Ultimate Guide to AC Contactor Abnormal Noise: From Electromagnetic Noise to Mechanical Vibration, Accurate Diagnosis and Handling

Felix Spark
Field: Failure and maintenance
China

In electrical control systems, AC contactors are among the commonly used electrical components, and they are also a common source of various electrical faults. After long-term use—especially in harsh environments with high levels of dust—AC contactors may sometimes emit squeaking or rattling noises after being pulled in and held. The causes of this phenomenon are analyzed as follows.

AC Contactor.jpg

Squeaking Noise After Pull-In and Holding

A fully functional AC contactor makes no noise when energized and pulled in. If a squeaking noise occurs during pull-in, the causes include: dirt on the surfaces of the moving iron core and static iron core; uneven force on the compression spring for resetting the moving iron core; or unsmooth movement path of the moving iron core.

AC Contactor.jpg

These issues result in poor contact and gaps between the surfaces of the moving iron core and static iron core, which increases the magnetic resistance of the magnetic circuit and reduces the magnetic attraction force. To counteract this, the current in the coil increases to prevent the magnetic attraction force from decreasing, and this adjustment process repeats continuously. The squeaking noise is exactly the resonance caused by the coil current noise and the vibration of the reset compression spring— the larger the gap between the moving iron core and static iron core, the louder the squeaking noise.

Consequences

a. The AC contactor coil may burn out.

b. Poor contact may occur between the main and auxiliary contacts. In particular, the main contacts bear a large load, making them prone to arc generation, which can burn the main contacts or cause uneven adhesion. Additionally, phase loss may occur, leading to phase-loss operation of the three-phase load (e.g., an electric motor) and even burning of the three-phase load. If the auxiliary contacts are used in other branches, the normal operation of those branches will be affected.

Therefore, once an AC contactor emits a squeaking noise, it should be addressed immediately.

AC Contactor.jpg

II. Rattling Noise During Pull-In

When an AC contactor pulls in, a rattling noise occurring 100 times per second is caused by an open circuit in the short-circuit ring of the contactor’s static (or moving) iron core.

Alternating current with a frequency of 50 Hz crosses zero 100 times per second. At the zero-crossing point, the magnetic force generated by the closed magnetic circuit formed by the moving and static iron cores also drops to zero. The function of the short-circuit ring (installed on the static or moving iron core) is to generate a counter electromotive force when the alternating current crosses zero. This counter electromotive force induces a current in the short-circuit ring, and the current produces a magnetic field that keeps the moving and static iron cores pulled together.

Core Physical Diagram.jpg

Once the short-circuit ring has an open circuit, its maintaining function is lost. At the zero-crossing point, the moving iron core is released under the action of the reset compression spring; after the zero-crossing point, the moving and static iron cores pull together again. This cycle repeats continuously, producing a rattling noise 100 times per second—which is the impact sound generated when the moving and static iron cores pull together.

Consequences

The connected three-phase load will be in a state of repeated starting and stopping, which easily damages the load. The consequences caused by auxiliary contacts are the same as those mentioned above.

In such cases, replace the AC contactor, or temporarily use a copper wire to make a short-circuit ring as a substitute.

Give a tip and encourage the author!
Recommended
Mismatched AC Contactor Sizing? These 4 Typical Issues You Must Not Ignore – Click to View Solutions
AC contactors (with the electrical schematic code KM) are core electrical devices used to control the connection/disconnection between power supplies and loads in circuits, and they are also common equipment that electricians need to work with regularly. In practice, it is not uncommon to find that some peers make mistakes in selecting AC contactors, leading to improper sizing and subsequent persistent issues. Here, four of the most typical common mistakes are highlighted for reference.I. Over-R
James
09/11/2025
Comprehensive Guide to High-Frequency Fault Handling of AC Contactors: 90% of Problems Solved with One Method
1. Fault Phenomena, Cause Analysis and Handling MethodsContactor does not operate or operates abnormally after coil energization Open circuit in coil control circuit; Check if there is wire breakage or loosening at the terminal blocks. If there is a wire breakage, replace the corresponding wire; if there is loosening, fasten the corresponding terminal block. Coil damage; Measure the coil resistance with a multimeter. If the resistance is ∞, replace the coil. Thermal relay not reset after operati
Felix Spark
09/11/2025
Proper Installation of AC Contactors | A Practical Guide to Avoid Burning and Misoperation, Master It in One Article
AC contactors are widely used for switching and controlling power circuits. They use main contacts to open and close circuits, and auxiliary contacts to execute control commands. Main contacts typically only have normally open contacts, while auxiliary contacts often have two pairs of contacts with normally open and normally closed functions. Small-sized contactors are also frequently used as intermediate relays to work with main circuits, thereby achieving the function of remote control or cont
James
09/11/2025
Application and Maintenance of AC Contactors | Comprehensive Analysis of Common Fault Handling, Master It in One Article
1 Analysis of Key Components of AC ContactorsAn AC contactor is an automated electromagnetic switch used for long-term, high-frequency switching of AC main circuits and control circuits. It features advantages such as automatic operation, under-voltage and no-voltage protection, high-capacity operation, strong stability, and low maintenance requirements. In the electrical control circuits of machine tools, AC contactors are mainly used to control electric motors and other loads.The key component
Felix Spark
09/11/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.