From 66 kV to 500 kV: The Rise of Eco-Friendly Vegetable Oil Transformers

Noah
Noah
Field: Design & Maintenance
Australia

Vegetable Oil in High-Voltage Power Transformers: Current Status, Technical Challenges, and Market Outlook

Natural ester (vegetable) oil is gaining traction as a sustainable alternative to mineral oil in power transformers. Thanks to its biodegradability, high fire point (>300°C), and extended insulation life, vegetable oil transformers are increasingly deployed worldwide—especially in environmentally sensitive or fire-risk areas.

As of 2025, over 2 million vegetable oil-filled transformers are in service globally. However, the vast majority are low-voltage distribution units (<35 kV). Adoption in high-voltage (HV) applications (≥66 kV) remains limited but is steadily growing.

Global Deployment of HV Vegetable Oil Transformers

  • China: Only one vegetable oil transformer rated 66 kV or above has been grid-connected to date.

  • Worldwide: Fewer than 1,000 HV units (≥66 kV) are estimated to be in operation.

  • Highest Voltage Achieved: A 420 kV natural ester transformer by Siemens (Germany), commissioned in 2013, continues safe operation.

  • 500 kV Prototypes: Several manufacturers (e.g., Hitachi ABB Power Grids, Siemens Energy) have developed 500 kV vegetable oil transformers, though none have been grid-connected yet.

  • HVDC Applications: Early-stage research is exploring natural esters in DC systems, but no commercial products exist.

transformer..jpg

Alt text: 110 kV natural ester-filled power transformer installed in a substation, showcasing eco-friendly high-voltage technology.

Why Is HV Adoption So Limited?

While vegetable oil offers clear environmental and safety advantages, its use in high-voltage transformers faces significant technical hurdles:

1. Insulation Performance in Non-Uniform Electric Fields

HV transformers feature complex geometries with highly non-uniform electric fields (e.g., near bushings, tap changers). Vegetable oil’s higher dielectric constant (~3.0 vs. ~2.2 for mineral oil) alters field distribution, requiring complete redesign of insulation systems.

2. Material Compatibility

Seals, gaskets, paints, and solid insulation (e.g., pressboard) must be compatible with vegetable oil’s:

  • Higher viscosity (affects cooling),

  • Oxidation behavior (forms acids over time),

  • Hygroscopic nature (absorbs more moisture).

3. Lack of Standards & Field Experience

  • IEC 62770 and IEEE C57.147 provide guidance for natural ester use, but HV-specific standards are incomplete.

  • Utilities lack long-term operational data on aging, maintenance intervals, and fault response.

4. Low Market Demand

HV transformers have long lifespans (30–50 years) and are rarely replaced. Combined with higher upfront costs, this slows adoption—even where regulations favor green alternatives.

The Path Forward: Collaboration Is Key

Overcoming these barriers requires close cooperation among:

  • Transformer manufacturers (design validation),

  • Oil producers (formulation stability),

  • Utilities (pilot projects, data sharing),

  • Standards bodies (updating IEC/IEEE guidelines).

China’s Strategic Opportunity

Although China’s HV vegetable oil transformer deployment lags, its position as the world’s largest transformer manufacturer offers unique leverage. With strong policy support for carbon neutrality and green grid infrastructure, China is poised to lead the next wave of HV natural ester transformer innovation.

Give a tip and encourage the author!
Recommended
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Neutral Grounding Gap Protection Measures?In a certain power grid, when a single-phase ground fault occurs on a power supply line, both the transformer neutral grounding gap protection and the power supply line protection operate simultaneously, causing an outage of an otherwise healthy transformer. The main reason is that during a system single-phase ground fault, the zero-sequence overvoltage causes the transformer neutral grounding gap to break down. The resulting
Noah
12/05/2025
Innovative & Common Winding Structures for 10kV High-Voltage High-Frequency Transformers
Innovative & Common Winding Structures for 10kV High-Voltage High-Frequency Transformers
1.Innovative Winding Structures for 10 kV-Class High-Voltage High-Frequency Transformers1.1 Zoned and Partially Potted Ventilated Structure Two U-shaped ferrite cores are mated to form a magnetic core unit, or further assembled into series/series-parallel core modules. Primary and secondary bobbins are mounted on the left and right straight legs of the core, respectively, with the core mating plane serving as the boundary layer. Windings of the same type are grouped on the same side. Litz wire i
Noah
12/05/2025
How to Increase Transformer Capacity? What Needs to Be Replaced for Transformer Capacity Upgrade?
How to Increase Transformer Capacity? What Needs to Be Replaced for Transformer Capacity Upgrade?
How to Increase Transformer Capacity? What Needs to Be Replaced for Transformer Capacity Upgrade?Transformer capacity upgrade refers to improving the capacity of a transformer without replacing the entire unit, through certain methods. In applications requiring high current or high power output, transformer capacity upgrades are often necessary to meet demand. This article introduces methods for transformer capacity upgrade and the components that need to be replaced.A transformer is a critical
Echo
12/04/2025
Causes of Transformer Differential Current and Hazards of Transformer Bias Current
Causes of Transformer Differential Current and Hazards of Transformer Bias Current
Causes of Transformer Differential Current and Hazards of Transformer Bias CurrentTransformer differential current is caused by factors such as incomplete symmetry of the magnetic circuit or insulation damage. Differential current occurs when the primary and secondary sides of the transformer are grounded or when the load is unbalanced.Firstly, transformer differential current leads to energy waste. Differential current causes additional power loss in the transformer, increasing the load on the
Edwiin
12/04/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.