Analysis on Live Testing of 10kV SF₆ Ring Main Units

Oliver Watts
08/09/2025

1 Live Testing Analysis

Detection of Issues through Live Testing

In October of a certain year, during live partial discharge (PD) testing on 10kV ring main units (RMUs) under our jurisdiction, the maintenance and testing team observed significantly elevated signal amplitudes in several units (Transient Earth Voltage (TEV) readings around 18 dB, and ultrasonic readings around 20 dB). Most of these units were from the same manufacturer. Consequently, a unified test was conducted on 15 RMUs from this manufacturer across the network, revealing similar discharge phenomena in 7 units.

Visual inspection through observation windows showed obvious tracking marks on the cable terminations and clear signs of burning on the T-connectors. Upon disassembling the cable terminations, severe discharge damage was found in some units. Tracking and arcing marks were visible on the inner wall of the plug, the main body of the surge arrester, the surface of the epoxy bushing, and the surface of the plug cap. Furthermore, the interface between the plug body and the cap could be easily pried apart by hand, indicating insufficient clamping force. This allowed moisture ingress, leading to corrosion of metal components and reduced insulation strength at the interface, resulting in varying degrees of surface tracking. After replacing the affected components with qualified parts, follow-up retesting was conducted on these RMUs. The partial discharge measurements have since remained within normal ranges.

2 Summary of Testing Experience

Determining whether an RMU has partial discharge requires a comprehensive assessment based on "listening," "smelling," "observing," and "measuring." Routine testing generally follows these steps:

  • Preparation before Testing: Ensure the handheld PD detector is self-checked and functioning properly. Prepare a flashlight and relevant equipment documentation. Inspect the environment around the RMU to ensure safety for personnel and equipment before proceeding. Verify that the equipment name and number match the system records, and confirm that the labeling on each cabinet is accurate.
  • Preliminary Diagnosis ("Listen," "Smell," "Observe"): Check if the RMU’s gas pressure is normal. Before measurement, listen for any abnormal sounds from the RMU; if distinct discharge noises are heard, immediately move away from the equipment and promptly report to the equipment manager for emergency handling. Before opening the cabinet door, smell for any unusual odors inside; a noticeable burnt smell indicates the unit should be prioritized for testing. If the RMU has an observation window, use a flashlight to inspect the interior. Discharge on the cable termination typically forms tree-like discharge traces on the T-connector extending to the grounding point, and the insulating plug may show white, melted burn marks.

Testing Procedure:

  • Measure Background Value: The background value refers to the signal measured on the metal door of the 10kV high-voltage room. Since high-frequency signals from partial discharge are electromagnetic waves that propagate in all directions, transient earth voltages can be induced on grounded metal surfaces even in non-energized areas. Measuring the background value before testing the RMU provides a rough indication of the overall PD condition in the high-voltage room.
  • TEV Measurement: Place the sensor tightly against the metal surface of the cabinet and pay attention to the measurement position. Due to the short wavelength of high-frequency PD signals, attenuation is rapid—shorter wavelengths decay faster. On the measuring instrument, this manifests as a signal amplitude that decreases from strong to weak, which can be used to help locate the source of the discharge.
  • Ultrasonic Measurement: Conduct measurements at the gaps between cabinet doors to enhance sensitivity to airborne sound waves.
  • Result Evaluation: Analyze the measurement data and draw conclusions based on the judgment criteria specified in the Shenzhen Bureau RMU Partial Discharge Testing Work Instruction. Refer to Table 1 for the RMU partial discharge testing evaluation standards.

Oliver Watts

Hey! I'm Oliver Watts, an electrical engineer in Inspection and Testing. With years of hands - on experience, I ensure electrical systems meet top safety and performance standards. Using advanced gear, I conduct diverse tests, easily spotting issues in both large - scale industrial and small - scale commercial setups. I love teaming up, sharing knowledge, and keeping up with industry regs. Also, I'm skilled at data analysis with software. If you're into electrical inspection or just want to chat engineering, reach out. Let's connect and explore!

Analysis of Two Faults in 10kV SF6 Ring Main Units
Analysis of Two Faults in 10kV SF6 Ring Main Units
1. Introduction to 10kV SF6 Ring Main Units (RMUs)A 10kV SF6 ring main unit typically consists of three main parts: the gas compartment (tank), the operating mechanism compartment, and the cable connection compartment.The gas compartment is the core component of the RMU. It is filled with SF6 gas and houses critical elements such as the load switch, busbars, and switch shaft. The load switch features a three-position design—comprising closing, opening, and grounding functions—and is
Felix Spark
08/09/2025
A Brief Analysis of Technical Issues in SF6 Fully Insulated Gas-Insulated Ring Main Units
A Brief Analysis of Technical Issues in SF6 Fully Insulated Gas-Insulated Ring Main Units
SF6 Fully Insulated Gas-Insulated Ring Main Units (hereinafter referred to as RMUs) primarily consist of load switch units and high-voltage AC load switch-fuse combination appliances (hereinafter referred to as combination appliances). Depending on user requirements, they can be configured as either common-tank or unitized structures.In practical engineering applications, electrical connections are typically established using either top-mounted solid-insulated busbars or side-mounted plug-in bus
Ron
08/09/2025
Advantages of SF6 Fully Insulated Ring Main Units in Power Supply Systems
Advantages of SF6 Fully Insulated Ring Main Units in Power Supply Systems
Current Power Supply Method Using SF6 Ring Main UnitsTo enhance grid performance, the design of traditional SF6 ring main units (RMUs) has been further optimized. A key feature of second-generation SF6 RMUs is the use of a grounded, enclosed epoxy resin housing, with SF6 gas as the insulating medium. Two three-position load switches and one three-position arc-rotating circuit breaker are integrated into a single sealed unit, equipped with a pressure relief safety valve. In the event of arc-quenc
Echo
08/09/2025
Problems during the induction test of an HKSSPZ-6300/110 type furnace transformer
Problems during the induction test of an HKSSPZ-6300/110 type furnace transformer
A HKSSPZ-6300/110 electric arc furnace transformer has the following basic parameters:Rated capacity S = 6300 kVA, primary voltage U₁ = 110 kV, secondary voltage U₂ = 110–160 V, vector group YNd11, with both low-voltage winding ends (start and finish) brought out, and equipped with 13-step on-load tap changing. Insulation levels: HV/HV neutral/LV, LI480AC200 / LI325AC140 / AC5.The transformer uses a dual-core series voltage regulation design, with an "8"-shaped low-voltage winding configur
Oliver Watts
08/06/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!