Out of phase in generator circuit breaker (GCB)

Edwiin
Field: Power switch
China

An out-of-phase condition transpires when a generator circuit breaker (GCB) closing operation is executed precisely at the moment when there is a lack of synchronism between the voltage phasors of the generator on one side of the GCB and those of the external grid on the other side. Another common scenario is when a generator runs in an out-of-phase state due to system instability, necessitating the tripping of the GCB.
The severity of such an interruption is directly related to the out-of-phase angle δ. Given that the generator faces significant risks when δ exceeds 90°, protective relays are typically configured to trip at around δ = 90°. Standardized out-of-phase transient recovery voltage (TRV) values are established based on a 90° out-of-phase angle at the rated voltage. It is worth noting that for smaller generator units, larger out-of-phase angles can still occur.
When the out-of-phase angle δ reaches 90°, the current is approximately 50% of the fault current supplied by the system. On the voltage side, the GCB is subjected to a TRV with a rate of rise of the recovery voltage (RRRV) roughly equivalent to that in a system-source fault, but its peak value is nearly twice as high. The out-of-phase current specified in the standard is indeed set at half of the system source-fault current.
The figure illustrates the standardized TRV waveforms for various generator faults, juxtaposed with the TRV of a 100% fault for a 24 kV GCB, providing a clear visual comparison of the electrical characteristics under different fault conditions.
Give a tip and encourage the author!
Recommended
Ensuring Reliability: A Deep Dive into Transformer Maintenance
IntroductionElectric transformers are the backbone of modern power distribution systems, silently enabling the reliable delivery of electricity to homes, businesses, and industries. As these critical assets age and the demand for uninterrupted power grows, the importance of diligent transformer maintenance has never been greater. This essay explores the essential role of transformer maintenance, highlighting the value of proactive care, the impact of advanced diagnostic technologies, and the tra
Vziman
09/03/2025
How does a transformer work?
Transformer Operation PrincipleA transformer is an electrical device that operates on the principle of electromagnetic induction to transfer electrical energy from one circuit to another. It enables the adjustment of voltage levels within an alternating current (AC) system, either stepping up (increasing) or stepping down (decreasing) voltage while maintaining the same frequency.Working Principle:Basic ComponentsA transformer consists of two coils, known as windings—the "primary winding" connect
Rockwell
09/03/2025
A hybrid DC circuit breaker
Most DC molded-case circuit breakers use natural air arc extinction, and there are typically two arc extinguishing methods: one is conventional opening and closing, where the contacts axially stretch the arc, while the conductive circuit generates a magnetic field that bends and elongates the arc, pulling it lengthwise perpendicular to the arc axis. This not only increases the arc length but also induces lateral motion, enabling air cooling to achieve arc extinction.The other method involves the
Echo
09/02/2025
Working Principle and Arc Extinction Mechanism of Magnetic Blowout Device in DC Circuit Breakers
The arc extinguishing system of a DC circuit breaker is crucial for the safe operation of equipment, as the arc generated during current interruption can damage contacts and compromise insulation.In AC systems, the current naturally passes through zero twice per cycle, and AC circuit breakers take full advantage of these zero-crossing points to extinguish the arc.However, DC systems lack natural current zero crossings, making arc extinction significantly more difficult for DC circuit breakers. T
Felix Spark
09/02/2025
Related Products
  • DNH50-400~630A DC isolation switch
  • epoxy resin contact box
  • IEEE Type Rear Connector
  • Isolating Switch DNH8(HGL)/H Series Operation Behind the Cabinet – Load Disconnector
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.