Power Factor Meters | Electrodynamometer Type Power Factor Meter

03/27/2024

What Are The Power Factor Meters

Before we introduce various types of power factor meters it is very essential to understand what are the needs of power factor meter? Why we do not directly calculate power factor in an AC circuit just by dividing the power with product of current and voltage because these readings can be easily obtained from wattmeter, ammeter and voltmeter. Obviously there various limitations of using this method as it may not provide high accuracy, also chances of increment of error is very high. Therefore this method is not adopted in industrial world. Measurement of power factor accurately is very essential everywhere.
In power transmission system and distribution system we measure power factor at every station and
electrical substation using these power factor meters.Power factor measurement provides us the knowledge of type of loads that we are using and helps in calculation of losses happening during the power transmission system and distribution.

Hence we need a separate device for calculating the power factor accurately and more precisely.
General construction of any power factor meter circuit include two coils namely pressure coil and current coil. Pressure coil is connected across the circuit while current coil is connected such that it can carry circuit current or a definite fraction of current. By measuring the phase difference between the voltage and current the electrical power factor can be calculated on suitable calibrated scale. Usually the pressure coil is splits into two parts namely inductive and non-inductive part or pure resistive part. There is no requirement of controlling system because at equilibrium there exist two opposite forces which balance the movement of pointer without any requirement of controlling force.

Now there are two types of power factor meters-

  1. Electrodynamometer type

  2. Moving iron type.

Let us study electrodynamometer type first.

Electrodynamometer Type Power Factor Meter

In electrodynamometer type power factor meter there are further two types on the basis of supply voltage

  1. Single phase

  2. Three phase.

The general circuit diagram of single phase electrodynamometer power factor meter is given below.
power factor meter

Now the pressure coil is split into two parts one is purely inductive another is purely resistive as shown in the diagram by resistor and inductor. At present the reference plane is making an angle A with coil 1. And the angle between both the coils 1 and 2 is 90o. Thus the coil 2 is making an angle (90o + A) with the reference plane. Scale of the meter is properly calibrated as shown the value values of cosine of angle A. Let us mark the electrical resistance connected to coil 1 be R and inductor connected to coil 2 be L. Now during measurement of power factor the values of R and L are adjusted such that R = wL so that both coils carry equal magnitude of current. Therefore the current passing through the coil 2 is lags by 90o with reference to current in coil 1 as coil 2 path is highly inductive in nature.
Let us derive an expression for deflecting torque for this power factor meter. Now there are two deflecting torques one is acting on the coil 1 and another is acting on the coil 2. The coil winding are arranged such that the two torques produced, are opposite to each other and therefore pointer will take a position where the two torques are equal. Let us write a mathematical expression for the deflecting torque for coil 1-

Where M is the maximum value of mutual inductance between the two coils,
B is the angular deflection of the plane of reference.
Now the mathematical expression for the deflecting torque for coil 2 is-

At equilibrium we have both the torque as equal thus on equating T1=T2 we have A = B. From here we can see that the deflection angle is the measure of phase angle of the given circuit. The phasor diagram is also shown for the circuit such that the current in the coil 1 is approximately at an angle of 90o to current in the coil 2.
vector diagram of power factor meter
Given below are some of the advantages and disadvantages of using electrodynamic type power factor meters.

Advantages of Electrodynamic Type Power Factor Meters

  1. Losses are less because of minimum use of iron parts and also give less error over a small range of frequency as compared to moving iron type instruments.

  2. They high torque is to weight ratio.

Disadvantages of Electrodynamic Type Power Factor Meters

  1. Working forces are small as compared to moving iron type instruments.

  2. The scale is not extended over 360o.

  3. Calibration of electrodynamometer type instruments are highly affected by the changing the supply voltage frequency.

  4. They are quite costly as compared to other instruments.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
What losses occur during operation of the transformer? How to reduce losses?
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Cable Fault Detection, Testing, Location and Repair
Cable Fault Detection, Testing, Location and Repair
I. Methods for Cable Testing and Inspection:Insulation Resistance Test: Use an insulation resistance tester to measure the insulation resistance value of the cable. A high insulation resistance value indicates good insulation, while a low value may suggest insulation problems requiring further investigation.Voltage Withstand Test: Apply a high-voltage test using a high-voltage tester to verify whether the cable can withstand high voltage under its rated operating conditions. Under normal circums
08/29/2025
Cable Quality Inspection and Cable Detection & Testing
Cable Quality Inspection and Cable Detection & Testing
Power cable quality inspection and cable testing are conducted to ensure that the cable's quality and performance meet specified requirements, thereby guaranteeing the safe and stable operation of power systems. Below are some common contents of power cable quality inspection and cable testing:Visual Inspection: Check the cable surface for physical defects such as damage, deformation, or scratches to ensure the cable's exterior is intact.Dimensional Measurement: Measure dimensional parameters su
08/29/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!