Fault Phenomenon
A power distribution system fault occurred in a customer's server room, resulting in damage to some IT equipment and instruments. Upon receiving the feedback, our company's engineers immediately rushed to the site to inspect the power distribution system and analyze the cause of the fault.
Fault Inspection
The server room uses a three-phase five-wire power supply system. Two three-phase input, three-phase output UPS units (without output isolation transformers) are operating in parallel to power the IT equipment in the room. Both the UPS input and output circuit breakers are controlled using 4-pole (4P) breakers.
Upon inspection of the damaged IT equipment, it was found that all affected devices and instruments were connected to the load side of the UPS output phase C, while equipment connected to phases A and B were operating normally. Further inspection revealed that the neutral wire (zero line) on the UPS input circuit breaker was loose, causing the neutral line to become disconnected (floating) on the downstream side of the UPS.
Fault Analysis
In a three-phase five-wire power supply system, when the neutral line is broken, single-phase loads lose their return path, creating phase voltage at the break point, which poses a risk to personal safety. If the three-phase loads are unbalanced, the neutral point will shift, causing the voltage on each phase to either increase or decrease. According to the principle of voltage division in a series circuit, because phase C had a lighter load, it acquired the highest voltage, approaching the 380V line voltage, which led to the destruction of equipment on that phase.
Severe three-phase load imbalance, combined with overheating of the distribution system circuit breakers and loose wiring terminals, created a latent fault that was not promptly eliminated. This led to poor contact on the neutral line, causing sparking, heating, oxidation, and ultimately complete disconnection.
Additionally, the use of 4P circuit breakers for both UPS input and output means that when the UPS input breaker is opened (for example, during battery discharge maintenance), the neutral line is also cut off, which can similarly cause equipment failure.
Summary
The server room's power distribution system requires regular inspection and maintenance by qualified personnel in the following aspects:
Hello! I'm Leon, with 20 years of extensive experience in the power industry. My expertise spans from power distribution equipment to grid operations and maintenance, grounded in robust hands-on and theoretical knowledge. Currently, I focus on sharing insights into electrical equipment fault diagnosis, demystifying complex technical challenges through accessible explanations. I welcome collaboration with industry peers and enthusiasts to collectively explore the intricacies of the power sector.