Out of phase in generator circuit breaker (GCB)

Edwiin
04/22/2025

An out-of-phase condition transpires when a generator circuit breaker (GCB) closing operation is executed precisely at the moment when there is a lack of synchronism between the voltage phasors of the generator on one side of the GCB and those of the external grid on the other side. Another common scenario is when a generator runs in an out-of-phase state due to system instability, necessitating the tripping of the GCB.
The severity of such an interruption is directly related to the out-of-phase angle δ. Given that the generator faces significant risks when δ exceeds 90°, protective relays are typically configured to trip at around δ = 90°. Standardized out-of-phase transient recovery voltage (TRV) values are established based on a 90° out-of-phase angle at the rated voltage. It is worth noting that for smaller generator units, larger out-of-phase angles can still occur.
When the out-of-phase angle δ reaches 90°, the current is approximately 50% of the fault current supplied by the system. On the voltage side, the GCB is subjected to a TRV with a rate of rise of the recovery voltage (RRRV) roughly equivalent to that in a system-source fault, but its peak value is nearly twice as high. The out-of-phase current specified in the standard is indeed set at half of the system source-fault current.
The figure illustrates the standardized TRV waveforms for various generator faults, juxtaposed with the TRV of a 100% fault for a 24 kV GCB, providing a clear visual comparison of the electrical characteristics under different fault conditions.
Edwiin

Analysis of the Principle of Second - harmonic Restraint for Overcurrent Protection of Distribution Automation Switches
Analysis of the Principle of Second - harmonic Restraint for Overcurrent Protection of Distribution Automation Switches
Substance of Second - harmonic Restraint in Overcurrent ProtectionThe substance of second - harmonic restraint in overcurrent protection is to use the second - harmonic component to judge whether the current is a fault current or an excitation inrush current. When the percentage of the second - harmonic component to the fundamental - wave component is greater than a certain value, it is judged to be caused by the excitation inrush current, and the overcurrent protection is blocked.Therefore, the
Leon
07/18/2025
What are the typical connection methods for 35kV distribution lines?
What are the typical connection methods for 35kV distribution lines?
Typical Wiring Diagram of 35kV Line Radial π ConnectionWhen a 35kV line adopts a radial power grid structure, a single - side power supply or a double - side power supply radial type can be used according to the situation of the power supply points, and a loop - out interval is reserved at the end of the line.Typical Wiring Diagram of 35kV Line Radial T - ConnectionFor double - radial lines, it is advisable to select a double - side power supply. When the power supply points do not meet the r
Leon
07/18/2025
Why are the ground fault point and the accident point not at the same location?
Why are the ground fault point and the accident point not at the same location?
Fault Transfer VoltageIn low - voltage distribution systems, there is a type of personal electric shock accident where the accident occurrence point and the system fault point are not at the same location. This kind of accident occurs because after a ground fault happens elsewhere, the generated fault voltage is conducted to the metal casings of other equipment through the PE wire or PEN wire. When the fault voltage on the metal casing of the equipment is higher than the human - body safe voltag
Leon
07/18/2025
What is reactive power measurement?
What is reactive power measurement?
The power which exists in the circuit when the voltage and current are out of phase to each other, such type of power is known as the reactive power. The formula measures the reactive power in the circuitReactive Power Measurement & VarmetersReactive power measurement is critical as it indicates circuit power loss: low reactive power worsens load power factor, increasing system losses. Varmeters (volt-ampere reactive meters) measure reactive power and are categorized by circuit phases:Single
Edwiin
07/17/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!