Online GIS PD monitoring system according to IEC61850 protocol

This article covers effective methods for GIS partial discharge detection (UHF, ultrasonic), key monitored data, system components (sensors, preprocessing, IED), signal flow, communication, and IEC 61850-compliant structure.

Edwiin
Field: Power switch
10Year<
China
Add us on Google

Online GIS PD monitoring system according to IEC61850 protocol

Partial Discharge (PD) Detection in GIS

Both UHF (Ultra-High Frequency) and ultrasonic methods are effective for detecting partial discharges (PD) in Gas-Insulated Switchgear (GIS), each with distinct advantages:

  • UHF Method: Detects PD pulses via high-frequency electromagnetic waves generated by PD activity within GIS.

  • Ultrasonic Method: Identifies ultrasonic waves produced by bubble shocks caused by PD.

Key Monitoring Data

The main data monitored by a GIS PD monitoring system includes:

  • UHF PD signals

  • Ultrasonic PD signals

  • Transformer voltage signals

The online monitoring system collects these signals and generates alarm information based on the GIS&rsquo;s operational status.

System Composition

A GIS PD monitoring system comprises three core components:

  • Sensors: Capture PD-related signals.

    • UHF PD sensors detect electromagnetic signals.

    • Ultrasonic sensors measure acoustic signals.

  • Data Preprocessing System: Conditions and prepares signals for analysis.

  • PD Monitoring IED (Intelligent Electronic Device): Processes, stores, and displays data at the bay level.

Signal Flow and Communication

  • Process Level: UHF and ultrasonic sensors acquire electrical and acoustic signals, which are conditioned and transmitted to the PD monitoring IED.

  • Bay Level: The IED stores, displays, and processes data. Specific communication service mapping (per IEC 61850) defines network transmission standards for sampled values between the process and bay levels.

  • Station Level: Data is reported from the bay level to the station level via predefined communication services for centralized monitoring.

System Structure

The figure illustrates the architecture of a GIS PD monitoring system compliant with IEC 61850 standards.