• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


RCD Keeps Tripping? Find the Real Cause Fast

Edwiin
Field: Power switch
China

How Residual Current Devices (RCDs) Work and Why They Trip

A residual current device (RCD), also known as a leakage circuit breaker, trips when it detects a current imbalance of 30mA or more between the live and neutral conductors. In older electrical circuits, or in installations where cables were not run through conduits, it can be extremely difficult to use RCDs effectively. Even if the system works initially, during damp or humid weather, the RCD may trip repeatedly. Identifying the exact cause and location of such leakage is often challenging.

Some suggest simply removing the RCD and replacing it with an air circuit breaker of the same rating—controlling only the live wire while connecting all neutral wires to a common busbar. While this may allow the circuit to function normally without tripping, this practice is extremely dangerous and strongly discouraged. It eliminates critical protection, putting lives and property at serious risk.

The Importance of Residual Current Devices (RCDs)

RCDs are essential safety components in residential electrical systems. They automatically disconnect the circuit when leakage current or ground faults are detected, preventing electric shocks, fires, and equipment damage. In daily use, circuits may occasionally develop faults, causing the RCD to trip. Before resetting the device, it's crucial to identify and resolve the underlying cause to ensure safety.

circuit.jpg

Below is a detailed explanation of common reasons for RCD tripping.

Why Do RCDs Trip?

RCDs are designed to prevent electrical accidents by cutting off power when dangerous leakage occurs. Tripping can be classified into two categories: normal tripping and abnormal tripping.

1. Normal Tripping

An RCD with a rated tripping current of 30mA will trip if the leakage current in the circuit exceeds approximately 25mA. This level of current is generally safe for humans (not causing fatal electric shock) and does not damage electrical equipment or cause abnormal operation. However, repeated tripping under these conditions indicates an underlying insulation issue that should be investigated.

2. Abnormal Tripping

This type of tripping is caused by defects in the RCD itself and falls into two subcategories: failure to close (reset) and nuisance tripping.

  • Failure to Close:
    If the RCD cannot be reset when power is applied but no load is connected, the device itself is likely defective. Do not attempt to repair it yourself. Repaired RCDs must be tested with specialized equipment to ensure proper function. Using a repaired device without testing is unsafe.

  • Nuisance Tripping:
    Random tripping—especially at night or when no one is home—indicates poor electromagnetic interference (EMI) immunity. RCDs exhibiting this behavior should be replaced immediately.

Sometimes, normal tripping due to minor leakage (around 25mA) can mimic nuisance tripping. This is often caused by insulation aging, where moisture causes leakage (tripping in damp conditions) but not in dry conditions. The most reliable way to distinguish between these cases is to measure the insulation resistance of the circuit and equipment.

  • Standard requirement: Insulation resistance of each conductor must be ≥ 0.5 MΩ.

  • If the total measured insulation resistance of the load circuit is less than 8.8 kΩ (calculated as 220V ÷ 25mA = 8.8 kΩ), normal tripping is expected.

circuit.jpg

Common Causes of RCD Tripping

  • Poor Installation
    Loose terminal connections can overheat, oxidize, and damage wire insulation over time. This may cause arcing, burning smells, and voltage drops, leading to circuit breaker operation.

  • Defective RCD
    Internal component failure or manufacturing defects can cause malfunction.

  • Overloaded Circuit
    When the actual load exceeds the rated current of the circuit breaker—common after installing high-power appliances like air conditioners or water heaters—a replacement with a properly rated breaker is required.

  • Leakage or Short Circuit in Appliances or Wiring
    If an appliance is leaking current, simply unplugging it and resetting the breaker may restore power.
    Troubleshooting method:

  • Turn off all branch circuits.

  • Energize them one by one.

  • If the breaker trips when a specific circuit is energized, that branch contains the fault. Isolate and repair it before restoring power.

  • Excessively High Supply Voltage
    This is dangerous and typically occurs in "three-phase four-wire" residential systems.
    Check:

  • Are both incoming lines live?

  • Are neighboring units also tripping?

  • Use a multimeter to measure input voltage.
    Never force-reset the breaker. Doing so may destroy appliances or cause a fire.

How to Troubleshoot RCD Tripping

1. Circuit Isolation Method

Follow the sequence: main line → branches → endpoints.

  • Disconnect all branch circuits.

  • Energize the main line first. If it holds, the main line is fault-free.

  • Re-energize branches one by one.

  • The circuit that causes tripping upon energizing contains the fault. Focus your inspection there.

2. Visual Inspection Method

Inspect the protected area—including the RCD and connected wiring/equipment—for visible signs of damage. Pay special attention to:

  • Corners and bends

  • Junctions and splices

  • Overhead line crossings

  • Areas prone to moisture or mechanical damage

3. Numerical Comparison Method

Use test instruments (e.g., multimeter, insulation resistance tester) to measure voltage, current, or insulation resistance. Compare results with baseline or expected values to locate faults.

Note: If the neutral wire has degraded insulation or is improperly grounded (repeated grounding), it may cause the main RCD to trip frequently while downstream (secondary) RCDs remain unaffected.

4. Test Energizing Method

Used to determine if the RCD itself is faulty:

  • Turn off power.

  • Disconnect all load-side wires from the RCD’s zero-sequence current transformer.

  • Attempt to reset the RCD.

    • If it still won’t reset → RCD is faulty (repair or replace).

    • If it resets successfully → RCD is functional; the fault lies in the distribution panel or downstream wiring.

Then:

  • Disconnect all outgoing circuits.

  • If the RCD still fails to hold → fault is in the panel (check wiring, meters, etc.).

  • If it holds → fault is in the external circuit. Use the circuit isolation method to locate the exact point.

Safety Reminder:
Never bypass or remove an RCD for convenience. While it may stop nuisance tripping, it removes vital protection against electric shock and fire. Always diagnose and fix the root cause. When in doubt, consult a licensed electrician.

Give a tip and encourage the author!

Recommended

Rockwill Powers Cambodia’s Battambang Solar-Storage Project
The Battambang Conch PV + Energy Storage Power Station in Cambodia has successfully completed its grid-connected trial operation. The project utilized medium-voltage switchgear supplied by Rockwill Intelligent Electric Co., Ltd. Despite numerous challenges—including an extremely tight delivery schedule—Rockwill Intelligent delivered high-quality products and exceptional service throughout project execution, earning consistent praise from the client.Located in Battambang, Cambodia, the Battambang
12/24/2025
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.