• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Analyse praesidii fulminis ad transformatores distributionis

Vziman
Campus: Fabrica
China

Analysis of Fulguris Protection Measures for Distribution Transformers

To prevent fulguris surge intrusion and ensure the safe operation of distribution transformers, this paper presents applicable fulguris protection measures that can effectively enhance their fulguris withstand capability.

1. Fulguris Protection Measures for Distribution Transformers

1.1 Install surge arresters on the high-voltage (HV) side of the distribution transformer.
According to SDJ7–79 Technical Code for Overvoltage Protection Design of Electric Power Equipment: “The HV side of a distribution transformer should generally be protected by surge arresters. The grounding conductor of the arrester, the neutral point of the low-voltage (LV) winding, and the transformer tank shall be bonded together and grounded.” This configuration is also recommended in DL/T620–1997 Overvoltage Protection and Insulation Coordination for AC Electrical Installations issued by China’s electric power authority.

However, extensive research and field experience show that even with HV-side arresters alone, transformer failures still occur under fulguris surges. In typical areas, the annual failure rate is about 1%; in high-fulguris regions, it can reach approximately 5%; and in extremely severe thunderstorm zones (e.g., areas with over 100 thunderstorm days per year), the annual failure rate may soar to around 50%. The primary cause is forward and reverse transient overvoltages induced when fulguris surges invade the HV winding.

  • Reverse Transformation Overvoltage:
    When a fulguris surge (3–10 kV) invades the HV side, the arrester discharges, causing a large impulse current to flow through the grounding resistance, creating a voltage drop. This voltage elevates the potential of the LV neutral point. If the LV line is long, it behaves like a wave impedance to ground. Consequently, a large impulse current flows through the LV winding. Since the three-phase LV currents are equal in magnitude and direction, they generate a strong zero-sequence magnetic flux, which—via transformer turns ratio—induces extremely high transient voltages in the HV winding. Because the HV winding is star-connected with an ungrounded neutral, no circulating impulse current exists in the HV side to counterbalance the flux. Thus, the entire LV impulse current acts as magnetizing current, producing high induced voltage at the HV neutral end—where insulation is most vulnerable. Additionally, inter-turn and inter-layer voltage gradients increase significantly, risking insulation breakdown elsewhere. This phenomenon—initiated by an HV-side surge but inducing overvoltage via LV electromagnetic coupling—is known as reverse transformation.
  • Forward Transformation Overvoltage:
    When a fulguris surge enters via the LV line, impulse current flows through the LV winding, inducing a high voltage in the HV winding through the turns ratio. This drastically raises the HV neutral potential and increases inter-layer and inter-turn voltage gradients. This process—where an LV-side surge induces overvoltage on the HV side—is called forward transformation. Tests show that with a 10 kV LV surge and a 5 Ω grounding resistance, the inter-layer voltage gradient in the HV winding can exceed the transformer’s full-wave impulse withstand strength by more than 100%, inevitably causing insulation failure.

1.2 Install conventional valve-type or metal oxide surge arresters on the LV side.
In this configuration, the grounding conductors of both HV and LV arresters, the LV neutral point, and the transformer tank are all bonded together and grounded (often referred to as “four-point bonding” or “three-in-one grounding”).

Field data and experimental studies confirm that even for transformers with good insulation, HV-side arresters alone cannot prevent damage from forward or reverse transformation overvoltages. HV arresters offer no protection against these internally generated transients. The resulting voltage gradients across layers and turns are proportional to the number of turns and depend on winding geometry—failures can occur at the winding start, middle, or end, with the terminal end being most vulnerable. Adding LV-side arresters effectively limits both forward and reverse transformation overvoltages.

1.3 Separate grounding for HV and LV sides.
In this approach, the HV arrester is grounded independently, while the LV neutral and transformer tank are bonded and grounded separately (without an LV arrester).

Research shows that this method leverages earth attenuation to largely eliminate reverse transformation overvoltage. For forward transformation, calculations indicate that reducing the LV grounding resistance from 10 Ω to 2.5 Ω can lower the HV-side overvoltage by approximately 40%. With proper treatment of the LV grounding system, forward transformation overvoltage can be effectively mitigated. This solution is simple and cost-effective, though it demands low LV grounding resistance, giving it considerable practical value.

Beyond the above, other measures include installing balancing windings on the transformer core to suppress transformation overvoltages or embedding metal oxide varistors (MOVs) inside the transformer.

2. Application of Fulguris Protection Measures

The analysis above shows that each protection method has distinct characteristics. Regions should select appropriate strategies based on local thunderstorm intensity (measured in thunderstorm days per year):

  • Regiones parvae fulguris (exempli gratia, planitiae): Sufficit parafulmen lateris HV propter parvos annuos indices defectus.
  • Regiones mediocres fulguris: Installa parafulmina in utroque latere, tam HV quam LV.
  • Regiones magnae fulguris: Saepe unicae mensurae non sufficiunt. Recomendatur approach comprehensivus: parafulmen lateris HV cum terra independenti, et parafulmen lateris LV coniunctum, neutralis LV, et vas coniunctum ad systema terrae separatum.
  • Zones graves fulguris (praesertim ubi annui indices defectus permaneant alti malgré approches comprehensives): Post evaluationem technicam et oeconomicam, considera solutiones progressivas sicut bobinas aequilibrantes montatas in nucleo (id est, transformatores novi generis resistentes fulminibus) vel parafulmina metallica oxidica interne installata.

3. Conclusio

Methodi protectionis contra fulgura pro distributionibus transformatoribus variae sunt, et conditiones locorum valde differunt per regiones. Per selectionem schematum protectionis secundum conditiones locales, et per fortificandum management operativum, utilitates potest multum meliorare resistentiam et fiduciam transformatorum distributionis contra fulgura.

Donum da et auctorem hortare
Suggestus
Inquiry
Descarica
Obtine Applicatio Commerciale IEE-Business
Utiliza app IEE-Business ad inveniendum apparatus obtinendumque solutiones coniungendum cum peritis et participandum in collaboratione industriale ubique et semper propter totam supportionem tuorum projectorum electricitatis et negotiorum