• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Indoor Vacuum Circuit Breaker: Operation & Maintenance

Echo
Echo
Maydon: Transformer Analysis
China

Overvoltage Protection

Vacuum circuit breakers possess excellent current-breaking performance. However, when interrupting inductive loads, the rapid change in current can generate high overvoltages across the inductance, which requires attention.

When switching small-capacity motors, starting currents are relatively high; measures should be taken to reduce the inrush current.

For transformers, the need for protection varies with design. Oil-immersed transformers have high impulse voltage withstand capability and large stray capacitance, generally not requiring additional protective devices. However, for dry-type transformers with lower impulse withstand levels or furnace transformers subject to frequent switching and lagging currents, protective measures such as metal-oxide surge arresters, distributed cable capacitance, or added shunt capacitors are recommended.

For vacuum circuit breakers used in feeder protection, the long line length provides sufficient stray capacitance, and multiple connected devices help suppress high restriking overvoltages. Thus, special protective measures are typically unnecessary.

For capacitor banks, field tests show that overvoltages during closing operations generally do not exceed twice the system voltage. In China, shunt capacitors are typically used at voltages below 60 kV, where equipment insulation levels are sufficient to withstand such overvoltages without damage. However, vacuum circuit breakers with poor mechanical performance may exhibit prolonged contact vibration during operation, leading to high overvoltages—phenomena observed in both domestic and international tests and thus require attention.

Strict Control of Closing and Opening Speeds

If the closing speed of a vacuum circuit breaker is too low, pre-arc time increases, accelerating contact wear. Additionally, as vacuum interrupters typically use copper welding and high-temperature degassing processes, their mechanical strength is relatively low and they are sensitive to vibration. Excessively high closing speeds can cause significant mechanical shock, imposing strong forces on the bellows and reducing their service life. Typically, the closing speed of vacuum circuit breakers ranges from 0.6 to 2 m/s, with an optimal value depending on the specific design.

During interruption, the arcing time is very short—usually less than 1.5 power-frequency half-cycles. To ensure sufficient dielectric strength at the first current zero, it is generally required that the contact travel reaches 50%–80% of the total stroke within the first half-cycle. Therefore, the opening speed must be strictly controlled.

Furthermore, both the opening and closing dampers should have good performance characteristics to minimize mechanical impact during operation, thereby extending the service life of the vacuum interrupter.

Strict Control of Contact Travel

It is incorrect to assume that a larger contact gap benefits arc extinction and arbitrarily increase the contact travel. Vacuum circuit breakers have relatively short contact strokes. For rated voltages of 10–15 kV, the typical contact stroke is only 8–12 mm, with an over-travel of 2–3 mm. Excessively increasing the contact travel can impose excessive stress on the bellows after closing, potentially damaging the bellows and compromising the vacuum seal of the interrupter.

Strict Control of Load Current

Vacuum circuit breakers have limited overload capacity. Due to the vacuum between the contacts and the enclosure acting as a thermal insulator, heat from the contacts and conductive rods is mainly dissipated through conduction along the rod. To ensure the operating temperature remains within allowable limits, the working current must be strictly controlled and kept below the rated value.

Rigorous Acceptance Testing upon Commissioning

Although vacuum circuit breakers are thoroughly tested before factory shipment, after transportation and on-site installation, key parameters must be re-measured and verified to detect any changes due to handling or misalignment between the breaker and operating mechanism. Key parameters to verify include:

  • Closing bounce

  • Opening synchronization

  • Contact gap (opening distance)

  • Compression travel

  • Closing and opening speeds

  • Closing and opening times

  • DC contact resistance

  • Interrupter insulation level

  • Mechanical operation tests

All results must meet the manufacturer’s technical specifications before the breaker is put into service.

Maintenance Intervals for Vacuum Circuit Breakers

Maintenance intervals should follow established regulations and be adjusted based on actual operating conditions. It is a misconception that vacuum circuit breakers require no maintenance. Specific guidelines include:

  • Perform power-frequency withstand voltage tests across the interrupter poles during seasonal or annual preventive maintenance to assess vacuum integrity.

  • After 2,000 normal operation cycles (making/breaking load current) or 10 interruptions of rated short-circuit current, inspect all screws for looseness. Maintenance should follow the manufacturer’s instructions. If all parameters remain within acceptable limits, the breaker may continue in service.

  • If a vacuum circuit breaker has been out of service or in storage for 20 years, its vacuum level should be tested using the specified method for vacuum interrupters. If the vacuum does not meet requirements, the interrupter must be replaced.

Vacuum Interrupter

The vacuum interrupter is the core component of a vacuum circuit breaker. It uses glass or ceramic envelopes for structural support and hermetic sealing, containing moving and stationary contacts along with a shield. The interior is under high vacuum, typically 1.33 × 10⁻⁵ to 1 Pa, ensuring reliable arc interruption and insulation performance.

Once the vacuum level degrades, the interrupting capability deteriorates significantly. Therefore, the vacuum interrupter must be protected from any external impact—no knocking, tapping, or applying force during handling or maintenance. Never place objects on top of the circuit breaker to avoid accidental impact.

Manufacturers perform strict parallelism checks and precise assembly before delivery. During maintenance, all interrupter mounting bolts must be uniformly tightened to ensure even stress distribution and prevent damage.

Авторга сўров ва қўлланма беринг!
Tavsiya etilgan
3D Wound-Core Transformer: Future of Power Distribution
3D Wound-Core Transformer: Future of Power Distribution
Technical Requirements and Development Trends for Distribution Transformers Low losses, especially low no-load losses; highlighting energy-saving performance. Low noise, particularly during no-load operation, to meet environmental protection standards. Fully sealed designto prevent transformer oil from contacting external air, enabling maintenance-free operation. Integrated protection devices within the tank, achieving miniaturization; reducing transformer size for easier on-site installation. C
Echo
10/20/2025
How to Inspect 10kV Vacuum Circuit Breakers Properly
How to Inspect 10kV Vacuum Circuit Breakers Properly
I. Inspection of Vacuum Circuit Breakers During Normal Operation1. Inspection in Closed (ON) Position The operating mechanism should be in the closed position; The main shaft roller should be disengaged from the oil damper; The opening spring should be in a charged (stretched) energy-stored state; The length of the moving contact rod of the vacuum interrupter protruding below the guide plate should be approximately 4–5 mm; The bellows inside the vacuum interrupter should be visible (this does no
Felix Spark
10/18/2025
How to Choose Vacuum Circuit Breakers Correctly?
How to Choose Vacuum Circuit Breakers Correctly?
01 PrefaceIn medium-voltage systems, circuit breakers are indispensable primary components. Vacuum circuit breakers dominate the domestic market. Therefore, correct electrical design is inseparable from the proper selection of vacuum circuit breakers. In this section, we will discuss how to correctly select vacuum circuit breakers and common misconceptions in their selection.02 Interrupting Capacity for Short-Circuit Current Need Not Be Excessively HighThe short-circuit interrupting capacity of
James
10/18/2025
Vacuum vs Air Circuit Breakers: Key Differences
Vacuum vs Air Circuit Breakers: Key Differences
Low-Voltage Air Circuit Breakers vs. Vacuum Circuit Breakers: Structure, Performance and ApplicationLow-voltage air circuit breakers, also known as universal or molded frame circuit breakers (MCCBs), are designed for AC voltages of 380/690V and DC voltages up to 1500V, with rated currents ranging from 400A to 6300A or even 7500A. These breakers use air as the arc-quenching medium. The arc is extinguished through arc elongation, splitting, and cooling by an arc chute (arc runner). Such breakers c
Garca
10/18/2025
O'xshash mahsulotlar
So'rov
Yuklab olish
IEE Business ilovalarini olish
IEE-Business ilovasini ishlatib jihozni qidirish orqali yechimlarni oling muvaffaqiyatlari bilan bog'laning va istalgan joyda va vaqtda sohaniy hamkorlikka qatnashing kuchli elektr energetika loyihalaringiz va biznesingiz rivojlanishi uchun