Fuse Maintenance & Replacement: Safety and Best Practices

James
Field: Electrical Operations
China

1. Fuse Maintenance

Fuses in service should be regularly inspected. The inspection includes the following items:

  • Load current should be compatible with the rated current of the fuse element.

  • For fuses equipped with a fuse blown indicator, check whether the indicator has actuated.

  • Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact.

  • Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge.

  • Listen for any internal discharge sounds within the fuse.

If any abnormalities are found during inspection, they should be corrected promptly to ensure safe and reliable operation of the fuse.

2. Safety Precautions When Replacing Fuse Elements

After a fuse element blows, first identify the cause and rectify the fault before replacement. The cause—short circuit or overload—can be determined by examining the condition of the blown fuse.

  • Overload indication:
    Little or no audible sound when blowing; the fuse element melts at only one or two locations. In stepped-section fuses, only the narrow section melts. No charring or burning inside the fuse tube.

  • Short circuit indication:
    Loud explosion when blowing; extensive melting or fragmentation of the fuse element; visible charring or burning inside the fuse tube.

Once the cause is identified, locate and eliminate the fault accordingly.

When replacing the fuse element:

  • Select a replacement with specifications matching the load characteristics and circuit current.

  • Always de-energize the circuit before replacement to prevent electric shock.

Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.