2 Delayed Sensor Calibration

The switch's contact resistance sensor, calibrated to ±10μΩ, had not been verified for 18 months. Actual accuracy had drifted to ±35μΩ, masking a 120μΩ contact degradation (critical threshold: 150μΩ). Such delays in calibration are common in remote Indonesian substations, where 37% of 145kV HVDs lack scheduled maintenance due to logistical challenges.

4. Comprehensive Countermeasures
4.1 Control System Redesign
4.1.1 Isolated Grounding Architecture

Implement a star grounding system for 145kV HVD control circuits, separating them from lightning protection grounds by 5m. Install 1000V isolation transformers on control power feeds, as demonstrated in a 2023 case study in Medan that reduced transient-induced maloperations by 92%.

4.1.2 Solid-State Relay Upgrade

Replace electromagnetic relays with IEC 60950-certified solid-state relays (SSR) rated for 10⁷ operations. SSRs in a Semarang pilot project showed zero voltage spikes and 50% faster switching times, eliminating arcing risks in humid environments.

4.2 Environmental Resilience Enhancement
4.2.1 IP66 Seal System Overhaul

  • Gasket Replacement: Use fluoroelastomer (FKM) gaskets with 200°C temperature resistance, 300% elongation, and UV stabilizers, meeting IEC 60068-3-3's tropical climate annex.

  • Drainage Modification: Add 12mm weep holes with anti-insect screens to switch enclosures, reducing water pooling. A Jakarta trial showed this reduced internal humidity from 85% to 55% within 24 hours.

4.2.2 Advanced Insulation Solutions

  • Superhydrophobic Coating: Apply aerosol - based SiO₂ coatings (contact angle >150°) to insulators, extending hydrophobicity from 3 to 7 years. Field tests in Bali reduced PD activity by 80%.

  • Dehumidifier Integration: Install Peltier - effect dehumidifiers (3L/day capacity) in enclosures, maintaining <40% RH. A Sulawesi substation saw contact resistance stability improve by 65% post - installation.

4.3 Predictive Maintenance Optimization
4.3.1 IoT - Enabled Monitoring

Deploy a 4G - enabled sensor network measuring:

  • Contact resistance (0.1&mu;&Omega; resolution)

  • Mechanism vibration (100Hz - 10kHz bandwidth)

  • Enclosure humidity/temperature (&plusmn;1% RH, &plusmn;0.5&deg;C)

Data is analyzed via a cloud - based AI platform (accuracy 94%) that predicts failures 72 hours in advance, as proven in a Papua pilot project that cut unplanned outages by 85%.

4.3.2 Regionalized Maintenance Schedules

Develop climate - based maintenance plans:

5. Technical and Economic Impact
5.1 Reliability Metrics Improvement

  • MTBF Increase: From 12,000 hours to 45,000 hours post - intervention, exceeding IEC 62271 - 102's target.

  • Fault Detection Time: Reduced from 4 hours to 15 minutes via real - time IoT monitoring.

5.2 Cost - Benefit Analysis

  • Initial Investment: $500,000 for a 10 - switch substation in Indonesia

  • 5 - Year Savings: $2.3 million from:

    • 75% reduction in maintenance labor

    • 90% decrease in equipment replacement costs

    • 88% minimization of downtime losses

6. Conclusion

The 145kV disconnect switch maloperation in Indonesia underscores the need for integrated solutions addressing control system vulnerabilities, environmental degradation, and maintenance gaps. By implementing IP66 - enhanced enclosures, IEC 60068 - 3 - 3 - compliant components, and IoT - driven predictive maintenance, Indonesia's 145kV grid can achieve reliability metrics on par with global standards. This approach not only mitigates maloperation risks but also supports the country's goal of a resilient, smart power infrastructure capable of meeting rising energy demands in tropical environments.

Give a tip and encourage the author!
Recommended
10kV RMU Common Faults & Solutions Guide
10kV RMU Common Faults & Solutions Guide
Application Issues and Handling Measures for 10kV Ring Main Units (RMUs)The 10kV ring main unit (RMU) is a common electrical distribution device in urban power distribution networks, primarily used for medium-voltage power supply and distribution. During actual operation, various issues may arise. Below are common problems and corresponding corrective measures.I. Electrical Faults Internal Short Circuit or Poor WiringA short circuit or loose connection inside the RMU can lead to abnormal operati
Echo
10/20/2025
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breakers: Classification and Fault DiagnosisHigh-voltage circuit breakers are critical protective devices in power systems. They rapidly interrupt current when a fault occurs, preventing damage to equipment from overloads or short circuits. However, due to long-term operation and other factors, circuit breakers may develop faults that require timely diagnosis and troubleshooting.I. Classification of High-Voltage Circuit Breakers1. By Installation Location: Indoor-type: Insta
Felix Spark
10/20/2025
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation! Never install the transformer too far away—avoid placing it in remote mountains or wilderness. Excessive distance not only wastes cables and increases line losses, but also makes management and maintenance difficult. Never choose transformer capacity arbitrarily. Selecting the right capacity is essential. If the capacity is too small, the transformer may be overloaded and easily damaged—overloading beyond 30% should not exceed two hours
James
10/20/2025
How to Maintain Dry-Type Transformers Safely?
How to Maintain Dry-Type Transformers Safely?
Maintenance Procedures for Dry-Type Transformers Put the standby transformer into operation, open the low-voltage side circuit breaker of the transformer to be maintained, remove the control power fuse, and hang a "DO NOT CLOSE" sign on the switch handle. Open the high-voltage side circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the high-voltage cabinet, and hang a "DO NOT CLOSE" sign on the switch handle. For dry-type trans
Felix Spark
10/20/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.