How is the contradiction between the small grounding residual current and the neutral point displacement voltage exceeding the standard resolved?
Contradiction PointsIn automatic tracking arc suppression coils, the adjustment precision is high, the residual current is small, and the operation is close to the resonance point.In an automatic tracking arc suppression coil grounding system, two factors must be considered: Under normal operating conditions, the long-term voltage displacement of the neutral point should not exceed 15% of the system's nominal phase voltage; In the case of a ground fault, the grounding residual current should be