• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Live Partial Discharge Testing for RMUs: Methods, Issues, and Solutions

Oliver Watts
Oliver Watts
Field: Inspection and testing
China

1 Live Testing Analysis

Detection of Issues through Live Testing

In October of a certain year, during live partial discharge (PD) testing on 10kV ring main units (RMUs) under our jurisdiction, the maintenance and testing team observed significantly elevated signal amplitudes in several units (Transient Earth Voltage (TEV) readings around 18 dB, and ultrasonic readings around 20 dB). Most of these units were from the same manufacturer. Consequently, a unified test was conducted on 15 RMUs from this manufacturer across the network, revealing similar discharge phenomena in 7 units.

Visual inspection through observation windows showed obvious tracking marks on the cable terminations and clear signs of burning on the T-connectors. Upon disassembling the cable terminations, severe discharge damage was found in some units. Tracking and arcing marks were visible on the inner wall of the plug, the main body of the surge arrester, the surface of the epoxy bushing, and the surface of the plug cap. Furthermore, the interface between the plug body and the cap could be easily pried apart by hand, indicating insufficient clamping force. This allowed moisture ingress, leading to corrosion of metal components and reduced insulation strength at the interface, resulting in varying degrees of surface tracking. After replacing the affected components with qualified parts, follow-up retesting was conducted on these RMUs. The partial discharge measurements have since remained within normal ranges.

2 Summary of Testing Experience

Determining whether an RMU has partial discharge requires a comprehensive assessment based on "listening," "smelling," "observing," and "measuring." Routine testing generally follows these steps:

  • Preparation before Testing: Ensure the handheld PD detector is self-checked and functioning properly. Prepare a flashlight and relevant equipment documentation. Inspect the environment around the RMU to ensure safety for personnel and equipment before proceeding. Verify that the equipment name and number match the system records, and confirm that the labeling on each cabinet is accurate.

  • Preliminary Diagnosis ("Listen," "Smell," "Observe"): Check if the RMU’s gas pressure is normal. Before measurement, listen for any abnormal sounds from the RMU; if distinct discharge noises are heard, immediately move away from the equipment and promptly report to the equipment manager for emergency handling. Before opening the cabinet door, smell for any unusual odors inside; a noticeable burnt smell indicates the unit should be prioritized for testing. If the RMU has an observation window, use a flashlight to inspect the interior. Discharge on the cable termination typically forms tree-like discharge traces on the T-connector extending to the grounding point, and the insulating plug may show white, melted burn marks.

Testing Procedure:

  • Measure Background Value: The background value refers to the signal measured on the metal door of the 10kV high-voltage room. Since high-frequency signals from partial discharge are electromagnetic waves that propagate in all directions, transient earth voltages can be induced on grounded metal surfaces even in non-energized areas. Measuring the background value before testing the RMU provides a rough indication of the overall PD condition in the high-voltage room.

  • TEV Measurement: Place the sensor tightly against the metal surface of the cabinet and pay attention to the measurement position. Due to the short wavelength of high-frequency PD signals, attenuation is rapid—shorter wavelengths decay faster. On the measuring instrument, this manifests as a signal amplitude that decreases from strong to weak, which can be used to help locate the source of the discharge.

  • Ultrasonic Measurement: Conduct measurements at the gaps between cabinet doors to enhance sensitivity to airborne sound waves.

  • Result Evaluation: Analyze the measurement data and draw conclusions based on the judgment criteria specified in the Shenzhen Bureau RMU Partial Discharge Testing Work Instruction. Refer to Table 1 for the RMU partial discharge testing evaluation standards.

Give a tip and encourage the author!
Recommended
A Guide to the Latest Transformer Testing Technologies
A Guide to the Latest Transformer Testing Technologies
Transformers come in many types, primarily oil-immersed and dry-type. Their fault manifestations are diverse, but most failures are concentrated in the windings, core, connecting components, and oil contamination. For example, winding insulation damage, open circuits, short circuits, and inter-turn short circuits at connection points. Common external symptoms of transformer faults include severe overheating, excessive temperature rise, abnormal noise, and three-phase imbalance.Routine transforme
Oliver Watts
10/20/2025
Inspection of transformers can be performed without any detection tools.
Inspection of transformers can be performed without any detection tools.
Transformers are electrical devices that change voltage and current based on the principle of electromagnetic induction. In power transmission and distribution systems, transformers are essential for stepping up or stepping down voltages to reduce energy losses during transmission. For example, industrial facilities typically receive power at 10 kV, which is then stepped down to low voltage via transformers for on-site use. Today, let’s learn about several common transformer inspection methods.1
Oliver Watts
10/20/2025
Vacuum Circuit Breakers for Capacitor Bank Switching
Vacuum Circuit Breakers for Capacitor Bank Switching
Reactive Power Compensation and Capacitor Switching in Power SystemsReactive power compensation is an effective means to increase system operating voltage, reduce network losses, and improve system stability.Conventional Loads in Power Systems (Impedance Types): Resistance Inductive reactance Capacitive reactanceInrush Current During Capacitor EnergizationIn power system operation, capacitors are switched in to improve power factor. At the moment of closing, a large inrush current is generated.
Oliver Watts
10/18/2025
Vacuum Circuit Breaker Withstand Voltage Test Guide
Vacuum Circuit Breaker Withstand Voltage Test Guide
Insulation Withstand Voltage Test Standards for Vacuum Circuit BreakersThe main purpose of the insulation withstand voltage test for vacuum circuit breakers is to verify whether the insulation performance of the equipment under high voltage is qualified, and to prevent breakdown or flashover accidents during operation. The test process must be strictly carried out in accordance with power industry standards to ensure equipment safety and power supply reliability.Test ObjectsThe test objects incl
Garca
10/18/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.