What is the voltage difference between two legs of a two-phase system?

Encyclopedia
10/05/2024

When discussing voltage differences in two-phase systems and between each pole and the ground in a grounded neutral system, we need to clarify some basic concepts.


Two-phase system


Two-phase systems are not common in modern power systems, but have been used at certain times in history. Two-phase systems usually come in two forms: four-wire and two-wire.


Four-wire two-phase system


In this system, the two sets of coils are 90 degrees out of phase and there are two neutral lines connected together. The voltage difference between the two phases (i.e. the voltage between the two poles) is usually the same as the voltage per phase, assuming that the voltage per phase is Vphase, then the voltage difference between the two phases is Vline=Vphase.


Two-wire two-phase system


In such a system, there is no neutral line and the voltage difference between the two phases is called Vline.


Grounded neutral system


A neutral point system is one in which the neutral line in the system is grounded, which is the most common configuration in three-phase systems, but is also applicable in two-phase systems.


The voltage difference of a grounded neutral system


In a neutral point system at a contact, the voltage between each pole and the ground depends on the configuration and load of the system. If the system is balanced and the neutral point is grounded, the voltage between each pole and the ground should be half of the Vphase, because ideally the neutral point should have a potential of 0V.


However, in practical applications, due to load imbalance or other factors, the neutral point may drift, resulting in the voltage between each pole and the ground not being completely consistent.


Illustrate by example


Suppose that in a connected neutral point system, the voltage of each phase is Vphase, then:


  • The voltage difference between the two phases (if a four-wire system) is Vline=Vphase.



  • The voltage between each pole and the ground is ideally Vphase/2.


Precautions in practical application


In practical applications, the following situations may be encountered:


  • Load imbalance: If the load is not perfectly symmetrical, the neutral points may drift, resulting in a different voltage between each pole and the ground.


  • System design: The specific design and configuration of the system also affects the voltage between each pole and the ground.


Sum up


  • Two-phase system: The voltage difference between the two phases depends on the specific configuration of the system, generally V phase or Vline.


  • Grounded neutral system: The voltage between each pole and the ground is usually V phase/2, but may vary in practice due to factors such as load imbalance.



In the specific application, it is recommended to refer to the specific design parameters of the system and the actual situation to determine the voltage difference. If there are specific system parameters, a more precise answer can be provided.


Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

How to Design and Install a Solar PV System?
How to Design and Install a Solar PV System?
Design and Installation of Solar PV SystemsModern society relies on energy for daily needs like industry, heating, transport, and agriculture, mostly met by non-renewable sources (coal, oil, gas). However, these cause environmental harm, are unevenly distributed, and face price volatility due to limited reserves—driving demand for renewable energy.Solar energy, abundant and capable of meeting global needs, stands out. Standalone PV systems (Fig 1) offer energy independence from utilities.
Edwiin
07/17/2025
Load Frequency Control (LFC) & Turbine Governor Control (TGC) in Power System
Load Frequency Control (LFC) & Turbine Governor Control (TGC) in Power System
Brief Introduction to Thermal Generating UnitsElectricity generation relies on both renewable and non - renewable energy resources. Thermal generating units represent a conventional approach to power production. In these units, fuels such as coal, nuclear energy, natural gas, biofuel, and biogas are combusted within a boiler.The boiler of a generating unit is an extremely complex system. In its simplest conception, it can be visualized as a chamber whose walls are lined with pipes, through which
Edwiin
06/06/2025
Why 3-Phase Power? Why Not 6, 12 or More for Power Transmission?
Why 3-Phase Power? Why Not 6, 12 or More for Power Transmission?
It is well-known that single-phase and three-phase systems are the most prevalent configurations for power transmission, distribution, and end-use applications. While both serve as fundamental power supply frameworks, three-phase systems offer distinct advantages over their single-phase counterparts.Notably, multi-phase systems (such as 6-phase, 12-phase, etc.) find specific applications in power electronics—particularly in rectifier circuits and variable frequency drives (VFDs)—wher
Edwiin
06/05/2025
How Many Poles and Towers are Situated Within a 1-km Span?
How Many Poles and Towers are Situated Within a 1-km Span?
The number of distribution poles and transmission towers within a 1-kilometer stretch of overhead lines varies significantly based on multiple factors, including voltage level, power line type, supporting structure, geographical location, local regulations, and specific grid requirements.In urban areas, distribution utility poles are typically positioned at closer intervals, while in rural regions, they are spaced farther apart. Additionally, the use of taller structures for higher-voltage trans
Edwiin
06/05/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!