• Flameproof Dry-Type Mining Substation Transformer
  • Flameproof Dry-Type Mining Substation Transformer
Flameproof Dry-Type Mining Substation Transformer
discuss personally
Model
KBSGZY2-T-100/10
Basic info
Brand ROCKWILL
Model NO. Flameproof Dry-Type Mining Substation Transformer
Rated voltage 100kV
Rated frequency 50/60Hz
Series KBSGZY
Product Detail

Product Introduction

The KBSGZY series flameproof dry-type mining transformers adopt a fully corrugated cylindrical flameproof enclosure and select high-quality materials to enhance operational reliability. They require no maintenance during normal operation. These transformers are suitable not only for underground mines, tunnels and other environments with methane mixtures and coal dust where explosion hazards exist, but also for environments with gases and vapors that are not corrosive enough to metals or destructive to insulation.

Operating Principle

 The variable frequency transformer section is designed to obtain two sets of three-phase power supplies with a phase difference of 30 degrees through low-voltage dual-splitting. An electrostatic screen is placed between the high and low-voltage sections, and the insulation level of the low-voltage coils is raised to a voltage rating of 10KV to meet the higher common-mode voltage generated by the secondary-side variable frequency rectifier.

An isolation switch and circuit breaker are installed inside the high-voltage switch to disconnect the control power supply and load current. The main power source is monitored and fault isolation is performed using a comprehensive protection system with PLC. The auxiliary transformer is protected against overcurrent using fuses.

The low-voltage switch employs a dual-circuit design and utilizes two PLC comprehensive protection systems to monitor and check each other, completing equipment operation monitoring and fault isolation.

Both high and low-voltage switches communicate with the downstream variable frequency inverters, enabling phase-locking and interlocking functions to prevent equipment damage due to operational errors.

Feature

  • High-efficiency Heat Dissipation:Patented full-corrugated cylindrical structure prevents water and dust accumulation on the top, ensuring excellent heat dissipation performance.

  • Effective Explosion Protection:The shell can withstand a pressure of 1MPa, providing superior flameproof performance.

  • Low Loss and Low Noise:Partial discharge quantity is less than 5pC, which improves product reliability with low noise operation.

Main parameters

Model

Rated Capacity (kVA)

primary voltage

Secondary voltage

The connection group designation number

Loss of empty load

Load loss

Short-circuit impedance

No-load current

L

B

H

Theoretical weight kg

KBSGZY2-T-50/6

50

6000±5%

693/400 1200/693

Yy0(d11)

350

550

4

2.5

3620

840

990

2275

KBSGZY2-T-80/6

80

6000±5%

693/400 1200/693

Yy0(d11)

450

780

4

2.5

3620

840

990

2440

KBSGZY2-T-100/6

100

6000±5%

693/400 1200/693

Yy0(d11)

520

920

4

2.5

3620

840

990

2480

KBSGZY2-T-125/6

125

6000±5%

693/400 1200/693

Yy0(d11)

600

1080

4

2.5

3620

840

990

2665

KBSGZY2-T-160/6

160

6000±5%

693/400 1200/693

Yy0(d11)

700

1300

4

2

3995

1175

1385

2765

KBSGZY2-T-200/6

200

6000±5%

693/400 1200/693

Yy0(d11)

820

1500

4

2

3995

1175

1385

2905

KBSGZY2-T-250/6

250

6000±5%

693/400 1200/693

Yy0(d11)

950

1800

4

2

4055

1175

1385

3070

KBSGZY2-T-315/6

315

6000±5%

693/400 1200/693

Yy0(d11)

1100

2150

4

1.8

4055

1175

1385

3365

KBSGZY2-T-400/6

400

6000±5%

693/400 1200/693

Yy0(d11)

1300

2600

4

1.8

4100

1175

1425

3640

KBSGZY2-T-500/6

500

6000±5%

693/400 1200/693

Yy0(d11)

1500

3100

4

1.5

4115

1175

1425

3715

KBSGZY2-T-630/6

630

6000±5%

693/400 1200/693

Yy0(d11)

1800

3680

4

1.5

4175

1175

1425

4230

KBSGZY2-T-800/6

800

6000±5%

1200/693 3450

yy0(d11) Yyn0

2050

4500

4

1

4265

1175

1425

4505

KBSGZY2-T-1000/6

1000

6000±5%

1200/693 3450

yy0(d11) Yyn0

2350

5400

4

1

4265

1175

1450

5170

KBSGZY2-T-1250/6

1250

6000±5%

1200/693 3450

yy0(d11) Yyn0

2750

6500

4

1

4390

1350

1600

5705

KBSGZY2-T-1600/6

1600

6000±5%

1200/693 3450

yy0(d11) Yyn0

3350

8000

4

0.8

4610

1190

1805

8480

KBSGZY2-T-2000/6

2000

6000±5%

1200

yy0(d11) Yyn0

3800

9500

4.5

0.6

4780

1220

1870

9750

KBSGZY2-T-2500/6

2500

6000±5%

3450

yy0(d11) Yyn0

4500

10600

5

0.6

4780

1220

1985

10725

KBSGZY2-T-3150/6

3150

6000±5%

3450

Dyn11

5300

12500

5.5

0.6

5740

1310

2055

12980

KBSGZY2-T-4000/6

4000

6000±5%

3450

Dyn11

6100

14000

6

0.6

5740

1310

2055

15120

KBSGZY2-T-50/10

50

10000±5%

693/400 1200/693

Yy0(d11)

390

680

4

2.5

3930

1030

1265

2725

KBSGZY2-T-80/10

80

10000±5%

693/400 1200/693

Yy0(d11)

490

880

4

2.5

3930

1030

1265

2785

KBSGZY2-T-100/10

100

10000±5%

693/400 1200/693

Yy0(d11)

560

1050

4

2.5

3930

1030

1265

2910

KBSGZY2-T-125/10

125

10000±5%

693/400 1200/693

Yy0(d11)

650

1300

4

2.5

3930

1030

1265

3000

KBSGZY2-T-160/10

160

10000±5%

693/400 1200/693

Yy0(d11)

800

1500

4

2

3980

1030

1265

3290

KBSGZY2-T-200/10

200

10000±5%

693/400 1200/693

Yy0(d11)

950

1800

4

2

4175

1030

1520

3400

KBSGZY2-T-250/10

250

10000±5%

693/400 1200/693

Yy0(d11)

1100

2100

4

2

4175

1030

1520

3530

KBSGZY2-T-315/10

315

10000±5%

693/400 1200/693

Yy0(d11)

1300

2500

4

1.8

4175

1030

1520

3500

KBSGZY2-T-400/10

400

10000±5%

693/400 1200/693

Yy0(d11)

1500

3000

4

1.8

4220

1090

1555

3985

KBSGZY2-T-500/10

500

10000±5%

693/400 1200/693

Yy0(d11)

1750

3500

4

1.5

4220

1260

1555

4445

KBSGZY2-T-630/10

630

10000±5%

693/400 1200/693

Yy0(d11)

2000

4100

4

1.5

4280

1260

1555

4685

KBSGZY2-T-800/10

800

10000±5%

1200/693 3450

yy0(d11) Yyn0

2300

5100

4

1.2

4345

1260

1555

4905

KBSGZY2-T-1000/10

1000

10000±5%

1200/693 3450

yy0(d11) Yyn0

2600

6100

4.5

1.2

4375

1330

1585

5505

KBSGZY2-T-1250/10

1250

10000±5%

1200/693 3450

yy0(d11) Yyn0

3100

7400

4.5

1

4420

1370

1610

5895

KBSGZY2-T-1600/10

1600

10000±5%

1200/693 3450

yy0(d11) Yyn0

3800

8500

5

1

4890

1270

1805

8600

KBSGZY2-T-2000/10

2000

10000±5%

1200

Yy0 Yyn0

4500

9700

5

0.7

4960

1270

1825

10720

KBSGZY2-T-2500/10

2500

10000±5%

3450

Yy0 Yyn0

5200

10800

5.5

0.7

4965

1270

2025

11490

KBSGZY2-T-3150/10

3150

10000±5%

3450

Dyn11

6100

12800

5.5

0.7

5065

1320

2095

13400

KBSGZY2-T-4000/10

4000

10000±5%

3450

Dyn11

7000

15000

6

0.7

5800

1320

2095

17500

KBSGZY2-T-5000/10

5000

10000±5%

3450

Dyn11

8200

17600

6.5

0.6

5980

1490

2150

20550

KBSGZY2-T-6300/10

6300

10000±5%

3450

Dyn11

9500

20000

7

0.6

5980

1490

2150

26000

 

Model

Rated Capacity (kVA)

primary voltage

Secondary voltage

The link group designation

Loss of empty load

Load loss

Short-circuit impedance

No-load current

L

B

H

KBSGZY-ZT-1600/6/2x1.903

1600

6000±5%

2x1.903

Qd0y11

3800

9500

7.5

0.6

5370

1180

1085

KBSG2Y-ZT-1600/10/2x1.903

1600

10000±5%

2x1.903

Qd0y11

4500

9700

7.5

0.7

5690

1260

1085

KBSGZY-ZT-2000/6/2x1.903

2000

6000±5%

2x1.903

Qd0y11

4500

10600

8

0.6

5410

1210

1085

KBSGZY-ZT-2000/10/2x1903

2000

10000±5%

2x1.903

Qd0y11

5200

10800

8

0.7

5760

1260

1085

KBSGZY-ZT-2500/6/2x1.903

2500

6000±5%

2x1.903

Qd0y11

5300

12500

8

0.6

5645

1260

2025

KBSGZY-ZT-2500/10/2x1.903

2500

10000±5%

2x1.903

Qd0y11

6100

12800

8

0.7

5845

1260

2025

Know your supplier
ROCKWILL
Rockwill Electric Group Global Manufacturer of High voltage and medium-voltage power equipment and smart grid solutions. Headquartered in Wenzhou, China. Serving 100+ countries with quality, innovation, and trust. What We Offer: • HV-MV switchgear (VCB, SF₆ circuit breakers, RMU, GIS) • Distribution transformers and substations • Smart grid and monitoring systems • Solar, wind, EV charging, and energy storage solutions • EPC turnkey power projects Certified: ISO 9001 / ISO 14001 / ISO 45001
Main Categories
High Voltage Electrical Apparatus
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$150,000,000
Professional Experience
16 years
Workplace
108000m²m²
占位
占位
Related Products
Related Knowledges
What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
Edwiin
08/30/2025
Fault Analysis and Treatment of Oil-Immersed Transformers
Fault Analysis and Treatment of Oil-Immersed Transformers
Oil Leakage at Welded JointsOil leakage at welded joints primarily stems from poor welding quality, such as incomplete or detached welds, and defects like pinholes and gas pores. Although oil-immersed transformers are initially coated with solder and paint during manufacturing, potentially masking these issues temporarily, the defects tend to surface during operation. Additionally, electromagnetic vibration can cause weld cracks, leading to oil leakage.To resolve such leaks, the first critical s
Edwiin
08/29/2025
What losses occur during operation of the transformer? How to reduce losses?
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Cable Fault Detection, Testing, Location and Repair
Cable Fault Detection, Testing, Location and Repair
I. Methods for Cable Testing and Inspection:Insulation Resistance Test: Use an insulation resistance tester to measure the insulation resistance value of the cable. A high insulation resistance value indicates good insulation, while a low value may suggest insulation problems requiring further investigation.Voltage Withstand Test: Apply a high-voltage test using a high-voltage tester to verify whether the cable can withstand high voltage under its rated operating conditions. Under normal circums
Leon
08/29/2025
Cable Quality Inspection and Cable Detection & Testing
Cable Quality Inspection and Cable Detection & Testing
Power cable quality inspection and cable testing are conducted to ensure that the cable's quality and performance meet specified requirements, thereby guaranteeing the safe and stable operation of power systems. Below are some common contents of power cable quality inspection and cable testing:Visual Inspection: Check the cable surface for physical defects such as damage, deformation, or scratches to ensure the cable's exterior is intact.Dimensional Measurement: Measure dimensional parameters su
Edwiin
08/29/2025
Transformer Detection, Testing, Maintenance and Servicing
Transformer Detection, Testing, Maintenance and Servicing
Transformer testing, inspection, and maintenance are essential tasks to ensure normal operation and extend the service life of transformers. Below are some recommended steps:Visual Inspection: Regularly inspect the transformer's exterior, including the enclosure, cooling system, and oil tank. Ensure the enclosure is intact, free from corrosion, damage, or leakage.Insulation Resistance Testing: Use an insulation resistance tester to check the transformer's insulation system. Verify that the insul
Vziman
08/29/2025
×
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!